ES-7792 Rev.6
R6-NP1
Remote I/O R6 Series
PROFIBUS-DP INTERFACE MODULE
(for 62-point analog signals)
MODEL: R6-NP1[1]
ORDERING INFORMATION
• Code number: R6-NP1[1]
Specify a code from below for [1].
(e.g. R6-NP1/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
RELATED PRODUCTS
• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R6CON)
Downloadable at our web site.
GENERAL SPECIFICATIONS
Connection
Network
: 9-pin D-sub connector, female
Internal bus
: Via the Installation Base (model: R6x-BS)
Power supply
: Via the Installation Base (model: R6x-BS)
Max. number of I/O modules
: 31 (analog 62 points)
Module address
: 1 to 31
Isolation
: PROFIBUS to internal bus or internal power
RUN indicator
: Bi-color (green/red) LED (refer to the instruction manual)
ERR indicator
: Bi-color (green/red) LED (refer to the instruction manual)
PROFIBUS COMMUNICATION
Interface
: PROFIBUS-DP, slave (RS-485 isolation)
Station No. setting
: Rotary switch; 00 - 7D
(Station No. is 7D even setting greater value)
Max. baud rate
: 12 Mbps
Protocol
: DPV1 (The following functions are available.)
Alarm function (Pull/Plug alarm, Status
alarm);
I&M function (I&M 0 through 3)
Transmission cable
: Approved for PROFIBUS-DP
GSD file
: Msys0C57.GSD
Downloadable at our web site
Input data
: Max. 124 bytes
Output data
: Max. 124 bytes
Total I/O data
: Max. 248 bytes
Diagnostics
: Module-related, Status (device-related), Channel-related (max. 32 channels, maskable)
INSTALLATION
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R6x-BS)
Weight
: 100 g (0.22 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @1 minute (PROFIBUS to internal bus or internal power)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
I/O DATA DESCRIPTIONS
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM