ES-7808-D Rev.2
R7FN-YV2
Remote I/O R7 Series
FLEX NETWORK I/O MODULE
(2 points DC voltage output, isolated)
Functions & Features
• 2 points DC voltage output module for FLEX NETWORK
• Output range can be selected with the front DIP switches for all channels.
• Easy parameter setting of individual channels with the configurator software
FLEX NETWORK is registered trademark of Digital Electronics Corporation in Japan.
MODEL: R7FN–YV2-R[1]
ORDERING INFORMATION
• Code number: R7FN-YV2-R[1]
Specify a code from below for [1].
(e.g. R7FN-YV2-R/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
I/O TYPE
YV2
: DC voltage output, 2 points
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[1] OPTIONS
blank
: none
/Q
: Options other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-7808-YV2)
RELATED PRODUCTS
• PC configurator software (model: R7CON)
The configurator software is downloadable at our web site.
A dedicated cable is required to connect the module to the PC. Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.
• Screen editor software (model: GP-Pro EX)
Screen editor software GP-Pro EX (Ver.2.70 or higher) is available.
For versions between 2.60 and 2.70, the driver must be installed. The driver is downloadable at Digital Electronics Corporation's web site.
http://www.proface.co.jp/
GENERAL SPECIFICATIONS
Connection:
M3 separable screw terminal (torque 0.5 N·m)
Solderless terminal
: Refer to the drawing at the end of the section.
•
Communication cable
Recommended manufacture
: Japan Solderless Terminal MFG.Co.Ltd
Applicable wire size
: 0.2 to 0.5 mm
2
(AWG 26 to 22)
•
Others
Recommended manufacture
: Japan solderless terminal MFG.Co.Ltd, Nichifu Co.,ltd
Applicable wire size
: 0.25 to 1.65 mm
2
(AWG 22 to 16)
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (gray)
Isolation
: Output 0 to output 1 to FLEX NETWORK to power to FG
Zero adjustments
: Configurable via R7CON
Span adjustments
: Configurable via R7CON
Output range
: Selectable with the front DIP SW or configurable via R7CON
Output at the loss of communication
:
Output hold (*), Output clear
Selectable with the front DIP SW
(*) factory default setting
Status indicator LED
: PWR, RUN
(Refer to the instruction manual)
■Recommended solderless terminal
FLEX NETWORK COMMUNICATION
Communication configuration
: 1: N
Connection method
: Multi-drop Connection
Communication method
: Cyclic Time Division, half-duplex
Communication I/F
: Differential, pulse transfer isolation
Error Check
: Format, bit, CRC-12 verification
Max. Number of Nodes
: 63 (1008 I/O points)
Required node
: 2
Network cable
: Pro-face’s following cable
FN-CABLE2010-31-MS (10 m)
FN-CABLE2050-31-MS (50 m)
FN-CABLE2200-31-MS (200 m)
Transmission distance
: 12 Mbps: 100 meters (328 ft)(*)
6 Mbps: 200 meters (656 ft)
(*) Factory default setting
Station address
: Rotary switch
(Refer to the instruction manual)
Terminating resistor
: Built-in
OUTPUT SPECIFICATIONS
■
Narrow Span voltage
Output range
: -1 – +1 V DC, 0 – 1 V DC, -0.5 – +0.5 V DC
Load resistance
: 100 kΩ min.
■
Wide Span voltage
Output range
: -10 – +10 V DC (*), -5 – +5 V DC, 0 – 10 V DC,
0 – 5 V DC, 1 – 5 V DC
(*) factory default setting
Load resistance
: 100 kΩ min.
■
Operational range
Except -10 to +10 V DC
: -15 to +115 % of output range
-10 to +10 V DC
: Approx. -11.5 to +11.5 V DC
INSTALLATION
Current consumption
•
DC
: Approx. 100 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail (35 mm rail)
Weight
: 200 g (0.44 lb)
PERFORMANCE
Conversion accuracy
: ±0.1 %
Data range
: 0 – 10000 of the output range
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Output delay time
: ≤ 250 msec. (0 - 90 %)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (output 0 to output 1 to FLEX NETWORK to power to FG)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
FUNCTIONS
Output hold function:
Output at the loss of communication is selectable from output clear (fix the output at -15 % or approx. -11.5 V) and output hold (last normally received data) with DIP switch.
At the startup, it outputs -15 % or approx. -11.5 V until the communication is established and normal data is received.
EXTERNAL VIEW
CONNECTION DIAGRAMS
TERMINAL ASSIGNMENTS
■OUTPUT TERMINAL ASSIGNMENT
DATA CONVERSION
I/O DATA DESCRIPTIONS
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.