ES-7785 Rev.8
R6-NC1
Remote I/O R6 Series
CC-Link INTERFACE MODULE
(CC-Link Ver.1.10; for 16-point analog signals)
Functions & Features
• Free combination of analog and discrete I/O
• Direct sensor inputs
• Space-saving
• Low power consumption
Typical Applications
• Remote I/O for DCS and PLC
MODEL: R6-NC1[1]
ORDERING INFORMATION
• Code number: R6-NC1[1]
Specify a code from below for [1].
(e.g. R6-NC1/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
RELATED PRODUCTS
• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R6CON)
Downloadable at our web site.
PACKAGE INCLUDES...
• Terminating resistor (110 Ω, 0.5 W)
GENERAL SPECIFICATIONS
Connection
Network
: Euro type connector terminal
(applicable wire size: 0.2 to 2.5 mm
2
, stripped length
7 mm)
Internal bus
: Via the Installation Base (model: R6x-BS)
Internal
power
: Via the Installation Base (model: R6x-BS)
Max. number of I/O modules
: 16 (analog 16 points)
Isolation
: CC-Link to internal bus or internal power
RUN indicator:
Bi-color (green/red) LED; Green ON in normal communication; Red ON when receiving data (Function selected with DIP SW)
ERR indicator:
Bi-color (green/red) LED;
Green ON or blinking at communication error; Red ON at transmitting data (Function selected with DIP SW)
Data allocation
: Mode 1 or 2 set with the side DIP switch
CC-Link COMMUNICATION
Protocol
: CC-Link V1.10
Device type
: Remote device station
Required node
: 4 (RX, RY: 32 bit, RWw, RWr: 16 words)
Network cable
: CC-Link cable
Station No. setting
: Rotary switch; 1 – 64
Baud rate setting
: Rotary switch
156kbps, 625kbps, 2.5Mbps, 5Mbps, 10Mbps
INSTALLATION
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R6x-BS)
Weight
: 100 g (0.22 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @ 1 minute (CC-Link to internal bus or internal power)
STANDARDS & APPROVALS
Refer to the manuals to comply with the standards.
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
COMMUNICATION CABLE CONNECTIONS
TRANSMISSION DATA DESCRIPTIONS
The DIP SW located at the side of the module switches the unit’s data allocation mode.
In the Data Allocation Mode 1, one (1) word is assigned per module. The second channel of analog I/O modules cannot be used.
Max. 16 I/O modules can be connected in this mode.
In the Data Allocation Mode 2, two (2) words are assigned per module regardless of whether the second word area is required or not, even for discrete I/O modules that require one (1) word.
Max. 8 I/O modules can be connected in this mode.
I/O DATA DESCRIPTIONS
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM