ES-7033 Rev.1

R80YVT4N

Remote I/O R80 Series

DC VOLTAGE OUTPUT MODULE, 4 points

(4 points, non-isolated, Tension clamp terminal block)
Functions & Features
• 4 points DC voltage output remote I/O module
• Non-isolated
• Tension clamp terminal block

MODEL: R80YVT4N[1]

ORDERING INFORMATION

• Code number: R80YVT4N[1]
Specify a code from below for [1].
(e.g. R80YVT4N/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating

RELATED PRODUCTS

• PC configurator software (model: R80CFG)
Downloadable at our web site.
For connecting to PC, use commercially available Mini-B type USB cable. (provided by user)

GENERAL SPECIFICATIONS

Connection
 Output: Separable tension clamp terminal
 Internal bus, internal power: Connected to internal bus connector
Housing material: Flame-resistant resin (black)
Isolation: Output 1-4 to excitation supply to internal bus or internal power to FE
Output setting: Scaling is configurable individually for each 4 points with configurator software (model: R80CFG)
Module address: With DIP switch
Terminating resistor: Built-in (DIP Switch, default: disable)
Status indicator: Bi-color (red/green) LED; Refer to the instruction manual.
Output status indicators: Red LED; Refer to the instruction manual.

OUTPUT

Output range: Selectable between -10 – +10 V DC
Operational range: -5 – +105 % (in percentage of output range)
Load resistance: ≥ 5 kΩ

INSTALLATION

Current consumption: 210 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Storage temperature: -10 to +55°C (14 to +131°F)
Operating humidity: 10 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail
Weight: 105 g (0.23 lb)

PERFORMANCE

Conversion accuracy (in percentage of output range)
±0.05 % (@ output range -10 - +10 V)
Conversion accuracy is inversely proportional to output span.
Conversion rate: 1 msec.
Output circuit time constant: ≤ 1 msec. (0 → 90 %)
Data range: 0 – 10000 of the output range
(Scaling of converted data is configurable with the configurator software)
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength:
  1500 V AC @ 1 minute (output1 - 4 to exc. supply to internal bus or internal power to ground)

CALCULATION EXAMPLES OF CONVERSION ACCURACY

When output range is 1 - 5 V: conversion accuracy = output span standard value (20 V) ÷ output span (4 V) × 0.05(%) = 0.25 (%).
output span standard value is the same as the span at output range -10 - +10 V DC.

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

CONNECTION DIAGRAMS

Tension clamp terminal block
Unit side connector: MC1,5/8-GF-3,5 (Phoenix Contact)
Applicable connector: FMC1,5/8-STF-3,5 (Phoenix Contact)
Applicable wire size: 0.2 − 1.5 mm2
Stripped length: 10 mm
Recommended solderless terminal
• AI0,25−10YE 0.25 mm2 (Phoenix Contact)
• AI0,34−10TQ 0.34 mm2 (Phoenix Contact)
• AI0,5−10WH 0.5 mm2 (Phoenix Contact)
• AI0,75−10GY 0.75 mm2 (Phoenix Contact)
• A1−10 1.0 mm2 (Phoenix Contact)
• A1,5−10 1.5 mm2 (Phoenix Contact)

OPERATING MODE SETTING

(*) factory default setting
Note: Be sure to set unused SW1-5 to 8 to OFF.

TERMINAL ASSIGNMENTS

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM