ES-4564-5 Rev.0

38D2-5

DCS Input/Output Relay Card Series

OUTPUT RELAY CARD

(high load current type)
Functions & Features
• Standard with a voltage output for driving electromagnetic valve and a relay contact (5 A)
• Test switch and LED help debugging and monitoring
• Fuse provided to each channel
 

MODEL: 38D2-5[1]

ORDERING INFORMATION

• Code number: 38D2-5[1]
Specify a code from below for [1].
  (e.g. 38D2-51)

INPUT

Dry contact or open collector

OUTPUT

Relay contact and voltage

[1] TEST SWITCH

0: Non-lock switch
1: Lock switch

RELATED PRODUCTS

• Standard Rack (model: 38D2-B)

GENERAL SPECIFICATIONS

Construction: Rack mounted; terminal access via screw terminals at the front and via connector at the rear
Connection
  Input
: Card-edge connector
  Relay & voltage output: M3.5 screw terminals
  (torque 0.8 N·m)
  Power input: Supplied from card-edge connector
Screw terminal: Nickel-plated steel
Isolation: Input or power to output
Power fuse: 0.5 A incorporated
Alarm contact: Dry contact output at the alarm output terminals of the rack when the fuse is blown
Indicator LED: Red LED turns on when the coil is energized.
Test switch
 AUTO: Relay energized at ON input
 OFF: Forced relay de-energized
 ON: Forced relay energized

INPUT SPECIFICATIONS

Input: Dry contact or open collector
Contact detecting: 24 V DC @ 45 mA

OUTPUT SPECIFICATIONS

VOLTAGE OUTPUT: 100 V AC or 24 V DC ±10 %
Load current: 0.5 A max. (8 A max. in the total of 16 cards)
Spark quenching diode: Close across the jumper pin on the PCB with voltage output
RELAY CONTACT OUTPUT: SPDT
Rating: 120 V AC or 24 V DC @ 5 A (resistive load)
Maximum switching rating: 250 V AC @ 2 A or 125 V DC @ 0.2 A (resistive load)
Relay life
Mechanical
: 5 × 107 cycles
Electrical: 105 cycles (30 cycles/min.)

INSTALLATION

DC: Operational voltage range 24 V ±10 %; ripple 10 % p-p max.,approx. 45 mA
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Standard Rack 38D2-B
Weight: 100 g (0.22 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1000 V AC @ 1 minute
(input or power to output)
2000 V AC @ 1 minute (output to ground)

EXTERNAL VIEW

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]