ES-2459 Rev.2

M5PP

Super-mini Terminal Block Signal Conditioners M5-UNIT

PULSE ISOLATOR

Functions & Features
• Galvanically isolates pulse rate signals
• Input frequency = output frequency
• Various outputs (open collector and voltage pulse)
• Power LED

MODEL: M5PP–[1][2][3]–R[4]

ORDERING INFORMATION

• Code number: M5PP-[1][2][3]-R[4]
Specify a code from below for each of [1] through [4].
  (e.g. M5PP-BMN-R/Q)
• Specify the specification for option code /Q
  (e.g. /C01/S01)

[1] INPUT

A1: Open collector (max. 10 kHz)
A2: Mechanical contact (max. 30 Hz)
B: Voltage pulse (max. 10 kHz)
I: Clamp-on pulse sensor CLSP

[2] OUTPUT

A1: High frequency open collector (max. 10 kHz)
A2: Low frequency open collector (max. 30 Hz)
M: 5 V pulse (max. 10 kHz)
N: 12 V pulse (max. 10 kHz)
P: 24 V pulse (max. 10 kHz)

[3] OUTPUT LOGIC

N: The same as the input
R: Inverted

POWER INPUT

DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[4] OPTIONS

blank: none
/Q: Options other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel

RELATED PRODUCTS

• Clamp-on pulse sensor (model: CLSP)

GENERAL SPECIFICATIONS

Construction: Terminal block
Connection: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel (standard) or stainless steel
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Frequency range: Input and output are the same.
Chattering protection: Filter provided for mechanical contact input
Power indicator LED: Green LED turns on when the power is supplied.
Input pulse sensing: DC coupled

INPUT SPECIFICATIONS

Excitation: 12 V DC @30 mA; shortcircuit protection
Open Collector
Maximum frequency
: 10 kHz
Pulse width time requirement: 10 μsec. min. for ON and OFF
Sensing: Approx. 12 V DC @3 mA
ON/OFF level: ≤ 600 Ω / 1.8 V for ON, ≥ 100 kΩ / 3.5 V for OFF
Mechanical Contact
Maximum frequency
: 30 Hz
Pulse width time requirement: 10 msec. min. for ON and OFF
Sensing: Approx. 12 V DC @3 mA
ON/OFF level: ≤ 200 Ω / 0.6 V for ON, ≥ 100 kΩ / 2.5 V for OFF
Voltage Pulse
Maximum frequency: 10 kHz
Pulse width time requirement: 10 μsec. min. for high and low levels
Waveforms: Square or sine
Hi/Lo level: 2 – 50 V DC for high level; ≤1 V DC for low level
Input impedance: 10 kΩ min.
Clamp-on Pulse Sensor CLSP
Maximum frequency: 50 000 pulses/hour
ON/OFF level: ≤ 400 Ω / 1.3 V for ON, ≥ 200 kΩ / 12 V for OFF

OUTPUT SPECIFICATIONS

High Frequency Open Collector:
50 V DC @100 mA (resistive load)
Maximum frequency: 10 kHz
Saturation voltage: 0.5 V DC
Low Frequency Open Collector:
50 V DC @100 mA (resistive load)
Maximum frequency: 30 Hz
Timer: Limits ≥ 75 msec. within 75 ±25 msec.
    ON time for output logic non-inverted
    OFF time for output logic inverted
Saturation voltage: 0.5 V DC
Voltage Pulse
Maximum frequency: 10 kHz
High level: Rating (5, 12 or 24 V) ±10 %
Low level: ≤ 0.5 V
Load resistance:
≥ 1.0 kΩ for 5 V
≥ 2.4 kΩ for 12 V
≥ 4.8 kΩ for 24 V

INSTALLATION

Power consumption
DC: Approx. 1.5 W
Operating temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: DIN rail
Weight: 80 g (2.8 oz)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute  (input to output to power to ground)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

FRONT VIEW

OUTPUT LOGIC

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM