ES-9668 Rev.3
R8-SVT8
Remote I/O R8 Series
DC VOLTAGE INPUT MODULE
(8 points, isolated, tension clamp terminal block)
Functions & Features
• 8 channels for DC voltage input, compact size remote I/O module
• Isolation between channels
• Input range adjustment with DIP switch or PC configurator
MODEL: R8–SVT8[1]
ORDERING INFORMATION
• Code number: R8-SVT8[1]
Specify a code from below for [1].
(e.g. R8-SVT8/UL/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] OPTIONS (multiple selections)
Standards & Approvals
blank
: CE marking
/UL
: UL approval, CE marking
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
RELATED PRODUCTS
• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R8CFG)
Downloadable at our web site.
GENERAL SPECIFICATIONS
Connection
•
Input
: Tension clamp
Applicable wire size
: 0.2 - 1.5 mm
2
Stripped length
: 10 mm
•
Excitation supply, internal bus
:
Connected to internal bus connector
•
Internal power
: Via bus connector
Isolation
: Input 1 to input 2 to input 3 to input 4 to input 5 to input 6 to input 7 to input 8 to exc. supply to internal bus or internal power
Input range
: Selectable with the side DIP SW
Module address
: With DIP switch
Terminating resistor
: Built-in (DIP Switch, default: disable)
Configuration mode
: With DIP switches on the side panel
Status indicator
: Bi-color (red/green) LED; Refer to the instruction manual.
Input status indicators
: Red LED; Refer to the instruction manual.
INPUT
Input range
: -10 – +10 V DC configurable
Operational
range
: :-5 - +105 % (in percentage of input range)
Input resistance
: ≥ 1 MΩ
INSTALLATION
Max. current consumption
: 200 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail
Weight
: 100 g (0.22 lb)
PERFORMANCE
Conversion accuracy
(in percentage of input range)
±0.05 % (@ input range -10 - +10 V)
Conversion accuracy is inversely proportional to input span.
Conversion accuracy computation example:
When input range is 1 - 5 V: conversion accuracy = nominal input span (20 V) ÷ input span (4 V) × 0.05(%) = 0.25 (%).
Nominal input span is the same as the span at input range
-10 - +10 V DC.
Conversion rate
: 8 msec.
Input circuit time constant
: Approx. 1 msec.
Data range
: 0 – 10000 of the input range
Data allocation
: 2
Module addresses in use
: 4
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
:
500 V AC @ 1 minute (input 1 to input 2 to input 3 to
input 4 to input 5 to input 6 to input 7 to input 8)
1500 V AC @ 1 minute (input to exc. supply to internal bus
or internal power to FG)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
Approval
:
UL/C-UL general safety requirements
(UL 61010-1, CAN/CSA-C22.2 No.61010-1-12)
(UL 61010-2-201, CAN/CSA-C22.2 No.61010-2-201)
Note: Use the Power/Network module for UL approval when using as conformity with UL/C-UL.
EXTERNAL VIEW
OPERATING MODE SETTING
(*) Factory setting
Caution ! - SW2-3, 2-4, 2-5, 2-7 are unused. Be sure to turn off unused ones.
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM