ES-9696 Rev.2
R8-YST4N
Remote I/O R8 Series
DC CURRENT OUTPUT MODULE
(4 points, non-isolated, Tension clamp terminal block)
Functions & Features
• 4 channels for DC current output, compact size remote I/O module
• 8 pins tension clamp connector
• Output range adjustment with DIP switch or PC configurator
MODEL: R8–YST4N[1]
ORDERING INFORMATION
• Code number: R8-YST4N[1]
Specify a code from below for [1].
(e.g. R8-YST4N/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
RELATED PRODUCTS
• PC configurator software (model: R8CFG)
Downloadable at our web site.
A dedicated cable is required to connect the module to the PC. Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.
GENERAL SPECIFICATIONS
Connection
•
Output
: Tension clamp
Applicable wire size
: 0.2 - 1.5 mm
2
Stripped length
: 10 mm
•
Excitation supply, internal bus
:
Connected to internal bus connector
•
Internal power
: Via bus connector
Isolation
: Output to exc. supply to internal bus or internal power
Output range
: Selectable with the side DIP SW
Module address
: With DIP switch
Output at the loss of communication
: Selectable with the side DIP SW
Terminating resistor
: Built-in (DIP Switch, default: disable)
Configuration mode
: With DIP switches on the side panel
Status indicator
: Bi-color (red/green) LED; Refer to the instruction manual.
Output status indicators
: Red LED; Refer to the instruction manual.
OUTPUT
Output range
: Selectable between 0 – 20mA DC
Operational range
: -5 – +105 % (in percentage of output range) ≤ 0 mA DC
Load resistance
: ≤ 350Ω
INSTALLATION
Max. current consumption
: 70 mA
Exc. supply
current consumption
: 90 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail
Weight
: 120 g (0.26 lb)
PERFORMANCE
Conversion accuracy (in percentage of output range)
±0.08 % (@ output range 0 - 20 mA)
Conversion accuracy is inversely proportional to output span.
Conversion accuracy computation example:
When output range is 4 - 20 mA: conversion accuracy = output span standard value (20 mA) ÷ output span (16 mA) × 0.08(%) = 0.1 (%).
output span standard value is the same as the span at output range 0 - 20 mA DC.
Conversion rate
: 4 msec.
Output circuit time constant
: ≤ 1 msec. (0 → 90 %)
Data range
: 0 – 10000 of the output range
Data allocation
: 2
Module addresses in use
: 2
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
:
1500 V AC @ 1 minute (output to exc. supply to internal bus or internal power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
OPERATING MODE SETTING
(*) Factory setting
Caution ! - SW2-2, 2-3, 2-4, 2-7 are unused. Be sure to turn off unused ones.
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM