ES-2777 Rev.2
M5XADS
Super-mini Terminal Block Signal Conditioners M5X-UNIT
ADDER
(PC programmable)
Functions & Features
• Receives two DC inputs and provides an output proportional to the addition of the inputs
• PC programmable
• High-density mounting
• Power LED
Typical Applications
• Adding two flow signals
MODEL: M5XADS-1-R[1]
ORDERING INFORMATION
• Code number: M5XADS-1-R[1]
Specify a code from below for [1].
(e.g. M5XADS-1-R
/Q)
• Specify the specification for option code /Q
(e.g. /C01/S01/SET)
INPUT 1 - Field-selectable
◆ DC Input
•
Current input
: 0 - 50 mA DC
•
Voltage
input
: -1000 - +1000 mV DC
•
Voltage
input
: -10 - +10 V DC
INPUT 2 - Field-selectable
◆ DC Input
•
Current input
: 0 - 50 mA DC
•
Voltage
input
: -1000 - +1000 mV DC
•
Voltage
input
: -10 - +10 V DC
EXTERNAL INTERFACE
◆ OUTPUT SIGNAL
1
: DC output (field-selectable)
• Current output: 0 - 20 mA DC
• Voltage output: -5 - +5 V DC
• Voltage output: -10 - +10 V DC
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
TERMINAL SCREW MATERIAL
/S01
: Stainless steel
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-2777)
RELATED PRODUCTS
• PC Configurator cable (model: COP-US)
• PC configurator software (model: M5CFG)
Downloadable at our web site.
GENERAL SPECIFICATIONS
Construction
: Terminal block
Connection
: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal
: Nickel-plated steel (standard) or stainless steel
Housing material
: Flame-resistant resin (black)
Isolation
: Input to output to power
Equation:
X
0
= K
0
{K
1
(X
1
+ A
1
) + K
2
(X
2
+ A
2
)} + A
0
X
1
- X
2
: input signal (%) -2 - +102 %
K
0
- K
2
: gain (no units) ±29.999
A
0
- A
2
: bias (%) ±299.99 %
Factory default setting
K
0
= 1, K
1
= 1, K
2
= 1, A
0
= 0 %, A
1
= 0 %, A
2
= 0 %
Power indicator LED
: Green LED; Blinking patterns indicate different operating status of the transmitter.
Parameters
: Stored in
non-volatile memory; w
rite/erase cycle endurance: less than 20 000
Programming
: Downloaded from PC;
• input type
• input range
• output type
• output range
• zero and span
• parameter
For detailed information, refer to the users manual for the PC configurator.
Configurator connection
: 2.5 dia. miniature jack;
RS-232-C level
INPUT SPECIFICATIONS
Standard default setting: DC current input 4 - 20 mA
Input type
•
DC current input: 0 - 50 mA DC
• DC voltage input: -1000 - +1000 mV DC
• DC voltage input: -10 - +10 V DC
(3 types can be switched for each input 1 and input 2 by DIP switch and PC)
■
DC Current
Input resistance
: Incorporated (15.5 Ω)
Input range
: 0 - 50 mA DC
Measurable range
: 0 – 52.5 mA DC
Minimum span
: 2 mA DC
Offset
: Lower range can be any specific value within the input range provided that the minimum span is maintained.
■
DC Voltage
Input range
• S1: -1000 - +1000 mV DC
• S2: -10 - +10 V DC
Measurable range
• S1: -1100 - +1100 mV DC
• S2: -11 - +11 V DC
Minimum span
:
• S1: 100 mV DC
• S2: 1 V DC
Offset
: Lower range can be any specific value within the input range provided that the minimum span is maintained.
If not specified, the input range is shown below.
Input resistance
• S1: ≥ 100 kΩ
• S2: ≥ 1 MΩ
OUTPUT SPECIFICATIONS
Standard default setting: DC current output 4 - 20 mA
Output type
• DC current output: 0 - 20 mA DC
• DC voltage output: -10 - +10 V DC
• DC voltage output: -5 - +5 V DC
(3 types can be switched by DIP switch and PC)
■ DC Current
: 0 – 20 mA DC
Output range:
0 - 23 mA DC
Minimum span
: 1 mA
Load resistance
: 550 Ω
■
DC Voltage
•
Output range -10 - +10 V DC
Voltage range
:
-11.5 – +11.5 V DC
Minimum span
: 1 V
Load resistance
: Output drive 1 mA max.
(ex. 0 - 10 V DC: 10 V ÷ 1 mA = 10 kΩ)
•
Output range -5 - +5 V DC
Voltage range
: -5.75 – +5.75 V DC
Minimum span
: 500 mV
Load resistance
: Output drive 1 mA max.
(ex. 1 - 5 V DC: 5 V ÷ 1 mA = 5000 Ω)
INSTALLATION
Power consumption:
≤ 1W
Operating temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail
Weight
: 80 g (2.8 oz)
PERFORMANCE in percentage of span
Input accuracy (% of max. input range):
±0.01 %
(±0.02 % for current input)
Output accuracy
(% of max. output range):
±0.02 %
(±0.04 % for current output)
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F) of max. span
Response time
: ≤ 500 msec. (0 – 90 %)
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @1 minute (input to output to power to ground)
ACCURACY AND CALCULATION EXAMPLES
■
Overall Accuracy
The accuracy includes input accuracy, which converts the sensor input into a digital value, and output accuracy, which converts the digital value into an analog signal.
The accuracy of the device is the total of the input accuracy and the output accuracy.
Input accuracy
Input accuracy for the setting value span is shown as following formula.
Input accuracy = (input range ÷ input setting value span) × 0.01 %
For current input,
Input accuracy = (input range ÷ input setting value span) × 0.02 %
(Use the larger one when input 1 accuracy and input 2 accuracy are different.)
Output accuracy
Output accuracy for the setting value span is shown as following formula.
Output accuracy = (output range ÷ output setting value span) × 0.02 %
For current output,
Output accuracy = (output range ÷ output setting value span) × 0.04 %
Calculation examples
The overall accuracy is ±0.1 % when following setting.
K
0
= 0.5, K
1
= K
2
= 1, A
0
= A
1
= A
2
= 0 %
Input 1: input range -10 - +10 V, input setting value span
0 - 5 V
Input 2: input range 0 - 50 mA, input setting value span
0 - 20 mA
Output: output range 0 - 20 mA, output settin value span
4 - 20 mA
Input 1 accuracy = (20 V ÷ 5 V) × 0.01 % = 0.04 %
Input 2 accuracy = (50 mA ÷ 20 mA) × 0.02 % = 0.05 %
Output accuracy = (20 mA ÷ 16 mA) × 0.04 % = 0.05 %
Input 2 accuracy (0.05 %) is larger than input 1 accuracy (0.04 %), the overall accuracy is input accuracy 0.05 % + output accuracy 0.05 % = 0.1 %.
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
Refer to the instruction manual for the setting procedure.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM