ES-3071 Rev.1
M50EXWTU
Terminal Block Signal Conditioners with Display M50E-UNIT
MULTI POWER TRANSDUCER
(PC programmable)
Functions & Features
• Super-mini power transducer
• 5 to 600 A clamp CT use for current sensor
• Single-phase/2-wire, single-phase/3-wire 3-phase/3-wire and 3-phase/4-wire are available
• Single phase can measure up to four circuits, single-phase/3-wire, Three-phase/2-wire can measure up to two circuits
• High-density mounting
• Organic EL display
MODEL: M50EXWTU-223-AD4[1]
ORDERING INFORMATION
• Code number: M50EXWTU-223-AD4[1]
Specify a code from below for [1].
(e.g. M50EXWTU-223-AD4
/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
CONFIGURATION
2
: Single phase / 2-wire and 3-wire,
3-phase / 3-wire and 4-wire
INPUT
2
: 480 V AC / CLSE
Clamp-on current sensor is selectable from below.
CLSE (5A, 50A, 100A, 200A, 400A, 600A)
5A is available as CT's secondary.
EXTERNAL INTERFACE
3
: Modbus communication
POWER INPUT
Universal
AD4
: 100 – 240 V AC / 100 – 240 V DC (universal)
(Operational voltage range 85 - 264 V AC, 47 - 66 Hz /
85 - 264 V DC, ripple 10 %p-p max.)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-3071)
RELATED PRODUCTS
• PC Configurator cable (model: COP-US)
• PC configurator software (model: PMCFG)
Downloadable at our web site.
• Clamp-on current sensor (model: CLSE)
GENERAL SPECIFICATIONS
Connection:
Tension clamp terminal
Applicable wire size:
Lower connector (voltage input, power, Modbus)
0.2 - 1.5 mm
2
, stripped length 8 - 9 mm
Upper connector (current sensor input, pulse output)
0.2 - 1.5 mm
2
, stripped length 10 - 11 mm
Housing material
: Flame-resistant resin (black)
Isolation
: Voltage input or current input to Modbus to pulse output 1 to pulse output 2 to power
Measured variables
Voltage
: 1-N, 2-N, 3-N, 1-2, 2-3, 3-1
Current
: 1, 2, 3, N
Active power
Reactive power
Apparent power
Power factor
Frequency
Active energy
: Incoming / outgoing
Reactive energy
: Incoming / outgoing / lag (inductive)
/lead (capacitive)
Harmonic distortion:
Overall distortion ratio, content rate (2nd to 31st)
Max. and min. values
CO
2
emissions (energy conversion value)
Simplified measurement mode:
Calculates power from current values with fixed voltage values and power factor.
MODBUS COMMUNICATION
Communication
: Half-duplex, asynchronous, no procedure
Standard
: Conforms to TIA/EIA-485-A
Transmission distance
: 500 meters max.
Baud rate
: 1200, 2400, 4800, 9600, 19200, 38400 bps (default: 38400 bps)
Protocol
: Modbus RTU
Node address
: 1 to 247 (default: 1)
Parity
: None, even or odd (default: odd)
Stop bit
: 1 or 2 (default: 1)
Max. number of nodes
: 31 (excluding master)
Transmission media
: Shielded twisted-pair cable
(CPEV-S 0.65 to 0.9 dia.)
Internal terminating resistor
:
110 Ω
DISPLAY
Display functions
: Displays measured value and status of the unit
Display size
: Approx. 14 × 40 mm (0.55” × 1.57”)
Character color
: Yellow
Brightness:
Standard or low brightness (default: standard)
Display life
: Approx. 120,000 hours
(Expected time for the Display brightness to be reduced to 50 % when the Display is used continuously with low brightness in 25 ℃)
Operating mode:
Automatically turn off after no operation, or always on
(default: automatically turn off after no operation for 10 minutes)
Display type
: OEL display
INPUT SPECIFICATIONS
Frequency
: 50 / 60 Hz (45 – 66 Hz)
•
Voltage Input
Rated voltage for each wiring
:
• Single-phase/2-wire rated voltage 240 V AC
• Single-phase/3-wire phase voltage 240 V AC / line voltage 480 V AC
• Three-phase/3-wire line voltage 240 V AC
(480 V AC when voltage to ground for each line is ≤ 277 V)
• Three-phase/4-wire phase voltage 277 V / line voltage 480 V AC
Input range
: 1-N, 2-N, 3-N 50 to 277 V AC
1-2, 2-3, 3-1 50 to 480 V AC
Consumption VA:
Voltage circuit ≤ ULN
2
/ 250 kΩ / ph
Selectable primary voltage range
: 50 – 400 000 V
•
Current Input
Current sensor (default: CLSE-R5)
CLSE-R5
: 0 – 5 A AC
CLSE-05
: 0 – 50 A AC
CLSE-10
: 0 – 100 A AC
CLSE-20
: 0 – 200 A AC
CLSE-40
: 0 – 400 A AC
CLSE-60
: 0 – 600 A AC
Input range:
0 - 120% of the rating
Low-end cutout (current):
0 - 99.9% (default setting: 1%)
Selectable primary current range
: 1 – 20 000 A (only with CLSE-R5, refer to the configurator settings)
OUTPUT SPECIFICATIONS
■
Pulse output
Outputs assignable to pulse
: various energy
Output type
: Photo MOSFET relay
Rated load
: 30 V 200 mA AC/DC at peak
ON resistance
: 1 Ω max.
Leakage current during opening
: 2 μA max.
INSTALLATION
Power consumption
•
AC
: Max. 3 VA
•
DC
: ≤ 1.5 W
Operating temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: DIN rail
Weight
: 90 g (0.2 lb)
PERFORMANCE
Accuracy
*1
Voltage
: ±0.5 %
*2
Current
: ±0.5 %
*2
Power
: ±0.5 %
*2
Power factor
: ±1.5 %
Frequency
: ±0.1 Hz
Energy
: ±2 % (power factor ≥ 0.5, input ≥ 10%)
*1. Sensor error margin not included. Add sensor error margin when using with the combination of the sensor.
*2. The described accuracy levels are ensured at the input 1% or more for neutral current in a single-phase/3-wire circuit, phase-2 current in a 3-phase/3-wire circuit and phase-N current in a 3-phase/4-wire circuit.
Temp. coefficient:
±0.0075 %/°C (0.004 %/°F)
Sampling time
: ≤ 500 msec.
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @ 1 minute
(current input or voltage input to Modbus to pulse output 1 or pulse output 2 to power)
500 V AC @ 1 minute (pulse output 1 to pulse output 2)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Measurement Category II (input)
Installation Category II (power supply)
Pollution Degree 2
Voltage input to current input or Modbus or pulse output:
Reinforced insulation (300 V)
Power to current input or Modbus or pulse output:
Reinforced insulation (300 V)
RoHS Directive
EXTERNAL VIEW
TERMINAL CONNECTIONS
MODBUS WIRING CONNECTION
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM