ES-7767-N Rev.1

R7F4DC-DC16A-H

Remote I/O R7F4D Series

CC-Link I/O MODULE

(NPN transistor output, 16 points each, e-CON connector)
Functions & Features
• Interchanges discrete I/O signals with the fieldbus (CC-Link)

MODEL: R7F4DC-DC16A-H-R[1]

ORDERING INFORMATION

• Code number: R7F4DC-DC16A-H-R[1]
Specify a code from below for [1].
  (e.g. R7F4DC-DC16A-H-R/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

I/O TYPE

DC16A: NPN transistor output, 16 point

TERMINAL BLOCK

H: Tension clamp terminal block for power
    Tension clamp terminal block for communication
    e-CON connector for output

POWER INPUT

DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS

• CSP+ file
The CSP+ file are downloadable at our web site.
CSP+ file is also downloadable at CC-Link Partner Association's web site.

GENERAL SPECIFICATIONS

Connection
  CC-Link:
Tension clamp terminal block
  Power supply, exc. supply: Tension clamp terminal
  Output: e-CON connector
Housing material: Flame-resistant resin (gray)
Isolation: Output or exc. supply to CC-Link to power supply to FE1
Discrete output status indicator LED: Green LED; turns on with output ON

CC-Link COMMUNICATION

Transmission: CC-Link ver.1.10
Network cable: CC-Link cable designated by Mitsubishi Electric
Station type: Remote I/O device
Station number: 1 - 64 (rotary switch, default:00)
Baud rate setting: 156 kbps (default), 625 kbps, 2.5 Mbps,
5 Mbps, 10 Mbps (DIP switch)
Terminating resistor: Built-in (DIP Switch, default: disable)
Status indicator LEDs: Power, Run, Error, SD, RD
(For details, refer to the users manual.)

OUTPUT SPECIFICATIONS

Common: Negative common (NPN) per 16 points
Number of output: 16 points
Maximum outputs applicable at once: No limit (at 24 V DC)
Rated load voltage: 24 V DC ±10 %, ripple 5 %p-p max.,
≤ 1 A (including discrete output load charge); rated current
8 A
Rated output current: 0.1 A per point, 1.6 A per common
Residual voltage: ≤ 1.2 V
Leakage current: ≤ 0.1 mA
ON delay: ≤ 0.2 msec.
OFF delay: ≤ 0.5 msec.
With shortcircuit protection
With overheat protection
(When driving an inductive load, connect a diode in parallel with the load.)

INSTALLATION

Current consumption
DC: Approx. 35 mA
 (contact I/O load charge is not included)
Operating temperature: -10 to +55°C (14 to 131°F)
Storage temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface or DIN rail (35 mm rail)
Weight: 120 g (0.26 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(output or exc. supply to communication/power supply)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

COMMUNICATION CABLE WIRING

TERMINAL ASSIGNMENTS

■ CC-Link, POWER SUPPLY, EXC. SUPPLY ASSIGNMENT
■ OUTPUT TERMINAL ASSIGNMENT

DATA ALLOCATION

I/O DATA DESCRIPTIONS

EXTERNAL DIMENSIONS unit: mm [inch]

MOUNTING REQUIREMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

Note: In order to improve EMC performance, bond the FE1 terminal to ground.
Caution: FE1 terminal is NOT a protective conductor terminal.