ES-6226 Rev.3

R9WTU-EP

Remote I/O R9 Series

MULTI POWER MONITORING EXTENTION UNIT

(clamp-on current sensor type CLSE use)
Functions & Features
• Extension unit for Multi Power Monitoring Unit (model: R9xWTU) to expand current inputs.
• By using clamp-on current sensors, there is no need of current transformers.
• Up to 16 circuits can be measured with R9xWTU. (Common voltage measurement)
• Current sensors are easy to install in existing systems. Wide input range of 5 to 600 A is availabe.

MODEL: R9WTU-EP8[1]

ORDERING INFORMATION

• Code number: R9WTU-EP8[1]
Specify a code from below for [1].
  (e.g. R9WTU-EP8/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

NO. OF CHANNELS

8: 8 circuits

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS

• Multi power monitoring unit for CC-Link (model: R9CWTU)
• Multi power monitoring unit for LonWorks (model: R9LWTU)
• Multi power monitoring unit for Modbus (model: R9MWTU)
• Multi power monitoring unit for Modbus/TCP (model: R9EWTU)
• Clamp-on current sensor (model: CLSE)
The clamp-on current sensors, not included in this product package, must be ordered separately. Required number depends upon the system configuration.

GENERAL SPECIFICATIONS

Construction: Stand-alone
Degree of protection: IP20
Connection: M3 screw terminals (torque 0.5 N·m)
Solderless terminal: Refer to the drawing at the end of the section.
   Recommended manufacturer: Japan Solderless Terminal MFG.Co.Ltd, Nichifu Co.,ltd 
  Applicable wire size: 0.25 to 1.65 mm2 (AWG 22 to 16)
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (black)
Isolation: Must be the same potential as R9xWTU current input
■ Measured variables
Refer to R9xWTU specification sheet.
■Recommended solderless terminal size - M3

INPUT SPECIFICATIONS

Refer to R9xWTU specification sheet.

INSTALLATION

Power consumption
AC: ≤ 1 VA
DC: ≤ 1 W
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface or DIN rail
Weight: 300 g (0.66 lb)

PERFORMANCE

Refer to R9xWTU specification sheet.

EXTERNAL VIEW

TERMINAL CONNECTIONS

Use the model CLSE clamp sensor for current inputs.
The figure below shows only one circuit.
A maximum of eight (8) current sensor inputs can be connected (Ch. 9 through Ch. 16).
Grounding is not required for low voltage circuits.

TERMINAL ASSIGNMENTS

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM