ES-9694 Rev.2
R8-FST4N
Remote I/O R8 Series
DC VOLTAGE/CURRENT INPUT MODULE
(built-in excitation, 4 points, non-isolated)
Functions & Features
• DC current input and DC voltage input compact size remote I/O module
• Switching between current input and voltage input with PC configurator (model: R8CFG)
• Accepts direct input from power output as sensor power and outputs from terminals
• Each channel is atachable/detachable independently with separable tension clamp terminal.
MODEL: R8-FST4N[1]
ORDERING INFORMATION
• Code number: R8-FST4N[1]
Specify a code from below for [1].
(e.g. R8-FST4N/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
RELATED PRODUCTS
• PC configurator software (model: R8CFG)
The configurator software is downloadable at our web site.
A dedicated cable is required to connect the module to the PC. Please refer to the users manual for the PC configurator for applicable cable types.
GENERAL SPECIFICATIONS
Connection
•
Input
: Tension clamp
•
Excitation supply, internal bus
:
Connected to internal bus connector
•
Internal power
: Via bus connector
Isolation
: Input or exc. supply to internal bus or internal power
Input type
: Configuration mode that selectable between current input and voltage input and available to configure scaling individually for each 4 points with configurator software (model: R8CFG) and fixed input mode that selectable between 0 - 10 V DC and 4 - 20 mA DC individually for each 4 points are available.
Module address
: With rotary switch
Terminating resistor
: Built-in (DIP Switch, default: disable)
Status indicator
: Bi-color (red/green) LED; Refer to the instruction manual.
Input status indicators
: Red LED; Refer to the instruction manual.
INPUT SPECIFICATIONS
■
DC Voltage
:
• Configuration mode
Input range
: -10 – +10 V DC
Input setting value
: Available to set in the input range
Operational range
: -5 - +105 % (% of input setting value)
Input resistance:
≥ 1 MΩ
• Fixed input mode
Input range
: 0 – 10 V DC
Input setting value
: Available to set in the input range
Operational range
: -5 - +105 % (% of input setting value)
Input resistance:
≥ 1 MΩ
■
DC Current
:
• Configuration mode
Input range
: -20 – +20 mA DC
Input setting value
: Available to set in the input range
Operational range
: -5 - +105 % (% of input setting value)
Input resistance
: 50 Ω (1/4 W)
• Fixed input mode
Input range
: 4 – 20 mA DC
Input setting value
: Available to set in the input range
Operational range
: -5 - +105 % (% of input setting value)
Input resistance
: 50 Ω (1/4 W)
Factory default (Input type and input setting value):
Voltage input, input range -10 - +10 V DC for all 4 points.
INSTALLATION
Max. current consumption
: 100 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail
Weight
: 80 g (0.18 lb)
PERFORMANCE
Conversion accuracy
(in percentage of input range)
Voltage input
:±0.05 %
Current input
:±0.1 %
Conversion accuracy is inversely proportional to input span.
Conversion rate
: 8 msec.
Input circuit time constant
: Approx. 1 msec.
Data range
: 0 – 10000 of the input range
(Scaling of converted data is configurable with the configurator software)
Data allocation
: 2
Module addresses in use
: 2
Power output (input
connector
)
: Rated current 0.5 A DC per channel (rated current 3 A for internal fuse (slow blow fuse i
2
t (A
2
sec.) max. 5.04); Total: 1 A DC
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute
(input or exc. supply to internal bus or internal power to ground)
CALCULATION EXAMPLES OF CONVERSION ACCURACY
■
Voltage input:
For input setting value 1 - 5 V DC
Conversion accuracy = Input range span (20 V) ÷ input setting value span (4 V) × 0.05 (%) = 0.25 (%)
■
Current input:
For input setting value 4 - 20 mA DC
Conversion accuracy = Input range span (40 mA) ÷ input setting value span (16 mA) × 0.1 (%) = 0.25 (%)
(Span is common for configuration mode and fixed input mode)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
WIRING
• TENSION CLAMP
Unit side connector:
Tension clamp
Cable side connector
: DFMC1,5/2-ST-3,5 (Phoenix Contact) (included in the package)
Applicable wire size
: 0.2 - 1.5 mm
2
Stripped length
: 10 mm
Recommended solderless terminal
• AI0,25-10YE 0.25 mm
2
(Phoenix Contact)
• AI0,34-10TQ 0.34 mm
2
(Phoenix Contact)
• AI0,5-10WH 0.5 mm
2
(Phoenix Contact)
• AI0,75-10GY 0.75 mm
2
(Phoenix Contact)
• A1-10 1.0 mm
2
(Phoenix Contact)
• A1,5-10 1.5 mm
2
(Phoenix Contact)
OPERATING MODE SETTING
(*) factory default setting
Note: Be sure to set unused SW4-5 through 4-7 to OFF.
EXTERNAL DIMENSIONS unit: mm [inch]