MULTI POWER MONITORING UNIT
(Clamp-on current sensor CLSE, Modbus/TCP)
Functions & Features
• Multi Power Monitoring Unit for Modbus/TCP (Ethernet)
• By using clamp-on current sensors, there is no need of current transformers.
• Up to 8 circuits can be measured. (Common voltage measurement)
• Current sensors are easy to install in existing systems. Wide input range of 5 to 600 A is availabe.
• All measured values, counter values, display mode, setting data are stored in the non-volatile memory when power is off.
• By using SD card, data logging of current and power etc. with calendar is available.
MODEL: R9EWTU-2001-AD4[1]
ORDERING INFORMATION
• Code number: R9EWTU-2001-AD4[1]
Specify a code from below for [1].
(e.g. R9EWTU-2001-AD4/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
CONFIGURATION
2
: Single-phase/2-wire, 3-phase/3-wire, single-phase/3-wire; 8 circuits
CONNECTION
0
: Terminal block
I/O
0
: Without
EXTENSION UNIT
1
: With connection
AUXILIARY POWER SUPPLY
AD4
: universal
100 – 240 V AC (Operational range 85 – 264 V, 50 / 60 Hz) /
110 – 240 V DC (Operational range 99 – 264 V,
ripple 10 %p-p max)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-6224)
RELATED PRODUCTS
• Discrete I/O extension unit (model: R9WTU-ED)
• Multi power monitoring extension unit (model: R9WTU-EP)
• PC configurator software (model: PMCFG)
Downloadable at our web site.
A dedicated cable is required to connect the module to the PC. Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.
• Clamp-on current sensor (model: CLSE)
The clamp-on current sensors, not included in this product package, must be ordered separately. Required number depends upon the system configuration.
• SD card
A SD card is required to store data in the unit.
Use the specified model number of memory card.
Available for purchase from us. Consult us.
- Hagiwara Solutions NSD6-004GH(B21SEI
(NSD6-004GH(A00SDI, NSDA-004GT,
NSDA-004GL ... discontinued)
- Apacer Technology AP-ISD04GIS4B-3T
(AP-ISD04GIS4B-T ... discontinued)
GENERAL SPECIFICATIONS
Construction
: Stand-alone
Degree of protection
: IP20
Connection
Auxiliary power or voltage input
: M3.5 screw terminals (torque 0.8 N·m)
Current input
: M3 screw terminals (torque 0.5 N·m)
Ethernet
: RJ-45 modular jack
Solderless terminal
: Refer to the drawing at the end of the section.
Recommended manufacturer
: Japan Solderless Terminal MFG.Co.Ltd, Nichifu Co.,ltd
Applicable wire size
M3 screw terminal
: 0.25 to 1.65 mm
2
(AWG 22 to 16)
M3.5 screw terminal
: 1.04 to 2.63 mm
2
(AWG 16 to 14)
Configuration
: Single-phase/2-wire, single-phase/3-wire, 3-phase/3-wire
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (black)
Isolation
: Sensor core to sensor output or current input or voltage input to Ethernet to auxiliary power to FE1
■ Measured variables
Voltage
: R – N, S – N, T – N, R – S, S – T, T – R
Current
: R, S, T, N
Active / reactive / apparent power
: R, S, T, Σ
Power factor
: R, S, T, Σ
Frequency
Active energy
: Incoming
Reactive energy
: Incoming lag
Active / reactive / apparent power intervals (demand)
Average (demand) current
: R, S, T, N
Harmonic contents
: Σ
Voltage
: R - N, S - N, T - N, R - S, S - T, T - R
Current
: R, S, T, N
Max. and min. values
Calendar log
(inserting SD card)
: Voltage, Current, power, electric energy, power factor
Operating mode setting
: Connection, clamp-on sensor selection
Status indicators
: Power, SD Card, RUN
■Recommended solderless terminal size - M3
■Recommended solderless terminal size - M3.5
ETHERNET COMMUNICATION
Communication Standard
: IEEE 802.3u
Transmission
: 10BASE-T, 100BASE-TX
Baud rate
: 10/100 Mbps (Auto Negotiation function)
Protocol
: Modbus/TCP
Data
: RTU (Binary)
Max. number of socket connections
: 2
Transmission media
: 10BASE-T (STP, Category 5) 100BASE-TX (STP, Category 5e)
Max. length of fieldbus segment
: 100 meters
IP address
: 192.168.0.1 (factory setting);
Selectable with PC Configurator Software (model: PMCFG)
Port No
.: 502
Ethernet indicator LED
: Link, Link100, COL
INPUT SPECIFICATIONS
Frequency
: 50 / 60 Hz (45 – 65 Hz)
•
Voltage Input
Rated voltage
•
Between lines
: 400 V AC
•
Line-neutral (phase voltage)
: 230 V (single-phase / 2-wire and 3-wire)
Input burden
: ≤ U
LN
2
/ 300 kΩ / phase
Overload capacity
: 200 % of rating for 10 sec., 120 % continuous
Selectable primary voltage range
: 50 – 400 000 V
•
Current Input
CLSE-R5
: 0 – 5 A AC
CLSE-05
: 0 – 50 A AC
CLSE-10
: 0 – 100 A AC
CLSE-20
: 0 – 200 A AC
CLSE-40
: 0 – 400 A AC
CLSE-60
: 0 – 600 A AC
Overload capacity
: 120 % continous, 500 % for 10 sec.
Note: Use for the circuit not exceed 480 V
Selectable primary current range
: 1 – 20 000 A (Using CLSE-R5 the unit is configurable only with configurator software.)
Operational range
Current
: 0 – 120 % of the rating
Voltage
: 10 – 120 % of the rating
Apparent power
: ≤ 120 % of the rating
Active/reactive power
: ±120 % of the rating
Frequency
: 45 – 65 Hz
Power factor
: ±1
INSTALLATION
Auxiliary power supply
•
AC
: < 9 VA
•
DC
: < 3 W
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Surface or DIN rail
Weight
: 500 g (1.1 lb)
PERFORMANCE
Accuracy
(at 10 - 35°C or 50 - 95°F, 45 – 65 Hz)
*1
Add the accuracy of the current sensor for overall values.
Voltage
: ±0.5 % of the rating
*2
Current
: ±0.5 % of the rating
*2
Power
: ±0.5 % of the rating
*2
Power factor
: ±1.5 %
Frequency
: ±0.1 % of the rating
*2
Energy
: ±1 %
Harmonic contents
: ±2 % of the rating
*2
*1. Sensor error margin not included
*2. The described accuracy levels are ensured at the input 1% or more for neutral current in a 1-phase/3-wire circuit and phase-S current in an unbalanced 3-phase/3-wire circuit.
Data update period
:
Harmonic contents and frequency
: ≤ 1 sec.
Other
: ≤ 500 msec.
Calendar clock
: (with battery backup)
Accuracy
: Monthly deviation 3 minutes at 25°C
Back up period
: Approx. 2 years at 25°C without power
With the power on, no battery drain
Battery
: Primary lithium battery (non-removable)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (current input or voltage input to Ethernet to auxiliary power to FE1)
EXTERNAL VIEW
TERMINAL CONNECTIONS
Use the model CLSE clamp sensor for current inputs.
The figure below shows only one circuit.
A maximum of eight (8) current sensor inputs can be connected (Ch. 1 through Ch. 8).
Grounding is not required for low voltage circuits.
TERMINAL ASSIGNMENTS
EXTERNAL DIMENSIONS unit: mm [inch]
MOUNTING REQUIREMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM