ES-4564-B1 Rev.0
38D2-B
DCS Input/Output Relay Card Series
STANDARD RACK
(high load current type)
Functions & Features
• 16 points per rack
• Standard rack receives either input cards or output cards
MODEL: 38D2-B[1]-[2][3]
ORDERING INFORMATION
• Code number: 38D2-B[1]-[2][3]
Specify a code from below for each of [1] through [3].
(e.g. 38D2-B1-K/W)
[1] CONNECTOR
1
: FCN type connector
2
: FCN type connector (plus FCN connector
to couple the nest with another)
Y1
: Yokogawa KS2 cable use
Y2
: Yokogawa KS9 cable use
K2
: Azbil DCS DO use + coupling connector
[2] POWER INPUT
AC Power
K
: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[3] OPTIONS
Mounting Bracket
blank
: Rack mounting, standard
/W
: Surface mounting
RELATED PRODUCTS
• Connector terminal block (model: CNT)
• Special cable with 40-pin connector (model: FCN)
GENERAL SPECIFICATIONS
Construction
: Metal plates assembly
Coating
: Zn-Cr (black), alumetized steel
Capacity
: 16 positions
Connection
Power, alarm, voltage output
: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal
: Nickel-plated brass
Isolation
: I/O connector to power to alarm output to voltage output to FG (For Azbil connector: I/O connector or power to alarm output to voltage output to FG)
Alarm output
: Dry contact output provided when a fuse on the relay cards is blown.
INSTALLATION
Power consumption
•
AC
: Max. 15 VA
Voltage output
: 125 V max. (100 V AC/24 V DC)
8 A max. for the total of relay cards
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: JIS or EIA standard rack or surface
Weight
: 2.0 kg (4.8 lb) (AC power 2.2 kg (4.9 lb))
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
38D2-B1, B2, BY1, BY2
: 500 V AC @ 1 minute
(I/O connector to power to alarm output)
(For Azbil DCS, I/O connector or power to alarm)
1500 V AC @ 1 minute (I/O connector or power or alarm output to voltage output)
500 V AC @ 1 minute (1000 V AC for 24 V DC power input)
(I/O connector or power or alarm output to FG)
2000 V AC @ 1 minute (voltage output to FG)
MOUNTING REQUIREMENTS unit: mm [inch]
CONNECTION DIAGRAM
EXTERNAL DIMENSIONS unit: mm [inch]
I/O CONNECTOR PIN ASSIGNMENT