ES-7026 Rev.1
R80NCIT1
Remote I/O R80 Series
POWER/NETWORK MODULE
(CC-Link IE TSN)
Functions & Features
• Interchanges analog or discrete I/O signals with the filedbus (CC-Link IE TSN)
• Space-saving
MODEL: R80NCIT1–R[1]
ORDERING INFORMATION
• Code number: R80NCIT1-R[1]
Specify a code from below for [1].
(e.g. R80NCIT1-R/Q)
• Specify the specification for option code /Q
(e.g. /C01)
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
RELATED PRODUCTS
• PC configurator software (model: R80CFG)
• CSP+ file
The configurator software and CSP+ file are downloadable at our web site.
CSP+ file is also downloadable at CC-Link Partner Association's web site.
For connecting to PC, use commercially available Mini-B type USB cable. (provided by user)
PACKAGE INCLUDES...
• Protective cover
GENERAL SPECIFICATIONS
Connection
•
Power input and excitation supply
: Tension clamp terminal block (Front Twin connection)
•
CC-Link IE TSN
: RJ-45 connector
•
Internal bus, internal power and excitation supply
: Via bus connector
Max. number of I/O modules
: 16
(Max. consumption current of I/O modules: 1.6 A)
Isolation
: Internal bus or internal power or power input to excitation supply to CC-Link IE TSN or FE1
Internal bus communication cycle:
Approx. 65μs+65μs×number of the modules.
Status indicator
: PWR, RUN, RD, SD, D LINK, ERR, L ER, LINK
(Refer to the instruction manual.)
CC-Link IE TSN
Protocol
: IEEE 802.3
Transmission type
: 1000BASE-T
Communication speed
: 1 Gbps
Communication method
: Time sharing method
Synchronization function
: IEEE802.1AS and IEEE1588v2 compliant
Certification class:
Class B
Network cable
: Cable conformed to CC-Link IE Field
Double shielded twist pair cable (CAT5e)
RJ-45 connector
Network topology
: Line, star and ring
Max. number stations
: 64770 (Total master and slave station)
(Number of max. connectable slaves may vary depending on the master module. Refer to the instruction manual of the master module)
Max. station-to-station distance
: 100 m
Station type
: Remote station
Link device
: RX/RY 112 points, RWw/RWr 64 points
INSTALLATION
Power consumption
•
DC
: Approx. 12 W 24 V DC (@ internal power max. current 1.6 A)
Internal power supply (power supply for I/O module)
:
• DC power supply: 5 V DC
• Current capacity: 1.6 A
Excitation supply output (excitation for I/O module)
•
DC
: 24 V DC ±10 %
•
Operational current:
10 A
(From power and excitation supply connector, via connector for internal bus, supplied to each I/O module. Power output current consumption must be under operational current.)
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Storage humidity
: -20 to +65 % RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail
Weight
: 230 g (0.51 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute
(internal bus or internal power or power input to excitation supply to CC-Link IE TSN or FE1)
STANDARDS & APPROVALS
Refer to the manuals to comply with the standards.
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
WIRING
• POWER SUPPLY AND EXCITATION SUPPLY CONNECTOR TERMINAL ASSIGNMENT
Unit side connector
: MSTBV2,5/5-GF-5, 08AU (Phoenix Contact)
Cable side connector
: TFKC2,5/5-STF-5, 08AU (Phoenix Contact)
Applicable wire size
: 0.2 − 2.5 mm
2
; stripped length 10 mm
Recommended solderless terminal
• AI0,25−10YE 0.25 mm
2
(Phoenix Contact)
• AI0,34−10TQ 0.34 mm
2
(Phoenix Contact)
• AI0,5−10WH 0.5 mm
2
(Phoenix Contact)
• AI0,75−10GY 0.75 mm
2
(Phoenix Contact)
• AI1−10RD 1.0 mm
2
(Phoenix Contact)
• AI1,5−10BK 1.5 mm
2
(Phoenix Contact)
• AI2,5−10BU 2.5 mm
2
(Phoenix Contact)
EXTERNAL DIMENSIONS unit: mm [inch]
■UNIT
■PROTECTIVE COVER
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FE1 terminal to ground.
Caution: FE1 terminal is NOT a protective conductor terminal.