ES-9655 Rev.0

R8-PAT4F

Remote I/O R8 Series

HIGH-SPEED TOTALIZED PULSE INPUT MODULE, 4 points

(NPN input)
Functions & Features
• Space-saving remote I/O module of 4 points input pulse counter
• Each channel is atachable/detachable independently with separable tension clamp terminal

MODEL: R8–PAT4FA[1]

ORDERING INFORMATION

• Code number: R8-PAT4FA[1]
Specify a code from below for [1].
  (e.g. R8-PAT4FA/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

INPUT

A: NPN input

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating

RELATED PRODUCTS

• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R8CFG)
Downloadable at our web site.
Note: When using with Power/Network module (model: R8-NECT1), firmware version Ver1.50 or later is supported.

GENERAL SPECIFICATIONS

Connection
 • Input: Separable tension clamp terminal
 Excitation supply, internal bus:
    Connected to internal bus connector
 • Internal power: Via bus connector
Isolation: Input or exc. supply to internal bus or internal power
Module address: With rotary switch
Terminating resistor: Built-in (DIP Switch, default: disable)
Status indicator: Bi-color (red/green) LED; Refer to the instruction manual.
Input status indicator: Green LED; Refer to the instruction manual.

INPUT SPECIFICATIONS

Common: Positive common (NPN) per 4 points
Number of inputs: 4
I/O status indicator: LED turns on with closed contact.
NPN input (internal supply with excitation supply input from network power module)
  Rated load voltage: 24 V DC ±10 %; ripple 5 %p-p max.
  ON voltage / ON current: ≥ 16 V DC (input terminal to COM) / ≥ 7.2 mA
  OFF voltage / OFF current: ≤ 6 V DC (input terminal to COM) / ≤ 2.5mA
  Input current: 11.2 mA / point (@24 V DC)
  Input resistance: Approx. 2 kΩ
Max. Frequency: 10 kHz
Min. pulse width requirement: 20 μsec. for both ON and OFF
Accumulated pulse count: 0 - 4 294 967 295
Max. accumulable pulse: 1 - 4,294,967,295 (factory setting: 4,294,967,295)
Overflow reset value
: 0 or 1 (factory setting: 0)

INSTALLATION

Max. current consumption: 90 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail
Weight: 80 g (2.8 oz)

PERFORMANCE

Data allocation: 2
Module addresses in use: 4
Power output (input connector): Rated current 0.1 A DC per channel (rated current 3 A for internal fuse (slow blow fuse i2t (A2sec.) max. 0.31); Total: 0.4 A DC
Input data update period: 10 msec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(input or exc. supply to internal bus or internal power to ground)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

WIRING

■ SEPARABLE TENSION CLAMP TERMINAL
Unit side connector:
MG's product
Cable side connector: DFMC1,5/2-ST-3,5 (Phoenix Contact) (included in the package)
Applicable wire size: 0.2 - 1.5 mm2
Stripped length: 10 mm
Recommended solderless terminal
 • AI0,25-10YE 0.25 mm2 (Phoenix Contact)
 • AI0,34-10TQ 0.34 mm2 (Phoenix Contact)
 • AI0,5-10WH 0.5 mm2 (Phoenix Contact)
 • AI0,75-10GY 0.75 mm2 (Phoenix Contact)
 • A1-10 1.0 mm2 (Phoenix Contact)
 • A1,5-10 1.5 mm2 (Phoenix Contact)

OPERATING MODE SETTING

(*) Factory setting

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM