ES-5044 Rev.20
M2PV
Super-mini Signal Conditioners Mini-M Series
P/I TRANSDUCER
Functions & Features
• Converts a standard pneumatic signal into a
proportional DC output
Typical Applications
• Converting a pneumatic system into a 4 – 20 mA for indicating and controlling in DCS system
MODEL: M2PV–C[1][2]–[3][4]
ORDERING INFORMATION
• Code number: M2PV-C[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
(e.g. M2PV-C2SA-M2/CE/Q)
• Special output range (For codes Z & 0)
• Specify the specification for option code /Q
(e.g. /C01/S01)
PNEUMATIC CONNECTION
C
: 6 mm dia. (.24”)
[1] INPUT
1S
: 19.6 – 98.1 kPa
2S
: 20 – 100 kPa
3S
: 20.7 – 103.4 kPa
1
: 0.2 – 1.0 kgf/cm
2
2
: 0.2 – 1.0 bar
3
: 3 – 15 psig
[2] OUTPUT
Current
A
: 4 – 20 mA DC (Load resistance 750 Ω max.)
B
: 2 – 10 mA DC (Load resistance 1500 Ω max.)
C
: 1 – 5 mA DC (Load resistance 3000 Ω max.)
D
: 0 – 20 mA DC (Load resistance 750 Ω max.)
E
: 0 – 16 mA DC (Load resistance 900 Ω max.)
F
: 0 – 10 mA DC (Load resistance 1500 Ω max.)
G
: 0 – 1 mA DC (Load resistance 15 kΩ max.)
Z
: Specify current (See OUTPUT SPECIFICATIONS)
Voltage
1
: 0 – 10 mV DC (Load resistance 10 kΩ min.)
2
: 0 – 100 mV DC (Load resistance 100 kΩ min.)
3
: 0 – 1 V DC (Load resistance 1000 Ω min.)
4
: 0 – 10 V DC (Load resistance 10 kΩ min.)
5
: 0 – 5 V DC (Load resistance 5000 Ω min.)
6
: 1 – 5 V DC (Load resistance 5000 Ω min.)
0
: Specify voltage (See OUTPUT SPECIFICATIONS)
[3] POWER INPUT
AC Power
M
: 85 – 264 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
(Select ‘/N’ for ‘Standards & Approvals’ code.)
M2
: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
(90 – 264 V for UL)
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
R2
: 11 – 27 V DC
(Operational voltage range 11 – 27 V, ripple 10 %p-p max.)
(Select ‘/N’ for ‘Standards & Approvals’ code.)
P
: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
(110 V ±10 % for UL)
[4] OPTIONS (multiple selections)
Standards & Approvals (must be specified)
/N
: Without CE or UL
/CE
: CE marking
/UL
: UL approval, CE marking
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating (UL not available)
/C04
: Polyolefin coating (UL not available)
TERMINAL SCREW MATERIAL
/S01
: Stainless steel (UL not available)
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
Output & power input
: M3 screw terminals (torque 0.8 N·m)
Pneumatic
: 6 mm dia (.24”) tube
Screw terminal
: Chromated steel (standard) or stainless steel
Housing material
: Flame-resistant resin (black)
Isolation
: Output to power
Overrange output
: Approx. -10 to +120 % at 1 – 5 V
Zero adjustment
: -5 to +5 % (front)
Span adjustment
: 95 to 105 % (front)
INPUT SPECIFICATIONS
■
Input
19.6 – 98.1 kPa, 0.2 – 1.0 kgf/cm
2
20 – 100 kPa, 0.2 – 1.0 bar
20.7 – 103.4 kPa, 3 – 15 psig
OUTPUT SPECIFICATIONS
■ DC Current
: 0 – 20 mA DC
Minimum span
: 1 mA
Offset
: Max. 1.5 times span
Load resistance
: Output drive 15 V max.
■
DC Voltage
: 0 – 12 V DC
Minimum span
: 5 mV
Offset
: Max. 1.5 times span
Load resistance
: Output drive 1 mA max.; at ≥ 1 V
INSTALLATION
Power Consumption
•
AC
:
Approx. 3 VA at 100 V
Approx. 4 VA at 200 V
Approx. 5 VA at 264 V
•
DC
: Approx. 3 W
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface or DIN rail
Weight
: 150 g (0.33 lb)
PERFORMANCE in percentage of span
Accuracy
: ±0.3 %
Temp. coefficient
: ±0.03 %/°C (±0.02 %/°F)
Response time
: ≤ 0.5 sec. (0 – 90 %)
Permissible overrange
: 196 kPa (2.0 kgf/cm
2
, 1.96 bar, 28 psig)
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @ 1 minute (output to power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Installation Category II
Pollution Degree 2
Output to power: Reinforced insulation (300 V)
RoHS Directive
Approval
:
UL/C-UL nonincendive Class I, Division 2,
Groups A, B, C, and D
(UL 121201, CAN/CSA-C22.2 No.213-17)
UL/C-UL general safety requirements
(UL 61010-1, CAN/CSA-C22.2 No.61010-1-12)
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]