ES-7815 Rev.6
R7LWTU
Remote I/O R7 Series
MULTI POWER MODULE
(Clamp-on current sensor CLSE, LonWorks)
ORDERING INFORMATION
• Basic module: R7LWTU-2[1]1-AD4[2]
Specify a code from below for each of [1] and [2].
(e.g. R7LWTU-221-AD4/Q)
• Specify the specification for option code /Q
(e.g. /C01)
• Extension module: R7LWTU-EA8[1]
Specify a code from below for [1].
(e.g. R7LWTU-EA8/Q)
• Specify the specification for option code /Q
(e.g. /C01)
MODEL: R7LWTU-2[1]1-AD4[2]
CONFIGURATION
2
: Single phase / 2-wire and 3-wire,
3-phase / 3-wire and 4-wire
[1] NO. OF SYSTEMS
1
: 1 system, Di / Pi x 4 (internal power 5 V)
(no connection with extension module)
2
: 2 systems
INPUT
1
: 240 V AC / CLSE
POWER INPUT
Universal
AD4
: 100 – 240 V AC / 110 – 240 V DC (universal)
(Operational voltage range 85 - 264 V AC, 50 - 60 Hz /
99 - 264 V DC, ripple 10 %p-p max.)
[2] OPTIONS
blank
: none
/Q
: With options (specify the specification)
EXTENSION MODULE: R7LWTU-EA8[1]
I/O TYPE
EA8
: Di / Pi, 8 points (internal power 5 V)
[1] OPTIONS
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
FUNCTIONS & FEATURES
The R7LWTU is a Multi Power Module for LonWorks.
The R7LWTU uses clamp-on current sensors, there is no need of current transformers.
Current sensors are easy to install in existing systems. Wide input range of 5 to 600 A is availabe.
All measured values, counter values, display mode, setting data are stored in the non-volatile memory when power is off.
A ‘basic’ module can be attached with an ‘extension’ module (except R7LWTU-211-AD4)because of this, it is able to use it as 2-circuit power and 8 discrete inputs module.
RELATED PRODUCTS
• PC configurator software (model: PMCFG)
• XIF File (Device Interface File)
XIF file is used to define a LonWorks device when programmed on LonMaker.
The XIF files and Software are downloadable at our web site.
To connect the module to a PC a dedicated cable is required (refer to our web site or instruction manual).
• Clamp-on current sensor (model: CLSE)
The clamp-on current sensors, not included in this product package, must be ordered separately. Required number depends upon the system configuration.
GENERAL SPECIFICATIONS
Connection:
M3 separable screw terminal (torque 0.5 N·m)
Solderless terminal
: Refer to the drawing at the end of the section.
Recommended manufacturer
: Japan Solderless Terminal MFG.Co.Ltd, Nichifu Co.,ltd
Applicable wire size
: 0.25 to 1.65 mm
2
(AWG 22 to 16)
Configuration
: Single phase/2-wire and 3-wire, 3-phase/3-wire balanced/unbalanced load, 3-phase/4-wire balanced/unbalanced load
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (gray)
Isolation
: Sensor core to sensor output or current input or voltage input to discrete input to LonWorks or FG to power
Measured variables
Voltage
: 1-N, 2-N, 3-N, 1-2, 2-3, 3-1
Current
: 1, 2, 3, N
Active / reactive
: Σ
Power factor
: Σ
Frequency
Active energy
: Incoming
Reactive energy
: Incoming
Status indicator LED
: PWR
■Recommended solderless terminal size - M3
LonWorks COMMUNICATION
Neuron Chip
: FT3150
(NeuronID printed in numbers and bar code [peel-off code 39 format])
Transceiver
: FT-X1 (equivalent to FTT10A)
Transmission speed
: 78 kbps
Twisted-pair cable
Distance, free topology
: 500 meters
Max. 64 nodes/channel
LNS
: Ver. 3.0 Service Pack 8 or higher
Status indicator
: ONLINE, ERR, TX/RX, SVCE (service)
Operation switch
: Service, reset
INPUT SPECIFICATIONS
Frequency
: 50 / 60 Hz (45 – 65 Hz)
•
Voltage Input
Rated voltage
Line-to-line (delta voltage): 240 V
Line-neutral (phase voltage): 138 V (three-phase/4-wire)
Consumption VA
: ≤ U
LN
2
/ 300 kΩ / phase
Overload capacity
: 200 % of rating for 10 sec., 120 % continuous
Selectable primary voltage range
: 50 – 400 000 V
•
Current Input
CLSE-R5
: 0 – 5 A AC
CLSE-05
: 0 – 50 A AC
CLSE-10
: 0 – 100 A AC
CLSE-20
: 0 – 200 A AC
CLSE-40
: 0 – 400 A AC
CLSE-60
: 0 – 600 A AC
Overload capacity
: 120 % continous, 500 % for 10 sec.
(Note: Use for the circuit not exceed 480 V)
Selectable primary current range
: 1 – 20 000 A (only with CLSE-R5, refer to the configurator settings)
Operational range
Current
: 0 – 120 % of the rating
Voltage
: 10 – 120 % of the rating
Active/reactive power
: ±120 % of the rating
Frequency
: 45 – 65 Hz
Power factor
: ±1
■
Discrete input
Common
: Negative common
Maximum frequency
: 10 Hz
Minimum pulse width
: 50 msec.
Totalized pulse range
: 0 - 9 999 999
Count at overflow
: Reset and restart at ‘0.’
Detecting voltage/current
: 5 V DC / 5 mA approx.
Detecting levels
: ≤ 5 kΩ / ≤ 2 V for ON;
≥ 100 kΩ / 4 V for OFF
Operation mode
: Discrete and pulse counter
INSTALLATION
Power consumption
•
AC
:
Basic module: < 5 VA
Basic with extension module: < 6 VA
•
DC
:
Basic module: < 1.5 W
Basic with extension module: < 2 W
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail
Weight
:
Basic module
: 200 g (0.44 lb)
Extension module
: 90 g (0.2 lb)
PERFORMANCE
Accuracy
(at 10 - 35°C or 50 - 95°F, 45 – 65 Hz)
Add the accuracy of the current sensor for overall values.
Voltage
: ±0.5 % of the rating
Current
: ±0.5 % of the rating
Power
: ±1.0 % of the rating
Power factor
: ±1.5 %
Energy
: ±2.0 % of the rating (range 5 - 100 %, PF 1)
Frequency
: ±0.1 % of the rating
The described accuracy levels are ensured at the input 1 % or more for phase 2 current with 3-phase/3-wire unbalanced load and for neutral current with 1-phase/3-wire.
Data update period
:
Frequency
: ≤ 1 sec.
Other
: ≤ 500 msec.
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
:
2000 V AC @ 1 minute (current input or voltage input or discrete input to LonWorks or FG to input power)
1000 V AC @ 1 minute (current input or voltage input to discrete input)
EXTERNAL VIEW
■ BASIC MODULE
■ EXTENSION MODULE
TERMINAL CONNECTIONS
CONNECTION DIAGRAMS
TERMINAL ASSIGNMENTS
■ BASIC MODULE
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
■ BASIC MODULE
■ EXTENSION MODULES
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM