ES-7032 Rev.1

R80DCT16A2

Remote I/O R80 Series

NPN TRANSISTOR OUTPUT MODULE, 16 points

(tension clamp terminal block)
Functions & Features
• 16 channels for discrete output, compact size remote I/O module
• 18 pins tension clamp connector

MODEL: R80DCT16A2[1]

ORDERING INFORMATION

• Code number: R80DCT16A2[1]
Specify a code from below for [1].
  (e.g. R80DCT16A2/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating

RELATED PRODUCTS

• PC configurator software (model: R80CFG)
Downloadable at our web site.
For connecting to PC, use commercially available Mini-B type USB cable. (provided by user)

GENERAL SPECIFICATIONS

Connection
 Output: Separable tension clamp terminal
 Internal bus, internal power, excitation power supply: Connected to internal bus connector
Isolation: Output or exc. supply to internal bus or internal power
Module address: With DIP switch
Terminating resistor: Built-in (DIP Switch, default: disable)
Status indicator: Bi-color (red/green) LED; Refer to the instruction manual.
Discrete output status indicators: Green LED; Refer to the instruction manual.

OUTPUT SPECIFICATIONS

Module type: Discrete output, 16 points
Common: Negative common (NPN) per 16 points
Maximum outputs applicable at once: No limit (at 24 V DC)
Number of output: 16 points
Rated load voltage: 24 V DC ±10 %
Rated output current: 0.1 A per point, 1.6 A per common
Residual voltage: ≤ 0.5 V
Leakage current: ≤ 0.1 mA
ON delay: ≤ 0.2 msec.
OFF delay: ≤ 0.5 msec.
With shortcircuit protection
With overheat protection
(When driving an inductive load, connect a diode in parallel with the load.)
Output when communication is lost:
Hold output (the previous output received normally is held)
Clear output (output is fixed to OFF)
(Settable with PC configurator)
(Factory setting: Hold output)

INSTALLATION

Max. current consumption: 160 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail
Weight: 110 g (0.24 lb)

PERFORMANCE

Power output (output connector): Rated current 3 A DC (rated current 3 A for internal fuse (slow blow fuse i2t (A2sec.) max. 5.04)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(output or exc. supply to internal bus or internal power to ground)

STANDARDS & APPROVALS

EU conformity:
EMC Directive  
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

WIRING

• OUTPUT CONNECTOR
Unit side connector:
MC1,5/18-GF-3,5 (Phoenix Contact)
Cable side connector: FMC1,5/18-STF-3,5 (Phoenix Contact) (included in the package)
Applicable wire size: 0.2 − 1.5 mm2; stripped length 10 mm
Recommended solderless terminal
 • AI0,25−10YE 0.25 mm2 (Phoenix Contact)
 • AI0,34−10TQ 0.34 mm2 (Phoenix Contact)
 • AI0,5−10WH 0.5 mm2 (Phoenix Contact)
 • AI0,75−10GY 0.75 mm2 (Phoenix Contact)
 • A1−10 1.0 mm2 (Phoenix Contact)
 • A1,5−10 1.5 mm2 (Phoenix Contact)

OPERATING MODE SETTING

• Module address setting
(*) Factory setting
Note) Be sure to set unused SW 1-5 thtough 1-8 to OFF.
Module address: Selectable between 0 and 15, with DIP switch 1-1 to 4.

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM