ES-8105 Rev.6
MDPA-65
Lightning Surge Protectors for
Electronics Equipment M-RESTER
LIGHTNING SURGE PROTECTOR FOR
STANDARD SIGNAL LINE & PULSE USE
Functions & Features
• Designed specifically for 4 – 20mA DC and
pulse signal line including both 4-wire and 2- wire transmitters
• Life monitor function helps you to decide when you should replace the surge protector; reduces maintenance and prevents downtime
• Pressing CHK (Check) button confirms the degradation and life span of the surge protection circuits with LEDs
• Absorbs surges only without affecting instrumentation signal
• No interruption of signal by unplugging surge protector element
MODEL: MDPA–65[1]
ORDERING INFORMATION
• Code number: MDPA-65[1]
Specify a code from below for [1].
(e.g. MDPA-65/BN/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] OPTIONS (multiple selections)
Configuration
blank
: With Base (model: SK-2E) included
/BN
: Element only for replacement
(Not selectable with DIN rail mounting adapter)
DIN Rail Mounting Adapter
blank
: Without
/A33
: With adapter (model A-33)
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
RELATED PRODUCTS
• Base (model: SK-2E)
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
: M4 screw terminals (torque 0.8 N·m)
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (black)
Indicators
: Activated by CHK (Check) button, see the status table shown below.
BAT
: Green LED
ALM
: Red LED
Degradation judged
: When the leakage current at the voltage limiter exceed approx. 7.5 μA.
Life time judged
: When the number of discharges of the discharge element reaches the expected life span.
CHK button
: Push button; momentary
Battery
: Lithium; No recharge or replacement available.
Battery life
: 10 years (when used ≤ 2 minutes/month)
INSTALLATION
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 85 %RH (non-condensing)
Mounting
: Surface or DIN rail
Weight:
150 g (0.33 lb), standard
175 g (0.39 lb), with DIN rail mounting adapter
Capacitance (reference value) @ 1 MHz
:
Line to line: 2000 pF
Line to earth: 100 pF
PERFORMANCE
Max. continuous operating voltage
(Uc)
:
Line to line: 70 V
Line to earth: ±160 V
Voltage protection level (Up)
:
• @ 1 kV (100 A)
Line to line: 85 V
Line to earth: ±650 V
• @ 2 kV (1 kA)
Line to line: 100 V
Line to earth: ±650 V
Response time
:
Line to line: ≤ 4 nsec.
Line to earth: ≤ 20 nsec.
Leakage current
:
Line to line: ≤ 5 μA @ 70 V DC
Line to earth: ≤ 5 μA @ ±140 V DC
Max. discharge current (Imax)
: 5000 A (8 / 20 μs)
Nominal current (I
N
)
: 100 mA
Internal series resistance
: 20 Ω ±10 % (including return)
Surge protection
: IEC 61643-21 Categories C1, C2, D1
EXTERNAL VIEW
CONNECTION EXAMPLES
GROUNDING
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
MOUNTING REQUIREMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM