ES-8005-A Rev.2
R7F4HEIP-DA16A
Remote I/O R7F4HEIP Series
EtherNet/IP I/O MODULE
(NPN discrete input, 16 points, tension clamp terminal block)
Functions & Features
• 16 points NPN discrete input module for EtherNet/IP
• Supports DLR (Device Level Ring) to form a ring topology
MODEL: R7F4HEIP-DA16A-4-R[1]
ORDERING INFORMATION
• Code number: R7F4HEIP-DA16A-4-R[1]
Specify a code from below for [1].
(e.g. R7F4HEIP-DA16A-4-R/Q)
• Specify the specification for option code /Q
(e.g. /C01)
I/O TYPE
DA16A:
NPN discrete input, 16 points
TERMINAL BLOCK: 4
Tension clamp terminal block for power supply
RJ-45 Modular jack for communication
Tension clamp terminal block for I/O
POWER INPUT
DC power
R
: 24 V DC
(Operational voltage range: ±10 %; ripple 10 %p-p max.)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
RELATED PRODUCTS
• PC configurator software (model: R7CFG)
• EDS file
The EDS file and configurator software are downloadable at our web site.
A dedicated cable is required to connect the module to the PC. Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.
GENERAL SPECIFICATIONS
Connection
EtherNet/IP
: RJ-45 Modular Jack
Power supply, exc. supply, input
: Tension clamp terminal
Housing material
: Flame-resistant resin (gray)
Isolation:
Input or exc. supply to EtherNet/IP or FE to power
Status indicator LED
: PWR, LNK1, LNK2
(Refer to the instruction manual)
Discrete intput status indicator LED
: Green LED turns on with input ON
Read rate:
Selectable with R7CFG
EtherNet/IP COMMUNICATION
Communication Standard
: IEEE 802.3u
Transmission
: 10BASE-T, 100BASE-TX
Baud rate
: 10/100 Mbps (Auto Negotiation function)
Protocol
: EtherNet/IP
Max. number of socket connections
: 3
Connection type
: Exclusive owner / Listen only / Input only
Transmission media
: 10BASE-T (STP, Category 5), 100BASE-TX (STP, Category 5e)
Network topology
: Line, star and ring
Max. length of fieldbus segment
: 100 meters
IP address
: 192.168.0.250 (factory setting);
Only host address in IP address is configurable via rotary switches, the other items via PC configurator software (model: R7CFG).
DLR supported
Port No
.: 2222, 44818
I/O data size
: One (1) word
Status indicator LEDs
: MS, NS (Refer to the instruction manual for details)
INPUT SPECIFICATIONS
Common
: Positive common (NPN), 8 points per common
Numbers of input
: 16
Maximum inputs applicable at once:
No limit (at 24 V DC)
Rated input voltage
: 24 V DC ±10 %; ripple 5 %p-p max.
ON voltage / current
: ≥ 15 V DC (X0 to X15 input teriminal – +24 V) / ≥ 3.5 mA
OFF voltage / current
: ≤ 5 V DC (X0 to X15 input teriminal – +24 V) / ≤ 1.0 mA
Input current
: ≤ 5.5 mA per point at 24 V DC
Input resistance
: Approx. 4.4 kΩ
ON delay
: ≤ 0.2 msec.
OFF delay
: ≤ 0.5 msec.
INSTALLATION
Current consumption
•
DC
: Approx. 70 mA
(contact I/O load charge is not included)
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Surface or DIN rail (35 mm rail)
Weight
: 170 g (0.37 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength:
1500 V AC @ 1 minute
(input or exc. supply to EtherNet/IP or FE to power)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
PC CONFIGURATOR
The following parameters can be set with using PC Configurator Software (model: R7CFG)
Refer to the users manual for the R7CFG for detailed operation of the software program.
EXTERNAL VIEW
TERMINAL ASSIGNMENTS
■SENSOR EXC. / INPUT CONNECTION
■ POWER SUPPLY TERMINAL ASSIGNMENT
I/O DATA DESCRIPTIONS
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
MOUNTING REQUIREMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FE terminal to ground.
Caution: FE terminal is NOT a protective conductor terminal.