ES-7817 Rev.4

R7G

Remote I/O R7 Series

GATEWAY MODULE

 

MODEL: R7G-SC-S[1]-R[2]

ORDERING INFORMATION

• Code number: R7G-SC-S[1]-R[2]
Specify a code from below for each of [1] and [2].
   (e.g. R7G-SC-SHL-R/Q)
• Specify the specification for option code /Q
   (e.g. /C01)

Module type of network 1

S: Slave

Type of network 1

C: CC-Link

Module type of network 2

S: Slave

[1] Type of network 2

HL: HLS (Hi-speed Link System) Full-duplex
HL1: HLS (Hi-speed Link System) Half-duplex

POWER INPUT

DC Power
R: 24 V DC

[2] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

FUNCTIONS & FEATURES

The Gateway Module for CC-Link and HLS (Hi-speed Link System) connects discrete I/O between the networks each other.  The module hands over 32 point inputs of CC-Link to 32 point outputs of HLS or 32 point inputs of HLS to 32 point outputs of CC-Link.

CAUTION

In this module, the transmission between CC-Link and HLS is not synchronized.  Therefore, if one of the networks read the transmitted data before completion of its update by the other network, the data may be uncertain as 16-bit data.  If the correct 16-bit data is necessary, arrange the host application program.
Refer to the instruction manual.

GENERAL SPECIFICATIONS

Connection
Power supply, CC-Link: Screwless spring terminal
  Applicable wire size: 0.2 - 1.25 mm2
  Stripped length: 10 mm
  Recommended solderless terminal
  AI0,25-10YE 0.25 mm2 (Phoenix Contact)
  AI0,34-10TQ 0.34 mm2 (Phoenix Contact)
  AI0,5-10WH 0.5 mm2 (Phoenix Contact)
  AI0,75-10GY 0.75 mm2 (Phoenix Contact)
  A1-10 1.0 mm2 (Phoenix Contact)
  A1,5-10 1.5 mm2 (Phoenix Contact)
HLS: RJ-45 Connectors
  Recommended cable connector:
  TM21P-88P (Hirose Electric)
  (not included in the package)
Isolation: CC-Link or FG to HLS to power
Station address setting: Rotary switch
(For the detail refer to the instruction manual.)
Transfer rate
CC-Link: Rotary switch
HLS: DIP switch
(For the detail refer to the instruction manual.)
Power indicator LED: Green LED turns on when the power is supplied.
Status indicator LED
CC-Link: Red LEDs indicate communication status.
HLS: Green LEDs indicate communication status.

COMMUNICATION

HLS COMMUNICATION
Network
: Full-duplex or half-duplex
Transmission distance:
12 Mbps: 100 meters (328 ft)
6 Mbps: 200 meters (656 ft)
Network cable:
Full-duplex communication: ZHY262PS, ZHT262PS
Half-duplex communication: ZHY221PS
(Shinko Seisen Industry Co., Ltd.)
Data allocation: 2
Terminating resistor: Built-in (Selected with the DIP SW; factory setting: disabled)
CC-LINK COMMUNICATION
CC-Link
:Ver.1.10
Network cable: CC-Link cable designated by Mitsubishi Electric
Station Type: Remote I/O
Data allocation: 2 (1 station x 2)
Terminating resistor: Built-in (Selected with the DIP SW; factory setting: disabled)

INSTALLATION

Power input
DC:
Operational voltage range 24 V DC ±10 %;
ripple 10 %p-p max., approx. 1.8 W
Operating temperature: -10 to +55°C (14 to 131°F)
Storage temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail
Weight: 150 g (0.33 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @1 minute
(CC-Link or FG to HLS to power)

EXTERNAL VIEW

CONNECTION DIAGRAMS

INDICATOR LED

DATA ALLOCATION

I/O DATA DESCRIPTIONS

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM