Functions & Features
• Designed specifically to protect devices connected to ISDN circuit from lightning surges
MODEL: MD-INS
ORDERING INFORMATION
• Code number: MD-INS
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
ISDN circuit
: Modular jack or M3.5 screw terminals
(torque 0.8 N·m)
Grounding
: M3.5 screw terminals
(torque 0.8 N·m)
Modular jack cord
: 6-pole, 2-core
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (black)
INSTALLATION
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface or DIN rail; Standard Rack Mounting Frame BX-16H available
Weight
: 150 g (0.33 lb)
PERFORMANCE
Discharge voltage (peak voltage)
Line to line: ±65 V min.
Line to ground: ±290 V min.
Maximum surge voltage
Line to line: ±100 V max.
Line to ground: ±650 V max.
(The maximum voltage that could pass through M-RESTER. Protected equipment must be able to withstand this voltage for very short time period.)
Response time
: ≤ 0.1 μsec.
Leakage current
Line to line: ≤ 50 μA at ±65 V DC
Line to ground: ≤ 50 μA at ±140 V DC
Discharge current capacity
Modular jack connection
: 500 A (8 / 20 μsec.)
Screw terminal connection
: 10000 A (8 / 20 μsec.)
Max. load current
: 100 mA
Internal series resistance
: Approx. 4 Ω including return
Maximum line voltage
: ±65 V
STANDARDS & APPROVALS
EU conformity
:
RoHS Directive
EXTERNAL VIEW
CONNECTION EXAMPLES
GROUNDING
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY