ES-9044 Rev.2
JC-IO
Remote I/O JC Series
I/O CONNECTION MODULE
Functions and features
• I/O mapping function connects the I/O from devices on the network.
• Supporting Modbus/TCP client and SLMP client
• Transmitting the data between deferent protocol
• Monitoring input value and configuring output value via web browser
MODEL: JC-IO–N-R[1]
ORDERING INFORMATION
• Code number: JC-IO-N-R[1]
Specify a code from below for [1].
(e.g. JC-IO-N-R/Q)
• Specify the specification for option code /Q
(e.g. /C01)
MODULE TYPE
N
: Standard
POWER INPUT
DC power
R
: 24 V DC
(Operational voltage range: ±10 %; ripple 10 %p-p max.)
[1] OPTIONS
blank
: none
/Q
: Options other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
RELATED PRODUCTS
• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: JCIOCFG)
PACKAGE INCLUDES...
• Protective cover
• Ferrite core
GENERAL SPECIFICATIONS
Connection
•Power supply, RUN contact output:
Tension clamp terminal (Front Twin connection)
Unit side connector: MSTB2,5/5-GF-5,08AU
Cable side connector: TFKC2,5/5-STF-5,08AU
(Applicable wire size: 0.2 - 2.5 mm
2
, stripped length 10 mm)
Recommended solderless terminal
AI0,25-10YE 0.25 mm
2
(Phoenix Contact)
AI0,34-10TQ 0.34 mm
2
(Phoenix Contact)
AI0,5-10WH 0.5 mm
2
(Phoenix Contact)
AI0,75-10GY 0.75 mm
2
(Phoenix Contact)
AI1-10RD 1.0 mm
2
(Phoenix Contact)
AI1,5-10BK 1.5 mm
2
(Phoenix Contact)
AI2,5-10BU 2.5 mm
2
(Phoenix Contact)
•Ethernet:
RJ-45 connector
Housing material
: Flame-resistant resin (gray)
Isolation
: Ethernet to power supply to RUN contact output to FE
Calendar clock:
Year (4 digits), month, date, day, hour, minute, second
Status indicator LED: POWER, RUN, COM, ERROR
RUN contact output
: Photo MOSFET relay (no polarity);
(OFF in error detected)
•Peak load voltage: 50 V max.
•Continuous load current: 50 mA max.
•Peak load current: 300 mA max. (≤0.1 sec.)
•Operation
Power down: OFF
Firmware operating: ON
Error in Ethernet LNK: OFF
ETHERNET COMMUNICATION
Communication Standard
: IEEE 802.3u
Transmission
: 10BASE-T, 100BASE-TX
Baud rate
: 10/100 Mbps (Auto Negotiation function)
Protocol
: TCP/IP, Modbus/TCP, SLMP, HTTP, SNTP
Transmission media
: 10BASE-T (STP, Category 5)
100BASE-TX (STP, Category 5e)
Max. length of fieldbus segment
: 100 meters
INSTALLATION
Power consumption
•
DC
: Approx. 2 W 24 V DC
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail
Weight
: 190 g (0.42 lb)
PERFORMANCE
Battery:
Vanadium-lithium secondary battery (undetachable)
Calendar clock accuracy
: Monthly deviation 2 minutes at 25°C
Battery backup
: Approx. 2 months
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (Power to Ethernet to RUN contact output to FE)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
CONNECTION DIAGRAMS
EXTERNAL DIMENSIONS unit: mm [inch]
■UNIT
■PROTECTIVE COVER
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FE terminal to ground.
Caution: FE terminal is NOT a protective conductor terminal.
COMMUNICATION
IP:
DHCP client is supported. Manual setting of IP address,
subnet mask, default gateway and DNS server available too.
Modbus/TCP master:
I/O expansion with remote I/O, e.g. R3 or R7 series, is
available. Measuring points in multiple locations can be
handled collectively.
Connectable Devices (Modbus/TCP)
· TR30-G
· DL8
· DL30
· R30NE1
· R3-NE1
· R3-GE1
· R7E
· R9EWTU
· R6-NE1
· R6-NE2
· R5-NE1
· D3-NE1
· D3-NE2
· D3-GE2
· D5-NE1
· IB10W2
· IB10W4
· IB10WS2
· WL40EW2
· WL40EWS2
· 72EM2-M4
· GR8-EM
· IT series
· SG6
SLMP Client:
JC-IO allows I/O expansion by connecting with the SLMP compatible CPU unit of Mitsubishi programmable-controller MELSEC; and collectively handles data from measuring
points in multiple locations.
Connecting Device (SLMP sever)
· MELSEC iQ-R series
· MELSEC iQ-F series
· MELSEC Q series
Max. no. of connectable devices
32 nodes (selectable from Modbus/TCP and SLMP devices)
Web server function (Direct):
This unit can be a web server, and manually operate to monitoring input status and setting output values via browser.
Compatible Terminals & Browsers
・Windows 10 (32bit/64bit)
Firefox: 126.0
Chrome: 125.0
Edge: 125.0
・Windows 11 (64bit)
Firefox: 126.0
Chrome: 125.0
Edge: 125.0
・iPadOS 17.5.1
Safari
・Android 14
Chrome: 125.0
Max. number of I/O modules
: 4
I/O MAPPING
Registration of Input-to-Internal register-to-Output mapping information allows multiplex data transmission for remote I/Os via internal register and allows JC-IO to work as an IP telemeter.
· Internal register
L: A register to save 32-bits data. Possible to allocate max. 256 points.
S: A register to save 16-bits data. Possible to allocate max. 256 points.
Allocating upper/lower 16-bit of L as 16 -it data is possible.
B: A register to save 1-bit data. Possible to allocate max. 512 points. Allocating a spesific bit of L or S as 1-bit data is possible.
P: A register to save 32-bit data and to output differential value of previous sampling as 16 bit data. Possible to allocate max. 256 points.
OTHER FUNCTIONS
Configuration: Configurable with the dedicated software model: JCIOCFG
Time zone: Selectable between –12:00 and +13:00
SYSTEM CONFIGURATION EXAMPLES
Devices other than the JC-IO in the configuration below shall be provided by the user.