ES-9789 Rev.6

R8-PS1

Remote I/O R8 Series

EXTENSION POWER SUPPLY MODULE

(non-isolated)
Functions & Features
• Inserted between I/O modules and supply the power
• Up to two R8-PS1 use is available

MODEL: R8–PS1-R[1]

ORDERING INFORMATION

• Code number: R8-PS1-R[1]
Specify a code from below for [1].
(e.g. R8-PS1-R/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

POWER INPUT

DC power
R: 24 V DC
(Operational voltage range: ±10 %; ripple 10 %p-p max.)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating

CAUTION

OUTPUT CURRENT & NUMBER OF CONNECTABLE UNIT
It is NOT available to connect 16 of R8-YV4N to power/network module because of limitation of output current of internal supply. The max. output current for internal supply of power/network module is 1.6 A.
The max. consumption current for internal supply of R8-YV4N is 160 mA.
  1.6 (A) < 160 (mA) x 16 = 2.56 (A)
Inserting the R8-PS1 between 10th and 11th R8-YV4N enables to connect 16 of R8-YV4N.
POWER UP
Turn the power on at the same time as the power/network module or turn the R8-PS1 on before the power/network module turned on. If the R8-PS1 is not turned on within 3 seconds after the power/network module is turned on, I/O modules are not correctly recognized

GENERAL SPECIFICATIONS

Connection
Power input, excitation supply: Tension clamp (Front Twin connection)
  Applicable wire size: 0.2 - 1.5 mm2
  Stripped length: 10 mm
Internal bus or internal power: Via connector
Max. number of I/O modules: 16
(Max. consumption current of I/O modules: 1.6 A)
Isolation: Internal bus or internal power or power input to exc. supply to FE1
Power indicator LED: Green LED turns on when the power is supplied.

INSTALLATION

Power consumption
DC: Approx. 11 W 24 V DC (@ internal power max. current 1.6 A)
Internal power supply (power supply for I/O module):
• DC power supply: 5 V DC
• Current capacity: 1.6 A
Excitation supply output (excitation for I/O module)
DC: 24 V DC ±10 %
Operational current: 8 A
(From power supply, exitation supply connector, via connector for internal bus, supplied to each I/O module. Power output current consumption must be under operational current.)
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail
Weight: 100 g (0.22 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(internal bus or internal power or power input to exc. supply to FE1)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

CONNECTION DIAGRAMS

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY

Note: In order to improve EMC performance, bond the FE1 terminal to ground.
Caution: FE1 terminal is NOT a protective conductor terminal.