ES-8003-A Rev.3

R7K4JML3-E-DAFC64A

Remote I/O R7K4J Series

MECHATROLINK I/O MODULE

(MECHATROLINK-III use, NPN/PNP discrete high-speed input & NPN transistor output, 32 points each, tension clamp terminal block)
Functions & Features
• 32 points NPN/PNP discrete high-speed input & 32 points NPN transistor output for MECHATROLINK-III
 

MODEL: R7K4JML3-E-DAFC64A–R[1]

ORDERING INFORMATION

• Code number: R7K4JML3-E-DAFC64A-R[1]
Specify a code from below for [1].
  (e.g. R7K4JML3-E-DAFC64A-R/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

TERMINAL BLOCK

E: Tension clamp terminal block for power supply
   Connector for MECHATROLINK-III for communication
   Tension clamp terminal block for I/O

I/O TYPE

DAFC64A: NPN/PNP discrete input, 32 points, high-speed &
  NPN transistor output, 32 points

POWER INPUT

DC power
R: 24 V DC
(Operational voltage range: ±10 %; ripple 10 %p-p max.)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

GENERAL SPECIFICATIONS

Connection
 • MECHATROLINK-III: MECHATROLINK-III connector 
 • Power input, I/O: Separable tension clamp terminal
Housing material: Flame-resistant resin (gray)
Isolation: Input to output to MECHATROLINK or FE to power
Output at the loss of communication:
Output hold (*), Output clear
Selectable with the front DIP SW
(*) factory default setting
Status indicator LEDs: PWR, ERR, CON, LNK1, LNK2 (5 LEDs) indicate the module’s operating conditions. (Refer to the instruction manual)
Discrete I/O status indicator LED: Green LED turns on with I/O ON
Read rate: 100(*) / 200 / 400 / 800μsec. / 4 / 8 / 16 / 40 msec. selectable with the front DIP SW
(*) factory default setting

MECHATROLINK-III COMMUNICATION

Baud rate: 100 Mbps
Transmission distance: 6300 m max.
Distance between stations: 100 m max.
Transmission media: MECHATROLINK cable (Model JEPMC-W6013-x-E, Yaskawa Controls Co., Ltd.)
Connector: TYCO AMP Industrial mini I/O connector
Max. number of slaves: 62
(The maximum number of slaves might change depending on the master unit. Refer to the manual of the master unit)
Transmission cycle: 125 µsec., 250 µsec., 500 µsec., 1 – 64 msec. (with 1 msec. increments)
Communication cycle: 125 µsec. through 64 msec.
Applicable profile: Standard I/O profile (cyclic communication)
 Event-driven communication acquiring ID profile (event-driven communication)
Transmission bytes: 16 bytes
Station address: 03H through EFH (set with rotary switches)
Cyclic communication: Available
Event-driven communication: Available
Slave monitoring: None

INPUT SPECIFICATIONS

Common: Positive or negative common (NPN/PNP) per 32 points
Maximum inputs applicable at once: No limit (at 24 V DC)
Rated input voltage: 24 V DC ±10 %; ripple 5 %p-p max.
ON voltage / current: ≥ 15 V DC (input – COM) / ≥ 3.5 mA
OFF voltage / current: ≤ 5 V DC (input – COM) / ≤ 1 mA
Input current: ≤ 5.5 mA per point at 24 V DC
Input resistance: Approx. 4.4 kΩ
ON delay: ≤ 0.2 msec.
OFF delay: ≤ 0.5 msec.

OUTPUT SPECIFICATIONS

Common: Negative common (NPN) per 32 points
Maximum outputs applicable at once: No limit (at 24 V DC)
Rated load voltage: 24 V DC ±10 %, ripple 5 %p-p max.
Rated output current: 0.1 A per point, 3.2 A per common
Residual voltage: ≤ 1.2 V
Leakage current: ≤ 0.1 mA
ON delay: ≤ 0.2 msec.
OFF delay: ≤ 0.5 msec.
Overload current protection function: Limits the current value when overcurrent is detected
Overheat protection function: Turns OFF the outputs when overheat is detected
(When driving an inductive load, connect a diode in parallel with the load.)

INSTALLATION

Current consumption
DC: Approx. 85 mA (Discrete I/O load charge is not included.)
Operating temperature: -10 to +55°C (14 to 131°F)
Storage temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface or DIN rail (35 mm rail)
Weight: 330 g (0.73 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input to output to MECHATROLINK or FE to power)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

TERMINAL ASSIGNMENTS

■I/O TERMINAL ASSIGNMENT
■POWER SUPPLY TERMINAL ASSIGNMENT

MECHATROLINK RELATED COMMANDS

RESPONSE TIME

Response time of discrete input module is the time till when the communication ASIC of the module transmits input data from when input signal is applied to the module.
Response time of discrete output module is the time till when the module output the signal from when output data is received by the communication ASIC of the module.
TCOM: MECHATROLINK-III transmission cycle set at master
(depends on system and configuration)

TINP: Response of input module ≤ Delay of input circuit (Ta, ON delay time or OFF delay time) +  Acquire cycle (Ts) + input internal processing delay time (Tc, two transmission cycle)


TOUT: Response of output module ≤ Output internal processing delay time (Td, one minimum transmission cycle the unit can handle) + Conversion time (Te) + Delay of output circuit (Tf, ON delay time or OFF delay time)


E.g. 1: R7K4JML3-E-DAFC64A: Acquire cycle: 0.1 msec., MECHATROLINK-III transmission cycle: 0.125 msec., discrete input ON
  Response of input module (TINP): Delay of input circuit (0.2 msec.) + Acquire cycle (0.1 msec.) + input internal processing delay time (0.125 msec. x 2) = 0.55 [msec.]

E.g. 2: R7K4JML3-E-DAFC64A: MECHATROLINK-III transmission cycle: 0.5 msec., discrete output OFF
Response of output module (T0UT): Output internal processing delay time (0.125 msec.) + Delay of output circuit (0.5 msec.) 
= 0.625 [msec.]

I/O DATA DESCRIPTIONS

EXTERNAL DIMENSIONS unit: mm [inch]

MOUNTING REQUIREMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

Note: In order to improve EMC performance, bond the FE terminal to ground.
Caution: FE terminal is NOT a protective conductor terminal.