ES-9790 Rev.4
R8-DCM32B2
Remote I/O R8 Series
PNP TRANSISTOR OUTPUT MODULE, 32 points
(with shortcircuit protection)
Functions & Features
• 32 channels for discrete output, compact size remote I/O module
• 40 pin MIL connector
MODEL: R8-DCM32B2[1]
ORDERING INFORMATION
• Code number: R8-DCM32B2[1]
Specify a code from below for [1].
(e.g. R8-DCM32B2/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
RELATED PRODUCTS
• PC configurator software (model: R8CFG)
A dedicated cable is required to connect the module to the PC. Please refer to the users manual for the PC configurator for applicable cable types.
Note: When using with Power/Network module (model: R8-NECT1), firmware version Ver1.30 or later is supported.
GENERAL SPECIFICATIONS
Connection
•
Output
:40-pin MIL connector
PWB connector XG4A-4034 (Omron)
Recommended socket XG5N-401 (Omron)
Recommended contact XG5W-0231 (Omron)
Applicable wire size AWG22, number of conductor
17, diameter of conductor 0.16 mm (The socket and
contact are not included in the package. Refer to the
specifications of the product.)
•Excitation supply, internal bus
:
Connected to internal bus connector
•
Internal power
: Supplied from internal bus connector
Isolation
: Output or exc. supply to internal bus or internal power
Module address
: With DIP switch
Output at the loss of communication
: Selectable with the side DIP SW
Terminating resistor
: Built-in (DIP Switch, default: disable)
Configuration mode
: With DIP switches on the side panel
Status indicator
: Bi-color (red/green) LED; Refer to the instruction manual.
Discrete output status indicators
: Green LED; Switch between output 1 to 16 and 17 to 32. Refer to the instruction manual.
OUTPUT SPECIFICATIONS
Common
: Positive common (PNP) per 32 points
Maximum outputs applicable at once
: No limit (at 24 V DC)
Number of output
: 32 points
Rated load voltage
: 24 V DC ±10 %
Rated output current
: 50 mA per point, 1.6 A per common
Residual voltage
: ≤ 0.5 V
Leakage current
: ≤ 0.1 mA
ON delay
: ≤ 0.5 msec.
OFF delay
: ≤ 1.5 msec.
With shortcircuit protection
With overheat protection
(When driving an inductive load, connect a diode in parallel with the load.)
INSTALLATION
Max. current consumption
: 110 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail
Weight
: 110 g (0.24 lb)
PERFORMANCE
Data allocation
: 1
Module addresses in use
: 2
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute
(output or exc. supply to internal bus or internal power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
OPERATING MODE SETTING
(*) Factory setting
Caution ! - SW2-1, 2-2, 2-3, 2-4, 2-7 are unused. Be sure to turn off unused ones.
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM