ES-3421 Rev.15

HVP

Space-saving Plug-in Signal Conditioners H-UNIT

I/P TRANSDUCER

Functions & Features
• Converting a DC input into a proportional standard pneumatic signal
• Semiconductor pressure sensor in the feedback circuit
• High resolution
• No mounting position effect
• High-density mounting
Typical Applications
• Converting a 4 – 20 mA from a PID controller into a pneumatic signal
 

MODEL: HVP–[1]–R[2]

ORDERING INFORMATION

• Code number: HVP-[1]-R[2]
Specify a code from below for each of [1] and [2].
  (e.g. HVP-6-R/A2S/P7)

[1] INPUT

Current
A: 4 – 20 mA DC (Input resistance 250 Ω)
Voltage
6: 1 – 5 V DC (Input resistance 1 MΩ min.)

POWER INPUT

DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[2] OPTIONS (multiple selections)

Output
blank: 0.2 – 1.0 kgf/cm2
/A1S: 19.6 – 98.1 kPa
/A2S: 20 – 100 kPa
/A3S: 20.7 – 103.4 kPa
/A2: 0.2 – 1.0 bar
/A3: 3 – 15 psig
Pneumatic Connection
blank: Rc 1/4"
/P7: 1/4" NPT fitting

RELATED PRODUCTS

Mounting Block is required. See the data sheet for model MB.
• Code number of the Mounting Block (e.g. MB-08)

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection
  Input & power input
: M3.5 screw terminals (torque 0.8 N·m)
  Pneumatic: Rc 1/4" or 1/4" NPT female; (torque ≤ 12 N·m)
Material
Housing: Flame-resistant resin (black)
Base socket: Die cast aluminium
Valve section: Die cast aluminium
Screw terminals: Nickel-plated steel;
Isolation: Input to power
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)

INPUT SPECIFICATIONS

DC Current:
Shunt resistor attached to the input terminals (0.5 W)

OUTPUT SPECIFICATIONS

Output:
19.6 – 98.1 kPa, 0.2 – 1.0 kgf/cm2
20 – 100 kPa, 0.2 – 1.0 bar
20.7 – 103.4 kPa, 3 – 15 psig
The output goes below 0 % if the input loop is open.
Maximum air delivery: 60 Nl/minute (2.1 SCFM)
Maximum air exhaust: 60 Nl/minute (2.1 SCFM)

INSTALLATION

Supply pressure: 140 kPa (1.4 kgf/cm2, 1.4 bar, 20 psig)
±10 %. Use dry air containing no carbon black or other foreign particles. To ensure reliability use an air filter (0.01 microns).
Air consumption: 6 Nl/minute (0.21 SCFM)
Current consumption: Approx. 30 mA
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface; Standard Rack Mounting Frame (BX-16H) available
Weight: 400 g (0.88 lb)

PERFORMANCE in percentage of span

Accuracy: ±0.3 % including linearity and repeatability
Linearity: ±0.2 %
Repeatability: 0.1 %
Temp. coefficient: ±0.05 %/°C (±0.03 %/°F)
Response time: ≤ 3 sec. (0 – 90 %)
Mounting position effect: ±0.1 % (all dimensions)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute
(input to power)
1500 V AC @ 1 minute (input or power to housing)

EXTERNAL DIMENSIONS unit: mm [inch]

TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM