ES-7034 Rev.1

R80DCT4D

Remote I/O R80 Series

RELAY OUTPUT MODULE

(4 points, Tension clamp terminal block)
Functions & Features
• 4 channels for relay output, compact size remote I/O module
• 8 pins tension clamp connector

MODEL: R80DCT4D[1]

ORDERING INFORMATION

• Code number: R80DCT4D[1]
Specify a code from below for [1].
  (e.g. R80DCT4D/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating

RELATED PRODUCTS

• PC configurator software (model: R80CFG)
Downloadable at our web site.
For connecting to PC, use commercially available Mini-B type USB cable. (provided by user)

GENERAL SPECIFICATIONS

Connection
 Output: Separable tension clamp terminal
 Internal bus, internal power: Connected to internal bus connector
Housing material: Flame-resistant resin (black)
Isolation: Output 1 to output 2 to output 3 to output 4 to internal bus or internal power to exc. supply to FE
Module address: With DIP switch
Terminating resistor: Built-in (DIP Switch, default: disable)
Status indicator: Bi-color (red/green) LED; Refer to the instruction manual.

OUTPUT SPECIFICATIONS

Output: Relay contact 4 points
Output common: Common per one point (4 terminals)
Maximum load current: 2 A per point
Rated load: 250 V AC @2 A (cos ø = 1)
              30 V DC @2 A (resistive load)
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 500 VA or 60 W
Minimum load: 5 V DC @1 mA
Mechanical life: 2 × 107 cycles (rate 300/min.)
When driving an inductive load, external contact protection and noise quenching are recommended.
ON delay: ≤ 10 msec.
OFF delay: ≤ 10 msec.

INSTALLATION

Current consumption: 110 mA
Exc. supply current consumption: 25 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Storage temperature: -10 to +55°C (14 to +131°F)
Operating humidity: 10 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail
Weight: 115 g (0.25 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength:
  1500 V AC @ 1 minute (output 1 to output 2 to output 3 to output 4 to internal bus or internal power to exc. supply to to ground)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
Low Voltage Directive 
  EN 61010-1, EN 61010-2-201
  Measurement Category II (output)
  Pollution Degree 2
Output to exc. supply or internal bus or internal power: Basic insulation (250 V)
RoHS Directive

EXTERNAL VIEW

CONNECTION DIAGRAMS

Tension clamp terminal block
Unit side connector: MSTB2,5/8-GF-5,08 (Phoenix Contact)
Cable side connector: FKC2,5/8-STF-5,08 (Phoenix Contact)
Applicable wire size: 0.2 − 2.5 mm2
Stripped length: 10 mm
Recommended solderless terminal
• AI0,25−10YE 0.25 mm2 (Phoenix Contact)
• AI0,34−10TQ 0.34 mm2 (Phoenix Contact)
• AI0,5−10WH 0.5 mm2 (Phoenix Contact)
• AI0,75−10GY 0.75 mm2 (Phoenix Contact)
• AI1−10RD 1.0 mm2 (Phoenix Contact)
• AI1,5−10BK 1.5 mm2 (Phoenix Contact)
• AI2,5−10BU 1.5 mm2 (Phoenix Contact)

OPERATING MODE SETTING

(*) factory default setting
Note: Be sure to set unused SW1-5 to 8 and 2-2 to OFF.

TERMINAL ASSIGNMENTS

DIMENSIONS unit: mm (inch)

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM