ES-7779-J Rev.3
R7I4DECT-1-DC32A
Remote I/O R7I4D Series
EtherCAT I/O MODULE
(NPN transistor output, 32 points each, e-CON connector)
Functions & Features
• 32 points NPN transistor output module for EtherCAT
EtherCAT® is a registered trademark and patented technology, licensed by Beckhoff Automation GmbH, Germany.
MODEL: R7I4DECT-1-DC32A-R[1]
ORDERING INFORMATION
• Code number: R7I4DECT-1-DC32A-R[1]
Specify a code from below for [1].
(e.g. R7I4DECT-1-DC32A-R/D1/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
TERMINAL BLOCK
1
: Tension clamp terminal block for power supply
RJ-45 Modular jack for communication
e-CON connector for I/O
I/O TYPE
DC32A
: NPN transistor output, 32 points
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[1] OPTIONS (multiple selections)
Wire Breakdown Detection
Blank
: With
/D1
: Without
Other Options
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-7779-DC32)
RELATED PRODUCTS
• PC configurator software (model: R7CFG)
• ESI file
The configurator software and ESI files are downloadable at our web site.
Use a commercially available Mini-B USB cable to connect the unit to a PC.
GENERAL SPECIFICATIONS
Connection
EtherCAT
: RJ-45 Modular Jack
Power & Sensor excitation
: Separable screwless spring
terminal
Output:
e-CON connector
Housing material
: Flame-resistant resin (gray)
Isolation
: Output or sensor excitation to EtherCAT or FE to power
Output at the loss of communication
: Configurable via R7CFG
Status indicator LED
: PWR, RUN, ERR, L/A IN, L/A OUT
(Refer to the instruction manual.)
Discrete Output status indicator LED
: Green LED turns on with Output ON
EtherCAT COMMUNICATION
Standard
: IEEE 802.3u
Transmission type
: 100BASE-TX
Transmission speed
: Full-duplex 100 Mbps
Transmission media
: 100BASE-TX (STP cable; Category 5e)
Maximum internode length
: 100 meters
Fixed address:
Set with rotary switches
(The master must support MDP.)
OUTPUT SPECIFICATIONS
Common
: Negative common (NPN) per 32 points
Maximum outputs applicable at once:
No limit (at 24 V DC)
Sensor Excitation
: 24 V DC ±10 %, ripple 5 %p-p max.,
≤ 5 A (including discrete output load charge); rated current
8 A
Rated output current
: 0.2 A per point, 3.2 A per common
Residual voltage
: ≤ 1.2 V
Leakage current
:
With wire breakdown detection: ≤ 0.7 mA
Without wire breakdown detection: ≤ 0.1 mA
ON delay
: ≤ 0.2 msec.
OFF delay
: ≤ 0.5 msec.
Overload current protection function
: Turns OFF the outputs when overcurrent is detected
Overheat protection function
: Turns OFF the outputs when overheat is detected
Diagnostic function
: When the overcurrent, overheat and open load (disconnection) are detected, notifies to the status bit of upper input area. Refer to the users manual for details
Note: Status is disabled with option code: /D1 (without wire breakdown detection).
(When driving an inductive load, connect a diode in parallel with the load.)
INSTALLATION
Current consumption
•
DC at 24 V DC
: Approx. 55 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Surface or DIN rail (35 mm rail)
Weight
: 180 g (0.40 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute
(output or sensor excitaion to EtherCAT or FE to power)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
FUNCTIONS
■
WIRE BREAKDOWN DETECTION
The function to notifies to the status bit of upper input area in case of open load (disconnection) of discrete output is detected.
Connect output load under 10 kΩ.
Pull-down resister is mounted to detect disconnection so weak leakage current flows even when the output is OFF.
Status bit is disabled and pull-down resister is not mounted with option code: /D1 (withourt wire breakdown detection).
PC CONFIGURATOR
The following parameters can be set with using PC Configurator Software (model: R7CFG)
Refer to the users manual for the R7CFG for detailed operation of the software program.
EXTERNAL VIEW
TERMINAL ASSIGNMENTS
■OUTPUT TERMINAL ASSIGNMENT
RESPONSE TIME
• Output module
Response time is time from when a step (0 to 100%) output signal is received by the communication CPU of the output module (slave) until when its output reaches 90% of the final value.
T
COM
: EtherCAT communication cycle set by the host device (master)
(The cycle is determined in accordance with the system configuration and settings.)
T
OUT
: Output module response time ≤ Delay time of output internal processing (Td) (communication cycle x 1) + 0 msec. (Te) + Delay time of output circuit (Tf)
ex.) When EtherCAT communication cycle: 1 msec. and delay time of output: ON,
Output module responce time(T
OUT
): Delay time of output internal processing (1 msec.) (communication cycle x 1) + 0 msec. + Delay time of output circuit (0.2 msec.) = 1.2 [msec.]
I/O DATA DESCRIPTIONS
EXTERNAL DIMENSIONS unit: mm [inch]
MOUNTING REQUIREMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FE terminal to ground.
Caution: FE terminal is NOT a protective conductor terminal.