ES-7030 Rev.1
R80YST4N
Remote I/O R80 Series
DC CURRENT OUTPUT MODULE, 4 points
(4 points, non-isolated, Tension clamp terminal block)
Functions & Features
• 4 points DC current output remote I/O module
• Non-isolated
• Tension clamp terminal block
MODEL: R80YST4N[1]
ORDERING INFORMATION
• Code number: R80YST4N[1]
Specify a code from below for [1].
(e.g. R80YST4N/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
RELATED PRODUCTS
• PC configurator software (model: R80CFG)
Downloadable at our web site.
For connecting to PC, use commercially available Mini-B type USB cable. (provided by user)
GENERAL SPECIFICATIONS
Connection
Output
: Separable tension clamp terminal
Internal bus, internal power
: Connected to internal bus connector
Housing material
: Flame-resistant resin (black)
Isolation
: Output 1-4 to excitation supply to internal bus or internal power to FE
Output setting
: Scaling is configurable individually for each 4 points with configurator software (model: R80CFG)
Module address
: With DIP switch
Terminating resistor
: Built-in (DIP Switch, default: disable)
Status indicator
: Bi-color (red/green) LED; Refer to the instruction manual.
Output status indicators
: Red LED; Refer to the instruction manual.
OUTPUT
Output range
: Selectable between 0 – 20mA DC
Operational range
: -5 – +105 % (in percentage of output range) ≤ 0 mA DC
Load resistance
: ≤ 350Ω
INSTALLATION
Max. current consumption
: 100 mA
Exc. supply
current consumption
: 90 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -10 to +55°C (14 to +131°F)
Operating humidity
: 10 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail
Weight
: 120 g (0.26 lb)
PERFORMANCE
Conversion accuracy (in percentage of output range)
±0.08 % (@ output range 0 - 20 mA)
Conversion accuracy is inversely proportional to output span.
Conversion rate
: 1 msec.
Output circuit time constant
: ≤ 1 msec. (0 → 90 %)
Data range
: 0 – 10000 of the output range
(Scaling of converted data is configurable with the configurator software)
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
:
1500 V AC @ 1 minute (output1 - 4 to exc. supply to internal bus or internal power to ground)
CALCULATION EXAMPLES OF CONVERSION ACCURACY
When output range is 4 - 20 mA: conversion accuracy = output span standard value (20 mA) ÷ output span (16 mA) × 0.08(%) = 0.1 (%).
output span standard value is the same as the span at output range 0 - 20 mA DC.
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
CONNECTION DIAGRAMS
■
Tension clamp terminal block
Unit side connecto
r: MC1,5/8-GF-3,5 (Phoenix Contact)
Applicable connector
: FMC1,5/8-STF-3,5 (Phoenix Contact)
Applicable wire size
: 0.2 − 1.5 mm
2
Stripped length
: 10 mm
Recommended solderless terminal
• AI0,25−10YE 0.25 mm
2
(Phoenix Contact)
• AI0,34−10TQ 0.34 mm
2
(Phoenix Contact)
• AI0,5−10WH 0.5 mm
2
(Phoenix Contact)
• AI0,75−10GY 0.75 mm
2
(Phoenix Contact)
• A1−10 1.0 mm
2
(Phoenix Contact)
• A1,5−10 1.5 mm
2
(Phoenix Contact)
OPERATING MODE SETTING
(*) factory default setting
Note: Be sure to set unused SW 2-2 to OFF.
TERMINAL ASSIGNMENTS
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM