ES-4614 Rev.12

MEX-B

Final Control Elements

VALVE POSITIONER

(potentiometert feedback; built-in SSR)
Functions & Features
• Controlling an electric actuator powered with 100 V AC
• Feedback potentiometer 100 Ω – 10 kΩ
• Built-in SSR directly drives an AC motor
• Timer for motor's overheat protection
• Re-transmitted output
Typical Applications
• Single phase AC motor
• Loop powered isolator can be used for isolating between setpoint input signal and transmitter output signal
 

MODEL: MEX–B–[1][2]

ORDERING INFORMATION

• Code number: MEX-B-[1][2]
Specify a code from below for each of [1] and [2].
  (e.g. MEX-B-B/Q)
• Specify the specification for option code /Q
  (e.g. /C01/BD/S01)

[1] POWER INPUT

AC Power
B: 100 V AC
C: 110 V AC
D: 115 V AC
F: 120 V AC
G: 200 V AC
H: 220 V AC
J: 240 V AC

[2] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
Optional Process
/BD: Bonding
TERMINAL SCREW MATERIAL
/S01: Stainless steel

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection: M3.5 screw terminals
Screw terminal: Chromated steel (standard) or stainless steel
Housing material: Flame-resistant resin (black)
Deadband adjustment: 2 – 20 % (front)
Timer adjustment: 1 – 30 sec. (front)
Isolation: Input or xmtr output to output to power
Zero adjustment: 0 – 25 % (front)
Span adjustment: 75 – 100 % (front)

INPUT SPECIFICATIONS

Setpont Signal: 4 – 20 mA DC; input resistor incorporated
Input resistance: 100 Ω
Feedback Potentiometer: 100 Ω – 10 kΩ
Minimum span: 50 % of total resistance
Excitation: 0.4 V DC

OUTPUT SPECIFICATIONS

Re-Transmitted Output: 4 – 20 mA DC
Load resistance: 750 Ω max.
Control Output: SSR (zero-crossing);
60 – 280 V AC @ 0.1 – 1 A
Note 1: The incorporated SSR is not capable for driving 200 V AC motor.
Note 2: When driving relays with this control output, relays may operate erratically due to the leakage current at OFF of SSR. To avoid the problem, install a resistor (R) in parallel with the relay coil.
R < [Release Voltage] ÷ [[Leakage Current at OFF] – [Release Current]]
Leakage current at OFF: Approx. 10 mA @ 240 V

INSTALLATION

Power input
AC: Operational voltage range: rating ±10 %,
50/60 ±2 Hz, approx. 3 VA
Operating temperature: -5 to +60°C (23 to 140°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 300 g (0.66 lb)

PERFORMANCE in percentage of span

Position conversion accuracy: ±0.5 %
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1000 V AC @ 1 minute
(input or xmtr output to output to power)
2000 V AC @ 1 minute (input or xmtr output or output or power to ground)

EXTERNAL VIEW

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

EXPLANATIONS OF TERMS

SSR (Solid State Relay)
Composed only of semiconductor parts, SSR is free from arc discharge or chattering which is typical with electromagnetic relays. It features excellent characteristics against vibration, physical impact or other environmental conditions.
Zero-Cross Function
SSR with zero-cross function turns on when AC power voltage is near zero, creating delay of switching when input is provided in the middle of an wave cycle, thus limiting transient switching noise voltage and rush current.
• Bonding
An silicone adhesive reinforces the part, which is sensitive to vibration, on PWB. The improvement of vibration performance is not assured.