Functions & Features
• 16 points PNP discrete input & 16 points NPN transistor output module for HLS
HLS is the abbreviation for “Hi-speed Link System” of Step Technica Co., Ltd.
MODEL: R7K4DH–1–DAC32A-R[1]
ORDERING INFORMATION
• Code number: R7K4DH-1-DAC32A-R[1]
Specify a code from below for [1].
(e.g. R7K4DH-1-DAC32A-R/H/Q)
• Specify the specification for option code /Q
(e.g. /C01)
TERMINAL BLOCK
1
: Tension clamp terminal block for power supply
RJ-45 Modular jack for communication
e-CON connector for I/O
I/O TYPE
DAC32A
: PNP discrete input &
NPN transistor output, 16 points each
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[1] OPTIONS (multiple selections)
Communication Mode
blank
: Full-duplex
/H
: Half-duplex
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
GENERAL SPECIFICATIONS
Connection
HLS
: RJ-45 Modular Jack
Power & Sensor excitation
: Separable screwless spring
terminal
I/O:
e-CON connector
Housing material
: Flame-resistant resin (gray)
Isolation
: Input or output or sensor excitation to HLS to power to FE
Output at the loss of communication
:
Output hold (*), Output clear
Selectable with the front DIP SW
(*) factory default setting
Status indicator LED
: Power (green) turns on while the power is supplied.
Discrete I/O status indicator LED
: Red LED turns on with I/O ON
HLS COMMUNICATION
Communication mode
: Full-duplex or half-duplex
Network cable
Shielded cable
:
Full-duplex communication:
ZHY262PS and ZHT262PS (Shinko Seisen Industry Co., Ltd.)
Half-duplex communication:
ZHY221PS (Shinko Seisen Industry Co., Ltd.)
Dual shielded cable
:
ZHY262PBA (Shinko Seisen Industry Co., Ltd.)
Transmission distance
:
12 Mbps: 100 meters (328 ft)
6 Mbps: 200 meters (656 ft)
3 Mbps: 300 meters (984 ft)
(Configurable with DIP SW; factory setting: 12 Mbps)
Terminating resistor
: Built-in (Selected with the DIP SW; factory setting: disabled)
Status indicator
: Run LED on in normal communication
Station address
: Set with rotary switch
(Refer to the instruction manual for details.)
INPUT SPECIFICATIONS
Common
: Negative common (PNP) per 16 points
Maximum inputs applicable at once:
No limit (at 24V DC)
Sensor excitation
: 24 V DC ±10 %; ripple 5 %p-p max.,
≤ 2 A (including discrete input load charge); rated current 8 A
ON voltage / current
: ≥ 15 V DC (X0 through XF to GND) / ≥ 3.5 mA
OFF voltage / current
: ≤ 5 V DC (X0 through XF to GND) / ≤ 1 mA
Input current
: ≤ 5.5 mA per point at 24 V DC
Input resistance
: Approx. 4.4 kΩ
ON delay
: ≤ 0.5 msec.
OFF delay
: ≤ 0.5 msec.
OUTPUT SPECIFICATIONS
Common
: Negative common (NPN) per 16 points
Maximum outputs applicable at once:
No limit (at 24 V DC)
Sensor Excitation
: 24 V DC ±10 %, ripple 5 %p-p max.,
≤ 2 A (including discrete output load charge); rated current 8 A
Rated output current
: 0.1 A per point, 1.6 A per common
Residual voltage
: ≤ 1.2 V
Leakage current
: ≤ 0.1 mA
ON delay
: ≤ 0.2 msec.
OFF delay
: ≤ 0.5 msec.
Overload current protection function
: Limits the current value when overcurrent is detected
Overheat protection function
: Turns OFF the outputs when overheat is detected
(When driving an inductive load, connect a diode in parallel with the load.)
INSTALLATION
Current consumption
•
DC
: Approx. 95 mA (rated current 8 A)
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Surface or DIN rail (35 mm rail)
Weight
: Approx. 185 g (0.41 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (input or output or sencor excitation to HLS to power to FE)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
TERMINAL ASSIGNMENTS
■I/O TERMINAL ASSIGNMENT
I/O DATA DESCRIPTIONS
EXTERNAL DIMENSIONS unit: mm [inch]
MOUNTING REQUIREMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FE terminal to ground.
Caution: FE terminal is NOT a protective conductor terminal.