ES-3137 Rev.10

BCT

Space-saving Two-wire Signal Conditioners B-UNIT

CT TRANSMITTER

Functions & Features
• Converting an alternating current from a current transformer into an isolated 4 – 20 mA DC signal
• Minimal ripple
• True RMS sensing
• CT Protector provided for open-circuit protection
• Monitor terminals
• High-density mounting
Typical Applications
• Centralized monitoring and control of motors, pumps or heaters by DCS
• Monitoring power line and power supply current

MODEL: BCT–[1][2]

ORDERING INFORMATION

• Code number: BCT-[1][2]
Specify a code from below for each of [1] and [2].
  (e.g. BCT-1/Q)
• Specify the specification for option code /Q
  (e.g. /C01/S01)

[1] INPUT

Current
1: 0 – 1 A AC
5: 0 – 5 A AC

[2] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel (standard) or stainless steel
Housing material: Flame-resistant resin (black)
Isolation: Input to output
Input waveform: Up to 15 % of 3rd harmonic content
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)

INPUT SPECIFICATIONS

Frequency: 50 or 60 Hz
Input burden: 0.5 VA maximum
Overload capacity: 1000 % of rating for 3 sec., 200 % for 10 sec., 120 % continuous
Operational range: 0 – 120 % of rating

OUTPUT SPECIFICATIONS

Output: 4 – 20 mA DC
Load resistance vs. supply voltage:
Load Resistance (Ω) = (Supply Voltage (V) – 12 (V)) 
÷ 0.02 (A)     (including leadwire resistance)

INSTALLATION

Supply voltage: 12 – 60 V DC
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail; Standard Rack Mounting Frame BX-16H available
Weight: 160 g (0.35 lb)

PERFORMANCE in percentage of span

Accuracy: ±0.3 %
Temp. coefficient: ±0.03 %/°C (±0.02 %/°F)
Response time: ≤ 0.5 sec. (0 – 90 %)
Ripple: 0.5 %p-p max. (100/120 Hz)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute (input to output)
1500 V AC @ 1 minute (input or output to ground)

EXTERNAL DIMENSIONS unit: mm [inch]

TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM