ES-5520 Rev.9
W2YV
Space-saving Dual Output Signal Conditioners
Mini-MW Series
ISOLATOR
Functions & Features
• Galvanically isolating the input and output signals
• Universal power input
• High-density mounting
Typical Applications
• Isolation between control room and field instrumentation
• Eliminating ground loops
MODEL: W2YV–[1][2][3]-[4][5]
ORDERING INFORMATION
• Code number: W2YV-[1][2][3]-[4][5]
Specify a code from below for each of [1] through [5].
(e.g. W2YV-6A6-M/Q)
• Specify the specification for option code /Q
(e.g. /C01 /V01)
Note: When the user requires a current and a voltage output, specify the current to be the Output 1 which allows a greater load.
[1] INPUT
Current
A
: 4 – 20 mA DC (Input resistance 250 Ω)
Voltage
6
: 1 – 5 V DC (Input resistance 1 MΩ min.)
[2] OUTPUT 1
Current
A
: 4 – 20 mA DC (Load resistance 750 Ω max.)
Voltage
6
: 1 – 5 V DC (Load resistance 5000 Ω min.)
[3] OUTPUT 2
Y
: None
Current
A
: 4 – 20 mA DC (Load resistance 350 Ω max.)
Voltage
6
: 1 – 5 V DC (Load resistance 5000 Ω min.)
[4] POWER INPUT
AC Power
M
: 85 – 264 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
DC Power
R2
: 11 – 27 V DC
(Operational voltage range 11 – 27 V, ripple 10 %p-p max.)
[5] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
ADJUSTMENT
/V01
: Multi-turn fine adjustment
TERMINAL SCREW MATERIAL
/S01
: Stainless steel
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
: M3 screw terminals (torque 0.8 N·m)
Screw terminal
: Chromated steel (standard) or stainless steel
Housing material
: Flame-resistant resin (black)
Isolation
: Input to output 1 to output 2 to power
Overrange output
: Approx. -10 to +120 % at 1 – 5 V
Zero adjustment
: -5 to +5 % (front)
Span adjustment
: 95 to 105 % (front)
Adjustable individually for each output 1 and output 2.
INPUT SPECIFICATIONS
■
DC Current
:
Shunt resistor attached to the input terminals (0.5 W)
INSTALLATION
Power Consumption
•
AC
:
Approx. 4 VA at 100 V
Approx. 5 VA at 200 V
Approx. 6 VA at 240 V
•
DC
: Approx. 3 W
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface or DIN rail
Weight
: 200 g (0.44 lb)
PERFORMANCE in percentage of span
Accuracy
: ±0.1 %
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: ≤ 0.5 sec. (0 – 90 %)
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @1 minute (input to output
1 to output 2 to power to ground)
EXTERNAL DIMENSIONS unit: mm [inch]
TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM