ES-3319 Rev.9
TSN
Super-mini Two-wire Signal Conditioners T-UNIT
INPUT LOOP POWERED ISOLATOR
Functions & Features
• Loop-powered design eliminates output loop power supply
• 500 V DC input-to-output isolation
• Highdensity mounting
Typical Applications
• Isolation between control room and field instrumentation, between telemetering system and input device
• Eliminates ground problems in existing systems thanks to easiness of application without requiring additional power wiring
MODEL: TSN–[1]
ORDERING INFORMATION
• Code number: TSN-[1]
Specify a code from below for [1].
(e.g. TSN-H6)
[1] INPUT / OUTPUT
blank
: 4 – 20 mA DC / 1 – 5 V DC
H6:
10 – 50 mA DC / 1 – 5 V DC
GENERAL SPECIFICATIONS
Construction
: Stand-alone; terminal access at the front
Connection
: Euro type terminal
(applicable wire size: 0.25 to 1.5 mm
2
, stripped length
7 mm)
Housing material
: Flame-resistant resin (black)
Isolation
: Input to output
Zero adjustment
: -5 to +5 % (front)
Span adjustment
: 95 to 105 % (front)
INPUT & OUTPUT
■ Input 4 – 20 mA DC / OUTPUT 1 – 5 V DC
Equivalent input impedance
: Approx. 250 Ω with 20 mA input
Operational range
: 3 – 22 mA DC
(Accuracy is assured within 4 – 22 mA)
Load resistance
: 50 kΩ min.
■ Input 10 – 50 mA DC / OUTPUT 1 – 5 V DC
Equivalent input impedance
: Approx. 100 Ω with 50 mA input
Operational range
: 7 – 55 mA DC
(Accuracy is assured within 8 – 55 mA)
Load resistance
: 50 kΩ minimum
•INPUT 4 – 20 mA DC / OUTPUT 1 – 5 V DC
•INPUT 10 – 50 mA DC / OUTPUT 1 – 5 V DC
INSTALLATION
Operating temperature
: -5 to +60°C (23 to 140°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface or DIN rail
Weight
: 120 g (0.26 lb)
PERFORMANCE in percentage of span
Accuracy
: ±0.1 %
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: ≤ 0.5 sec. (0 – 90 %)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 500 V AC @ 1 minute (input to output)
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM