ES-9803 Rev.9
MP1200
Limit Alarms M-PAC
RTD INPUT LIMIT ALARM
Functions & Features
• Accepting standard thermocouple inputs and providing relay contact closure(s) at a preset input level
• Cold junction compensation and upscale burnout protection as standard
• Downscale or no burnout optional
• Single, latching or dual setpoint
• Failsafe operation available
• Deadband adjustable from 1 to 100%
• Indicator LED provided
Typical Applications
• Annunciator
• Various alarm applications
MODEL: MP12[1][2]-[3]-[4]/[5]
ORDERING INFORMATION
• Code number: MP12[1][2]-[3]-[4]/[5]
Specify a code from below for each of [1] through [5].
(e.g. MP1200-2-F/T/V)
• Temperature range (e.g. 0 – 800°C)
[1] RELAY CONTACT OUTPUT
0
: Single (Hi) trip, non-latching
1
: Single (Hi) trip, latching
2
: Dual (Hi/Lo) trip, non-latching
[2] SETPOINT CONTROL
0
: Front-accessed three-turn screwdriver adjust
2
: Remote dial connections (total resistance 1 k – 100 kΩ)
3
: DC programmable (0 – 1 V DC)
[3] INPUT THERMOCOUPLE
Srandard Span (10 mV ≤ EMF)
1
: (PR)
2
: K (CA)
3
: E (CRC)
4
: J (IC)
5
: T (CC)
6
: B (RH)
7
: R
8
: S
0
: Specify
Narrow Span (3 mV ≤ EMF < 10 mV)
1L
: (PR)
2L
: K (CA)
3L
: E (CRC)
4L
: J (IC)
5L
: T (CC)
6L
: B (RH)
7L
: R
8L
: S
0L
: Specify
[4] POWER INPUT
AC Power
F
: 120 V AC
J
: 240 V AC
DC Power
S
: 12 V DC
R
: 24 V DC
[5] OPTIONS
H
: Latching operation for dual trip;
reset at power off (5 seconds min.)
(dual trip type only)
R
: Reversed relay sense
T
: Transmitter output (0 – 1 V DC)
V
: Relay drive voltage output
X
: Lo-trip sense for single trip; Lo/Lo for dual trip
Y
: Hi/Hi-trip sense for dual trip (dual trip type only)
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
: M3.5 screw terminals
Screw terminal:
Chromated steel
Housing material
: Flame-resistant resin (black)
Isolation
: Input to output to power
(non-isolated between I/O with Option V)
Zero adjustment
: -5 to +5 % (front)
Span adjustment
: 95 to 105 % (front)
Setpoint adjustments
: Front accessed three-turn screwdriver, remote dial potentiometer or DC input
Deadband adjustments
: Front accessed single-turn screwdriver; 1 – 100 %
Burnout
: Upscale standard; downscale or no burnout optional
Cold junction compensation
: CJC sensor attached to the
input terminals
Front LEDs
: Red LED turns on at a tripped condition
Power ON timer
: Relays de-energized for approx. 2 seconds after power is turned on.
INPUT SPECIFICATIONS
■ Input:
Thermocouples
Minimum span
: Standard span 10 mV min., narrow span 3 mV min.
Offset
: Max. 1.5 times span
Input resistance
: 10 kΩ min.
Burnout sensing
: 0.1 μA
Minimum span requirement
*
STANDARD (≥ 10 mV)
K (CA)
: 247°C, 445°F
E (CRC)
: 153°C, 282°F
J (IC)
: 186°C, 339°F
T (CC)
: 214°C, 394°F
R
: 962°C, 1751°F
S
: 1036°C, 1883°F
Others
: Consult factory or representatives.
NARROW (< 10 mV)
K (CA)
: 74°C, 135°F
E (CRC)
: 50°C, 92°F
J (IC)
: 58°C, 106°F
T (CC)
: 73°C, 135°F
R
: 361°C, 665°F
S
: 373°C, 686°F
Others
: Consult factory or representatives.
*Approximate values to obtain minimum e.m.f. span for your reference. Consult thermocouple reference tables, factory or representatives for confirmation.
■ Setpoint Control
•
Remote dial connections
Potentiometer
: Total resistance 1 k – 100 kΩ
Excitation
: 4 V DC
•
DC programmable
: 0 – 1 V DC
OUTPUT SPECIFICATIONS
■
Relay Contact
•
Single / Latching
: Isolated DPDT relay; de-energized at trip
• Dual
: Isolated SPDT relay; energized at trip
Rating
: 120 V AC @ 3 A (cosø=1)
30 V DC @ 3 A (resistive load)
Electrical
life
: 10
5
cycles
Mechanical
life
: 10
7
cycles
For maximum relay life with inductive loads, external protection is recommended.
■
Relay Drive Voltage Output (option V)
: 24 V DC average; drives 1.2 kΩ or greater coil impedance
■
Transmitter Output (option T)
: 0 – 1 V DC; 1 mA max. (setpoint and process input)
INSTALLATION
Power input
•
AC
: Operational voltage range: rating ±10 %,
50/60 ±2 Hz, approx. 2 VA
•
DC
: Operational voltage range: rating ±10 %
ripple 10 %p-p max.
80 mA at 24 V
160 mA at 12 V
Operating temperature
: -5 to +60°C (23 to 140°F)
Storage temperature
: -20 to +85°C (-4 to +185°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface (DIN rail available for 11-pin base)
Weight
: 400 g (0.88 lb)
PERFORMANCE in percentage of span
Repeatability
: ±0.2 %
Cold junction compensation error
: (at 20°C ±10°C or 68°F ±18°F)
K, E, J & T: ±0.5°C or ±0.9°F
S, R & PR: ±1°C or ±1.8°F
Temp. coefficient
: ±0.05 %/°C (±0.03 %/°F)
Response time
: ≤ 0.5 sec. (0 – 100 % at 90 % setpoint)
Burnout response
: 1 sec.
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1000 V AC @ 1 minute
(input to output to power)
2000 V AC @ 1 minute (output to ground)
Common mode noise rejection
:
60 Hz
: Greater than 120 dB
DC
: Greater than 140 dB
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
MOUNTING REQUIREMENTS unit: mm [inch]
BLOCK DIAGRAM
I/O TERMINAL ASSIGNMENT