ES-5516 Rev.9
W2RS1
Space-saving Dual Output Signal Conditioners
Mini-MW Series
RTD TRANSMITTER
(1 mA sensing current)
Functions & Features
• Accepts direct input from an RTD
• Linearization
• Burnout
• 1 mA sensing current (except Cu Input)
• “Active bridge” circuit containing two constant current sources allows large leadwire resistances up to 200 Ω
• Fast response type available
Typical Applications
• Long distance transmission between the RTD and the transmitter
• Combination with intrinsic safety barriers
MODEL: W2RS1–[1][2][3]-[4][5]
ORDERING INFORMATION
• Code number: W2RS1-[1][2][3]-[4][5]
Specify a code from below for each of [1] through [5].
(e.g. W2RS1-4A6-M2/BL/CE/Q)
• Temperature range (e.g. 0 – 500°C)
• Special output ranges (For codes Z & 0)
• Specify the specification for option code /Q
(e.g. /C01/V01)
For the input code C, specify also the following. If not specified, Cu 10 Ω @25°C (usable range -140 – +260°C) will be used.
• Input type (e.g. Cu 10 Ω)
• Resistance range (e.g. 9.038 – 12.891 Ω)
Note: When the user requires a current and a voltage output, specify the current to be the Output 1 which allows a greater load.
[1] INPUT RTD (2- or 3-wire)
1
: JPt 100 (JIS'89)
(Usable range: -200 to +500°C, -328 to +932°F; min.span: 50°C, 90°F)
3
: Pt 100 (JIS'89)
(Usable range: -200 to +650°C, -328 to +1202°F; min.span: 50°C, 90°F)
4
: Pt 100 (JIS'97, IEC)
(Usable range: -200 to +650°C, -328 to +1202°F; min.span: 50°C, 90°F)
5
: Pt 50 Ω (JIS'81)
(Usable range: -200 to +500°C, -328 to +932°F; min.span: 100°C, 180°F)
6
: Ni 508.4 Ω
(Usable range: -50 to +200°C, -58 to +392°F; min.span: 30°C, 54°F)
C
: Cu (Refer to ‘Cu INPUT’.)
0
: Specify
Note: Consult us for 2-wire RTD
[2] OUTPUT 1
Current
A
: 4 – 20 mA DC (Load resistance 750 Ω max.)
B
: 2 – 10 mA DC (Load resistance 1500 Ω max.)
C
: 1 – 5 mA DC (Load resistance 3000 Ω max.)
D
: 0 – 20 mA DC (Load resistance 750 Ω max.)
E
: 0 – 16 mA DC (Load resistance 900 Ω max.)
F
: 0 – 10 mA DC (Load resistance 1500 Ω max.)
G
: 0 – 1 mA DC (Load resistance 15 kΩ max.)
Z
: Specify current (See OUTPUT SPECIFICATIONS)
Voltage
1
: 0 – 10 mV DC (Load resistance 10 kΩ min.)
2
: 0 – 100 mV DC (Load resistance 100 kΩ min.)
3
: 0 – 1 V DC (Load resistance 1000 Ω min.)
4
: 0 – 10 V DC (Load resistance 10 kΩ min.)
5
: 0 – 5 V DC (Load resistance 5000 Ω min.)
6
: 1 – 5 V DC (Load resistance 5000 Ω min.)
0
: Specify voltage (See OUTPUT SPECIFICATIONS)
[3] OUTPUT 2
Y
: None
Current
A
: 4 – 20 mA DC (Load resistance 350 Ω max.)
B
: 2 – 10 mA DC (Load resistance 700 Ω max.)
C
: 1 – 5 mA DC (Load resistance 1400 Ω max.)
D
: 0 – 20 mA DC (Load resistance 350 Ω max.)
E
: 0 – 16 mA DC(Load resistance 430 Ω max.)
F
: 0 – 10 mA DC (Load resistance 700 Ω max.)
G
: 0 – 1 mA DC (Load resistance 7000 Ω max.)
Z
: Specify current (See OUTPUT SPECIFICATIONS)
Voltage
Same range availability as Output 1
[4] POWER INPUT
AC Power
M2
: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
R2
: 11 – 27 V DC
(Operational voltage range 11 – 27 V, ripple 10 %p-p max.)
(Select ‘/N’ for ‘Standards & Approvals’ code.)
P
: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
[5] OPTIONS (multiple selections)
Response Time (0 – 90 %)
blank
: Standard (≤ 0.5 sec.)
/K
: Fast Response (Approx. 25 msec.)
Burnout
blank
: Upscale burnout
/BL
: Downscale burnout
Standards & Approvals (must be specified)
/N
: Without CE
/CE
: CE marking
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
ADJUSTMENT
/V01
: Multi-turn fine adjustment
TERMINAL SCREW MATERIAL
/S01
: Stainless steel
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
: M3 screw terminals (torque 0.8 N·m)
Screw terminal
: Chromated steel (standard) or stainless steel
Housing material
: Flame-resistant resin (black)
Isolation
: Input to output 1 to output 2 to power
Overrange output
: Approx. -10 to +120 % at 1 – 5 V
Zero adjustment
: -5 to +5 % (front)
Span adjustment
: 95 to 105 % (front)
Adjustable individually for each output 1 and output 2.
At burnout
: Downscale ≤ -10 %, Upscale ≥ 110 %
Linearization
: Standard (not available for the input code C)
INPUT SPECIFICATIONS
Maximum leadwire resistance
: 200 Ω per wire (3-wire)
Sensing current
: 1 mA
Refer to 'Cu Input' for the input code C.
OUTPUT SPECIFICATIONS
■
DC Current
: 0 – 20 mA DC
Minimum span
: 1 mA
Offset
: Max. 1.5 times span
Load resistance
: Output drive 15 V max. for Output 1;
7 V max. for Output 2
■
DC Voltage
: -10 – +12 V DC (up to 10 V for Output 2)
Minimum span
: 5 mV
Offset
: Max. 1.5 times span
Load resistance
: Output drive 1 mA max.; at ≥ 0.5 V
INSTALLATION
Power Consumption
•
AC
:
Approx. 4 VA at 100 V
Approx. 5 VA at 200 V
Approx. 6 VA at 240 V
•
DC
: Approx. 3 W
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface or DIN rail
Weight
: 100 g (0.22 lb)
PERFORMANCE in percentage of span
Accuracy
: ±0.2 %
(Refer to ‘Cu INPUT’ for the input code C.)
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Refer to ‘Cu Input’ for the input code C.
Burnout response
: ≤ 20 sec.
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @1 minute (input to output
1 to output 2 to power to ground)
Cu INPUT
■
INPUT
•
Sensing current (resistance span)
:
140 Ω ≤ Span ≤ 300 Ω : 1 mA
12 Ω ≤ Span < 140 Ω : 2 mA
8 Ω ≤ Span < 12 Ω : 3 mA
3.5 Ω ≤ Span < 8 Ω : 5 mA
•
Max. leadwire resistance
:
200 Ω or the value calculated using the equation below, whichever is smaller.
Leadwire resistance(Ω) = (2500 - 100% resistance(Ω) × Sensing current(mA)) ÷ (3 × Sensing current(mA))
•
Usable range
:
3.5 Ω ≤ Resistance span(Ω) ≤ 300Ω
0 % resistance(Ω) ≥ 3.25 Ω
100 % resistance(Ω) ≤ (2500 – 3 × Leadwire resistance (Ω) × Sensing current (mA)) ÷ Sensing current (mA)
■
PERFORMANCE
•
Accuracy
Resistance span ≥ 20 Ω
: ±0.2 %
Otherwise use the equation below
:
Accuracy(%) = 0.02(Ω) ÷ Resistance span(Ω) × 100 + 0.1(%) × 40(mV) ÷ (Resistance span(Ω) × Sensing current(mA))
•
Temperature coefficient
Resistance span(Ω) × Sensing current(mA) ≥ 40(mV)
: ±0.015 %/°C
Otherwise use the equation below
:
Temperature coefficient(%/°C) = 0.015(%/°C) × 40(mV) ÷ (Resistance span(Ω) × Sensing current(mA))
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Installation Category II
Pollution Degree 2
Input or output 1 or output 2 to power input:
Reinforced insulation (300 V)
Input to output 1 to output 2: Basic insulation (300 V)
RoHS Directive
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM