ES-8171 Rev.12

MA-100

Lightning Surge Protectors for
Electronics Equipment M-RESTER

LIGHTNING SURGE PROTECTOR FOR POWER SUPPLY

(2 A, 100 V / 110 V / 120 V AC)
Functions & Features
• Designed specifically for AC power supplies up to 2 amps
• No degradation of normal (50/60 Hz) line frequency
• Power indicator lamp provided

MODEL: MA–100[1]

ORDERING INFORMATION

• Code number: MA-100[1]
Specify a code from below for [1].
  (e.g. MA-100/CE)

[1] OPTIONS

Standards & Approvals
blank: Without CE
/CE: CE marking

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal: Chromated steel
Housing material: Flame-resistant resin (black)
Monitor lamp: Green neon lamp turns on when the power is supplied.

INSTALLATION

Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 330 g (0.73 lb)

PERFORMANCE

Discharge voltage (peak voltage)
  Line to line: 190 V min.
  Line to ground: 410 V min.
Maximum surge voltage
  Line to line: 350 V max.
  Line to ground: 700 V max.
(The maximum voltage that could pass through M-RESTER. Protected equipment must be able to withstand this voltage for very short time period.)
Response time: ≤ 0.1 μsec.
Leakage current
  Line to line: ≤ 1 mA at 150 V DC
  Line to ground: ≤ 1 mA at 300 V DC
Max. discharge current (Imax): 1000 A (8/ 20 μsec.)
Max. load current: 2 A
Voltage drop: ≤ 2 V (50/60 Hz)
Rated line voltage: 100 V / 110 V / 120 V AC

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
Low Voltage Directive 
  EN 61010-1
  Installation Category II
  Pollution Degree 2
RoHS Directive

CONNECTION EXAMPLES

GROUNDING

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENT unit: mm [inch]

SCHEMATIC CIRCUITRY