ES-3317 Rev.12
TV
Super-mini Two-wire Signal Conditioners T-UNIT
SIGNAL TRANSMITTER
(non-isolated)
Functions & Features
• Converting a DC input into a standard 4 – 20 mA DC signal
• Monitor terminals
• High-density mounting
Typical Applications
• mV, voltage and current scaling
MODEL: TV–[1]
ORDERING INFORMATION
• Code number: TV-[1]
Specify a code from below for [1].
(e.g. TV-6)
• Special input range (For code 0)
[1] INPUT
Voltage
2
: 0 – 100 mV DC (Input resistance 50 kΩ min.)
3
: 0 – 1 V DC (Input resistance 1 MΩ min.)
4
: 0 – 10 V DC (Input resistance 2 MΩ min.)
5
: 0 – 5 V DC (Input resistance 2 MΩ min.)
6
: 1 – 5 V DC (Input resistance 1 MΩ min.)
0
: Specify voltage (See INPUT SPECIFICATIONS)
GENERAL SPECIFICATIONS
Construction
: Stand-alone; terminal access at the front
Connection
: Euro type terminal
(applicable wire size: 0.25 to 1.5 mm
2
, stripped length
7 mm)
Housing material
: Flame-resistant resin (black)
Zero adjustment
: -5 to +5 % (front)
Span adjustment
: 95 to 105 % (front)
INPUT SPECIFICATIONS
Input
: 0 – 300 V DC
Minimum span
: 0.1 V
Offset
: max. 0.25 times span
Input resistance
Input Span
:
Input Resistance
0.1 – 1 V: ≥ 50 kΩ
1 – 5 V: ≥ 1 MΩ
≥ 5 V : ≥ 2 MΩ
OUTPUT SPECIFICATIONS
Output
: 4 – 20 mA DC
Load resistance vs. supply voltage:
Load Resistance (Ω) = (Supply Voltage (V) – 12 (V)) ÷ 0.02 (A) (including leadwire resistance)
INSTALLATION
Supply voltage
: 12 – 28 V DC
Operating temperature
: -5 to +60°C (23 to 140°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface or DIN rail
Weight
: 120 g (0.26 lb)
PERFORMANCE in percentage of span
Accuracy
: ±0.1 %
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: ≤ 0.5 sec. (0 – 90 %)
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM