ES-8132 Rev.13
MDP-JS
Lightning Surge Protectors for
Electronics Equipment M-RESTER
LIGHTNING SURGE PROTECTOR FOR
SELF-SYNCH USE
Functions & Features
• Designed specifically for self-synchronizing motor circuit
• Protects self-synch transmitter and converter from damage caused by surges on the wiring
• Absorbs surges only without affecting instrumentation signal
• No interruption of signal by unplugging the protector element
MODEL: MDP–JS[1]
ORDERING INFORMATION
• Code number: MDP-JS[1]
Specify a code from below for [1].
(e.g. MDP-JS/A33/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] OPTIONS (multiple selections)
DIN Rail Mounting Adapter
blank
: Without
/A33
: With adapter (model A-33)
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
: M4 screw terminals (torque 0.8 N·m)
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (black)
INSTALLATION
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface or DIN rail
Weight
: 100 g (0.22 lb), standard; 125 g (0.28 lb), with DIN rail mounting adapter
PERFORMANCE
Max. continuous operating voltage
(Uc)
:
A to B to C: ±170 V
Line to earth: ±290 V
Voltage protection level (Up)
:
• @ 1 kV (100 A)
1 to 2 to 3: ±350 V
Line to earth: ±650 V
• @ 2 kV (1 kA)
1 to 2 to 3: ±450 V
Line to earth: ±800 V
Response time
: ≤ 0.1 μsec.
Leakage current
:
A to B to C: ≤ 50 μA @ ±170 V DC
Line to earth: ≤ 50 μA @ ±290 V DC
Max. discharge current (Imax)
: 5000 A (8 / 20 μs)
Nominal current (I
N
)
: 500 mA
Internal series resistance
: Approx. 2 Ω (per wire)
Rated line voltage
: 90 V AC
Capacitance @ 1 MHz
:
Line to line: ≤ 1.5 nF
Line to earth: ≤ 50 pF
Surge protection
: IEC 61643-21 Categories C1, C2, D1
CONNECTION EXAMPLES
GROUNDING
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
MOUNTING REQUIREMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM