ES-9721 Rev.20

R8

Remote I/O R8 Series

R8 SERIES GENERAL SPECIFICATIONS

Functions & Features
• Remote I/O modules which interchange analog or digital I/O signals with the fieldbus
• Space-saving
Typical Applications
• Remote I/O for DCS and PLC
• Personal computer I/O

ORDERING INFORMATION

• Power/Network module: R8-[1]-R
Specify a code from below for [1].
(e.g. R8-NM1-R)
• I/O module: R8-[1]
Specify a code from below for [1].
(e.g. R8-DA4A)
• Extension power supply module: R8-[1]-R
Specify a code from below for [1].
(e.g. R8-PS1-R)

POWER/NETWORK MODULE: R8-[1]-R

Refer to the specifications for the respective models.

[1] MODULE TYPE

ND1: DeviceNet
ND2: DeviceNet
NM1: Modbus
NECT1: EtherCAT
NEIP1: EtherNet/IP
NC3: CC-Link
NC3A: CC-Link

POWER INPUT

DC power
R: 24 V DC
(Operational voltage range: ±10 %; ripple 10 %p-p max.)

I/O MODULE: R8-[1]

Refer to the specifications for the respective models.

[1] MODULE TYPE

• Analog Input
SS2: DC current input, (isolated), 2 points
SS4NJ: DC current input (built-in excitation, non-isolated), 4 points
SS4N: DC current input (non-isolated), 4 points
SST8: DC current input (isolated), 8 points
SV2: DC voltage input (isolated), 2 points
SV4N: DC voltage input (non-isolated), 4 points
SVT8: DC voltage input (isolated), 8 points
TS2: Thermocouple input (isolated), 2 points
RS4N: RTD input (non-isolated), 4 points
FS16N: DC current/voltage input
(built-in excitation, non-isolated), 16points
FST4N: DC current/voltage input
(built-in excitation, non-isolated), 4points
CT4E: AC current input
(RMS sensing, clamp-on current sensor, non-isolated), 4 points
• Analog Output
YS2: DC current output (isolated), 2 points
YS2NJ: DC current output
(built-in excitation, non-isolated), 2 points
YST4N: DC current output (non-isolated), 4 points
YV4N: DC voltage output (non-isolated), 4 points
YVM4N: DC voltage output (non-isolated), 4 points
YVT4N: DC voltage output (non-isolated), 4 points
• Pulse Input
PA4: Totalized pulse input, 4 points
PA4F: High-speed totalized pulse input, 4 points
• Pulse Output
PC4A: Open collector output, 4 points
• Discrete Input
DA4A: Discrete input, 4 points
DAM16A: Discrete input (NPN), 16 points
DAT8A2: Discrete input (NPN), 8 points
DAT8B2: Discrete input (PNP), 8 points
DAT16A2: Discrete input (NPN), 16 points
DAT16B2: Discrete input (PNP), 16 points
• Discrete Output
DC4A: Discrete output (NPN), 4 points
DC4A2: Discrete output (NPN), 4 points
DC4C: Photo MOSFET relay output, 4 points
DCT4D: Relay output, 4 points
DCM16A: Discrete output (NPN), 16 points
DCM16ALZ: Discrete output (NPN) with full interlock, 16 points
DCM16ALK: Discrete output (NPN) with full and individual
interlock, 16 points
DCM16ALH: Discrete output (NPN) with full and partial
interlock, 16 points
DCM32B2: Discrete output (PNP), 32 points
DCT8A2: Discrete output (NPN), 8 points
DCT8B2: Discrete output (PNP), 8 points
DCT16A2: Discrete output (NPN), 16 points
DCT16B2: Discrete output (PNP), 16 points
• Temperature Control
TC2: Temperature Control Module
Since internal power supply source and internal
communication bus are performed through the connector of
each module, installation base is unnecessary.

EXTENSION POWER SUPPLY MODULE: R8-[1]-R

Refer to the specifications for the respective models.

[1] MODULE TYPE

PS1: Extension power supply module

POWER INPUT

• DC power
R: 24 V DC
(Operational voltage range: ±10 %; ripple 10 %p-p max.)

FUNCTIONS & FEATURES

The R8 Series Remote I/O is composed of power/network modules, I/O modules and extension power supply module.
I/O MODULE
Performs data conversion of field inputs; Data conversion of data received through the internal bus into outputs.
POWER/NETWORK MODULE
The power/network module supplies the I/O modules with required internal electrical power source.
The power/network module changes the receiving data from internal bus into output signal and vice versa, acts as a gateway between transmission line and internal bus.
EXTENSION POWER SUPPLY MODULE
Inserted between I/O modules and supply the power when output current of power/network module is insufficient.
DATA CONVERSION
Depends upon the type of module and ranges.
For analog input module, 0 to 100 % of the selected range is converted into 0 to 10000 (dec) or 0000 to 2710 (hex). -5 to 0 % is represented in 2’s complements.
Analog output is represented with 16-bit binary data.  0 to 10000 (dec) or 0000 to 2710 (hex) 
is converted into 0 to 100 % of the selected range.
-5 to 0 % is represented in 2’s complements.
For RTD, thermocouple input module at factory setting, data is represented with 16-bit signed binary data of engineering unit value (℃) multiplied by 10. e.g. In case of measuring 27.5℃, value is 275.
Refer to each model manual for details.
SCALING & ZERO & SPAN ADJUSTMENTS
The PC Configurator Software (model: R8CFG) is available to scale 0 to 100 % data. It is available to configure in the range between -32000 and 32000. e.g. Configuring temperature range by Configurator Software enables to handle 100 to 200℃ as value 0 to 10000.
HOT INSERTION/REMOVAL OF I/O MODULES
Since internal power supply and internal bus are performed through the connector of each module, it cannot be replaced with the power on.
DIELECTRIC STRENGTH
As dielectric strength differs depending on each module, refer to each specification sheet.

RELATED PRODUCTS

• PC configurator software (model: R8CFG)
Downloadable at our web site.
A dedicated cable is required to connect the module to the PC.  Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.

GENERAL SPECIFICATIONS

Power input:
• R8-NM1-R 
• R8-NECT1-R
• R8-NEIP1-R
• R8-ND1-R
• R8-ND2-R
• R8-NC3-R
• R8-NC3A-R
• R8-PS1-R: 
  24 V DC ±10 %; ripple 10 %p-p max.
  Power consumption
  •DC: Approx. 12 W (Approx. 11 W for R8-PS1-R) 
   24 V DC (@ output current 1.6 A)
  Internal power
  •DC: 5 V DC
  •Operational current: 1.6 A
  Excitation supply output
  •DC: 24 V DC ±10 %
  •Operational current: 10 A (8 A for R8-PS1-R)
   (Power output current consumption must be under rated current)
Operating temperature: -10 to +55°C (14 to 131°F)
  R8-NC3, R8-NC3A: 0 to 55°C (32 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail (35 mm wide)
Connection
•Power/network module
·Power supply, exc. supply:
  Tension clamp style: Front Twin Connection
  Applicable wire size: 0.2 to 2.5 mm2, stripped length 10 mm
·Modbus:
  Tension clamp style: Front Twin Connection
  Applicable wire size: 0.2 to 1.5 mm2, stripped length 10 mm
·EtherCAT: RJ-45 connector
·DeviceNet:
  Tension clamp style: Front Twin Connection
  Communication cable: Cable to meet the DeviceNet specification, Stripped length 10 mm
·CC-Link:
  Tension clamp style: Front Twin Connection
  Communication cable: Cable to meet the CC-Link specification, Stripped length 10 mm
•I/O module:
Connection
·4 pin e-CON connector  
Unit side connector XN2D-1474-S002 (Omron)
Recommended cable side connector XN2A-1470 (Omron)*1
Applicable wire size: 0.08 mm2 (AWG28) - 0.5 mm2 (AWG20)
(Outer sheath diameter: max. 1.5 dia)
·20 pin MIL connector 
Unit side connector XG4A-2034 (Omron), our product
Recommended cable side socket XG5N-201 (Omron)*1
Recommended cable side contact XG5W-0231 (Omron)*1
Applicable wire size: AWG22, number of conductor 17, diameter of conductor 0.16 mm
*1. Not included in the package.  Refer to the specifications of the product.
·40 pin MIL connector 
Unit side connector XG4A-4034 (Omron), our product
Recommended cable side socket XG5N-401 (Omron)*1
Recommended cable side contact XG5W-0231 (Omron)*1
Applicable wire size: AWG22, number of conductor 17, diameter of conductor 0.16 mm
*1. Not included in the package.  Refer to the specifications of the product.
•Extension power supply module:
  Tension clamp style: Front Twin Connection
  Applicable wire size: 0.2 to 1.5 mm2, stripped length 10 mm
Housing material: Flame-resistant resin (black)
Max. number of I/O modules: 16 (module address: 0 to 31)
Internal communication bus: Transmission cycle approx. 250 μsec / Module address
WEIGHT
  R8-NM1: 160g (0.35 lb)
  R8-NECT1: 180g (0.40 lb)
  R8-NEIP1: 180g (0.40 lb)
  R8-ND1: 180g (0.40 lb)
  R8-ND2: 180g (0.40 lb)
  R8-NC3: 180g (0.40 lb)
  R8-NC3A: 180g (0.40 lb)
  R8-CT4E: 65g (2.30 oz)
  R8-DA4A: 60g (2.12 oz)
  R8-DAM16A: 65g (2.30 oz)
  R8-DAT8A2: 110g (0.24 lb)
  R8-DAT8B2: 110g (0.24 lb)
  R8-DAT16A2: 110g (0.24 lb)
  R8-DAT16B2: 110g (0.24 lb)
  R8-DC4A: 60g (2.12 oz)
  R8-DC4A2: 60g (2.12 oz)
  R8-DC4C: 60g (2.12 oz)
  R8-DCT4D: 120g (0.26 lb)
  R8-DCM16A: 65g (2.30 oz)
  R8-DCM16ALZ: 110g (0.24 lb)
  R8-DCM16ALK: 110g (0.24 lb) 
  R8-DCM16ALH: 110g (0.24 lb) 
  R8-DCM32B2: 110g (0.24 lb)
  R8-DCT8A2: 110g (0.24 lb)
  R8-DCT8B2: 110g (0.24 lb)
  R8-DCT16A2: 110g (0.24 lb)
  R8-DCT16B2: 110g (0.24 lb)
  R8-FS16N: 110g (0.24 lb)
  R8-FST4N: 80g (0.18 lb)
  R8-PA4: 60g (2.12 oz)
  R8-PA4F: 60g (2.12 oz)
  R8-PC4A: 60g (2.12 oz)
  R8-PS1: 100g (0.22 lb)
  R8-RS4N: 60g (2.12 oz)
  R8-SS2: 60g (2.12 oz)
  R8-SS4N: 60g (2.12 oz)
  R8-SS4NJ: 60g (2.12 oz)
  R8-SST8: 100g (0.22 lb)
  R8-SV2: 60g (2.12 oz)
  R8-SV4N: 60g (2.12 oz)
  R8-SVT8: 100g (0.22 lb)
  R8-TC2: 110g (0.24 lb)
  R8-TS2: 60g (2.12 oz)
  R8-YS2: 110g (0.24 lb)
  R8-YS2NJ: 60g (2.12 oz)
  R8-YST4N: 120g (0.26 lb)
  R8-YV4N: 60g (2.12 oz)
  R8-YVM4N: 70g (2.47 oz)
  R8-YVT4N: 70g (2.47 oz)
  Protective cover: 15g  (0.53 oz)
DATA ALLOCATION
  R8-CT4E: 2
  R8-DA4A: 1
  R8-DAM16A: 1
  R8-DAT8A2: 1
  R8-DAT8B2: 1
  R8-DAT16A2: 1
  R8-DAT16B2: 1
  R8-DC4A: 1
  R8-DC4A2: 1
  R8-DC4C: 1
  R8-DCT4D: 1
  R8-DCM16A: 1
  R8-DCM16ALZ: 1
  R8-DCM16ALK: 1
  R8-DCM16ALH: 1
  R8-DCM32B2: 1
  R8-DCT8A2: 1
  R8-DCT8B2: 1
  R8-DCT16A2: 1
  R8-DCT16B2: 1
  R8-FS16N: 2
  R8-FST4N: 2
  R8-PA4: 2
  R8-PA4F: 2
  R8-PC4A: 2
  R8-RS4N: 2
  R8-SS2: 2
  R8-SS4N: 2
  R8-SS4NJ: 2
  R8-SST8: 2
  R8-SV2: 2
  R8-SV4N: 2
  R8-SVT8: 2
  R8-TC2: 2
  R8-TS2: 2
  R8-YS2: 2
  R8-YS2NJ: 2
  R8-YST4N: 2
  R8-YV4N: 2
  R8-YVM4N: 2
  R8-YVT4N: 2
ADDRESSES IN USE
  R8-CT4E: 2
  R8-DA4A: 1
  R8-DAM16A: 1
  R8-DAT8A2: 1
  R8-DAT8B2: 1
  R8-DAT16A2: 1
  R8-DAT16B2: 1
  R8-DC4A: 1
  R8-DC4A2: 1
  R8-DC4C: 1
  R8-DCT4D: 1
  R8-DCM16A: 1
  R8-DCM16ALZ: 1
  R8-DCM16ALK: 1
  R8-DCM16ALH: 1
  R8-DCM32B2: 2
  R8-DCT8A2: 1
  R8-DCT8B2: 1
  R8-DCT16A2: 1
  R8-DCT16B2: 1
  R8-FS16N: 8
  R8-FST4N: 2
  R8-PA4: 4
  R8-PA4F: 4
  R8-PC4A: 2
  R8-RS4N: 2
  R8-SS2: 1
  R8-SS4N: 2
  R8-SS4NJ: 2
  R8-SST8: 4
  R8-SV2: 1
  R8-SV4N: 2
  R8-SVT8: 4
  R8-TC2: 8
  R8-TS2: 1
  R8-YS2: 1
  R8-YS2NJ: 1
  R8-YST4N: 2
  R8-YV4N: 2
  R8-YVM4N: 2
  R8-YVT4N: 2

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

CURRENT CONSUMPTION

The I/O modules operate by the DC voltage (5 V DC) supplied from the power/network module. Arrange these modules in order that the total current consumed by these modules be within the supply current capacity. If the current consumption exceeds the limit, insert an extension power supply module. Even if total consumption current of the I/O modules is less than the supply current capacity, the total install number of the modules is max. 16. (Except extension power supply module)


Max. current consumption
R8-CT4E: 100 mA
R8-DA4A: 80 mA
R8-DAM16A: 100 mA
R8-DAT8A2: 100 mA
R8-DAT8B2: 100 mA
R8-DAT16A2: 100 mA
R8-DAT16B2: 100 mA
R8-DC4A: 100 mA
R8-DC4A2: 100 mA
R8-DC4C: 120 mA
R8-DCT4D: 100 mA
R8-DCM16A: 110 mA
R8-DCM16ALZ: 160 mA
R8-DCM16ALK: 160 mA
R8-DCM16ALH: 160 mA
R8-DCM32B2: 110 mA
R8-DCT8A2: 110 mA
R8-DCT8B2: 110 mA
R8-DCT16A2: 110 mA
R8-DCT16B2: 110 mA
R8-FS16N: 100 mA
R8-FST4N: 100 mA
R8-PA4: 80 mA
R8-PA4F: 90 mA
R8-PC4A: 100 mA
R8-RS4N: 100 mA
R8-SS2: 100 mA
R8-SS4N: 80 mA
R8-SS4NJ: 80 mA
R8-SST8: 200 mA
R8-SV2: 100 mA
R8-SV4N: 80 mA
R8-SVT8: 200 mA
R8-TC2: 200mA
R8-TS2: 100 mA
R8-YS2: 80 mA
R8-YS2NJ: 70 mA
R8-YST4N: 70 mA
R8-YV4N: 160 mA
R8-YVM4N: 160 mA
R8-YVT4N: 160 mA

USING EXCITATION SUPPLY

Some I/O modules use excitation supply, on the other hand some I/O modules do not. When excitation supply is cut off during power supply is on, operation is as the table shown below.

COMBINATION OF I/O MODULES

BASIC CONFIGURATION

The number of I/O modules that can be mounted changes depending on power/network module. Refer to the specifications of each power/network module for details.
Although Module address position can be set arbitrary, avoid from address overlap. 
4-point analog I/O module takes two addresses per module.  For example with the model R8-SV4N located at the module address 5, the inputs 1 and 2 are assigned to the address 5, and the inputs 3 and 4 are to the address 6.  Do not assign another module to the address 6.  All 4 inputs (input 1 through 4) can be used with Data Allocation 2, while only the inputs 1 and 3 can be used with Data Allocation 1.
Totalize pulse input 4 points module have 4 adresses available per module. Set to allocation area 2.
For modules which use more than 2 address, set address so that end address does not exceed 31. For totalize pulse input 4 points module, adddress should not exceed 28.
Only for rightmost module, set termination resistor to enable. Protective cover included for power/network modules.
■ HOW TO UNMOUNT MODULES

MOUNTING REQUIREMENTS unit: mm (inch)

SYSTEM CONFIGURATION EXAMPLES

■ POWER/NETWORK MODULE: R8-NM1