ES-2471 Rev.3
M5YV
Super-mini Terminal Block Signal Conditioners M5-UNIT
ISOLATOR
Functions & Features
• Isolation of instrument unified signals (DC isolation between inputs and outputs)
• High-density mounting
• Power LED
MODEL: M5YV-[1][2]-R[3]
ORDERING INFORMATION
• Code number: M5YV-[1][2]-R[3]
Specify a code from below for each of [1] through [3].
(e.g. M5VS-6A-R
/Q)
• Special input and output ranges (For codes Z, 0, 01 & 02)
• Specify the specification for option code /Q
(e.g. /C01/VN/S01)
[1] INPUT
Current
A
: 4 – 20 mA DC (Input resistance 249 Ω)
Voltage
6
: 1 – 5 V DC (Input resistance 1 MΩ min.)
[2] OUTPUT
Current
A
: 4 – 20 mA DC (Load resistance 550 Ω max.)
Voltage
6
: 1 – 5 V DC (Load resistance 500 Ω min.)
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[3] OPTIONS
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
ADJUSTMENT
/VN
: Sealed adjustment holes
TERMINAL SCREW MATERIAL
/S01
: Stainless steel
GENERAL SPECIFICATIONS
Construction
: Terminal block
Connection
: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal
: Nickel-plated steel (standard) or stainless steel
Housing material
: Flame-resistant resin (black)
Isolation
: Input to output to power
Overrange output
: Approx. -10 to +110 % at 1 – 5 V
Zero adjustment
: -2 to +2 % (front)
Span adjustment
: 98 to 102 % (front)
Power indicator LED
: Green LED turns on when the power is supplied.
INPUT SPECIFICATIONS
■
DC Current
: Input resistor incorporated
■
DC Voltage
Input resistance
: 1 MΩ min. (10 kΩ min. in power failure)
INSTALLATION
Power consumption
•
DC
: Approx. 2 W
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 0 to 90 %RH (non-condensing)
Mounting
: DIN rail
Weight
: 80 g (2.8 oz)
PERFORMANCE in percentage of span
Accuracy
: ±0.1 %
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: ≤ 0.5 sec. (0 – 90 %)
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @1 minute (input to output to power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
FRONT VIEW
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM