ES-7029 Rev.1
R80FST4NJ
Remote I/O R80 Series
DC VOLTAGE/CURRENT INPUT MODULE, 4 points
(built-in excitation, 4 points, non-isolated, Tension clamp terminal block)
Functions & Features
• 4 points DC voltage input and DC current input remote I/O module
• Accepts direct input from power output as sensor power and outputs from terminals
• Non-isolated
• Tension clamp terminal block
MODEL: R80FST4NJ[1]
ORDERING INFORMATION
• Code number: R80FST4NJ[1]
Specify a code from below for [1].
(e.g. R80FST4NJ/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
RELATED PRODUCTS
• PC configurator software (model: R80CFG)
Downloadable at our web site.
For connecting to PC, use commercially available Mini-B type USB cable. (provided by user)
GENERAL SPECIFICATIONS
Connection
Input
: Separable tension clamp terminal
Internal bus, internal power
: Connected to internal bus connector
Housing material
: Flame-resistant resin (black)
Isolation
: Input 1-4 or excitation supply to internal bus or internal power to FE
Input type
: Configuration mode that selectable between current input and voltage input and available to configure scaling individually for each 4 points with configurator software (model: R80CFG) is available.
Module address
: With DIP switch
Terminating resistor
: Built-in (DIP Switch, default: disable)
Status indicator
: Bi-color (red/green) LED; Refer to the instruction manual.
Input status indicators
: Red LED; Refer to the instruction manual.
INPUT SPECIFICATIONS
■
DC Voltage
:
Input range
: -10 – +10 V DC
Input setting value
: Available to set in the input range
Operational range
: -5 - +105 % (% of input setting value)
Input resistance:
≥ 1 MΩ
■
DC Current
:
Input range
: -20 – +20 mA DC
Input setting value
: Available to set in the input range
Operational range
: -5 - +105 % (% of input setting value)
Input resistance
: 50 Ω (1/4 W)
Factory default (Input type and input setting value):
Voltage input, input range -10 - +10 V DC for all 4 points.
INSTALLATION
Current consumption:
120 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -10 to +55°C (14 to +131°F)
Operating humidity
: 10 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail
Weight
: 120 g (0.26 lb)
PERFORMANCE
Conversion accuracy
(in percentage of input range)
Voltage input
:±0.05 %
Current input
:±0.1 %
Conversion accuracy is inversely proportional to input span.
Conversion rate
: 1 msec.
Input circuit time constant
: Approx. 1 msec.
Data range
: 0 – 10000 of the input range
(Scaling of converted data is configurable with the configurator software)
Power output (input
connector
)
: Rated current 0.5 A DC per channel (rated current 3 A for internal fuse (slow blow fuse i
2
t (A
2
sec.) max. 5.04); Total: 1 A DC
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute
(input1-4 or exc. supply to internal bus or internal power to ground)
CALCULATION EXAMPLES OF CONVERSION ACCURACY
■
Voltage input:
For input setting value 1 - 5 V DC
Conversion accuracy = Input range span (20 V) ÷ input setting value span (4 V) × 0.05 (%) = 0.25 (%)
■
Current input:
For input setting value 4 - 20 mA DC
Conversion accuracy = Input range span (40 mA) ÷ input setting value span (16 mA) × 0.1 (%) = 0.25 (%)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
CONNECTION DIAGRAMS
■
Tension clamp terminal block
Unit side connecto
r: MC1,5/16-GF-3,5 (Phoenix Contact)
Applicable connector
: FMC1,5/16-STF-3,5 (Phoenix Contact)
Applicable wire size
: 0.2 − 1.5 mm
2
Stripped length
: 10 mm
Recommended solderless terminal
• AI0,25−10YE 0.25 mm
2
(Phoenix Contact)
• AI0,34−10TQ 0.34 mm
2
(Phoenix Contact)
• AI0,5−10WH 0.5 mm
2
(Phoenix Contact)
• AI0,75−10GY 0.75 mm
2
(Phoenix Contact)
• A1−10 1.0 mm
2
(Phoenix Contact)
• A1,5−10 1.5 mm
2
(Phoenix Contact)
OPERATING MODE SETTING
(*) factory default setting
Note: Be sure to set unused SW1-5 to 8 to OFF.
TERMINAL ASSIGNMENTS
EXTERNAL DIMENSIONS unit: mm [inch]