ES-5096 Rev.15
M2RTS
Super-mini Signal Conditioners Mini-M Series
RATIO/BIAS TRANSMITTER
(input bias)
Functions & Features
• Provides precise matching of DC control signals to final control elements in open- or closed-loop systems
• Easy ratio/bias setting with the front digital display
• Ratio adjustable from 0.1 to 4.00 or from -0.1 to -4.00; Bias adjustable to ±100 %
Typical Applications
• Ratio control for air/fuel flows or for two flows
• Gain calculation for manipulated variable from a controller
• Large scale signal span adjustment
MODEL: M2RTS-[1]-[2][3]-[4][5]
ORDERING INFORMATION
• Code number: M2RTS-[1]-[2][3]-[4][5]
Specify a code from below for each of [1] through [5].
(e.g. M2RTS-S-6A-M2/CE/Q)
• Special input and output ranges (For codes Z & 0)
• Specify the specification for option code /Q
(e.g. /C01/S01)
[1] OUTPUT CHARACTERISTICS
S
: Proportional; ratio 0.1 to 4.00
R
: Inverted; ratio -0.1 to -4.00
[2] INPUT
Current
A
: 4 – 20 mA DC (Input resistance 250 Ω)
A1
: 4 – 20 mA DC (Input resistance 50 Ω)
B
: 2 – 10 mA DC (Input resistance 500 Ω)
C
: 1 – 5 mA DC (Input resistance 1000 Ω)
D
: 0 – 20 mA DC (Input resistance 50 Ω)
E
: 0 – 16 mA DC (Input resistance 62.5 Ω)
F
: 0 – 10 mA DC (Input resistance 100 Ω)
G
: 0 – 1 mA DC (Input resistance 1000 Ω)
H
: 10 – 50 mA DC (Input resistance 100 Ω)
K
: 0 – 100 μA DC (Input resistance 1000 Ω)
GW
: -1 – +1 mA DC (Input resistance 1000 Ω)
FW
: -10 – +10 mA DC (Input resistance 100 Ω)
Z
: Specify current (See INPUT SPECIFICATIONS)
Voltage
2
: 0 – 100 mV DC (Input resistance 100 kΩ min.)
3
: 0 – 1 V DC (Input resistance 1 MΩ min.)
4
: 0 – 10 V DC (Input resistance 1 MΩ min.)
5
: 0 – 5 V DC (Input resistance 1 MΩ min.)
6
: 1 – 5 V DC (Input resistance 1 MΩ min.)
4W
: -10 – +10 V DC (Input resistance 1 MΩ min.)
5W
: -5 – +5 V DC (Input resistance 1 MΩ min.)
0
: Specify voltage (See INPUT SPECIFICATIONS)
[3] OUTPUT
Current
A
: 4 – 20 mA DC (Load resistance 750 Ω max.)
B
: 2 – 10 mA DC (Load resistance 1500 Ω max.)
C
: 1 – 5 mA DC (Load resistance 3000 Ω max.)
D
: 0 – 20 mA DC (Load resistance 750 Ω max.)
E
: 0 – 16 mA DC (Load resistance 900 Ω max.)
F
: 0 – 10 mA DC (Load resistance 1500 Ω max.)
G
: 0 – 1 mA DC (Load resistance 15 kΩ max.)
Z
: Specify current (See OUTPUT SPECIFICATIONS)
Voltage
1
: 0 – 10 mV DC (Load resistance 10 kΩ min.)
2
: 0 – 100 mV DC (Load resistance 100 kΩ min.)
3
: 0 – 1 V DC (Load resistance 1000 Ω min.)
4
: 0 – 10 V DC (Load resistance 10 kΩ min.)
5
: 0 – 5 V DC (Load resistance 5000 Ω min.)
6
: 1 – 5 V DC (Load resistance 5000 Ω min.)
4W
: -10 – +10 V DC (Load resistance 10 kΩ min.)
5W
: -5 – +5 V DC (Load resistance 5000 Ω min.)
0
: Specify voltage (See OUTPUT SPECIFICATIONS)
[4] POWER INPUT
AC Power
M2
: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
(90 – 264 V for UL)
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
R2
: 11 – 27 V DC
(Operational voltage range 11 – 27 V, ripple 10 %p-p max.)
(Select ‘/N’ for ‘Standards & Approvals’ code.)
P
: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
(110 V ±10 % for UL)
[5] OPTIONS (multiple selections)
Standards & Approvals (must be specified)
/N
: Without CE or UL
/CE
: CE marking
/UL
: UL approval, CE marking
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating (UL not available)
/C04
: Polyolefin coating (UL not available)
TERMINAL SCREW MATERIAL
/S01
: Stainless steel (UL not available)
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
: M3 screw terminals (torque 0.8 N·m)
Screw terminal
: Chromated steel (standard) or stainless steel
Housing material
: Flame-resistant resin (black)
Isolation
: Input to output to power
Overrange output
: Approx. -10 to +120 % at 1 – 5 V
Ratio adjustment
Proportional
: 0.10 to 4.00; 0.01 increments
Inverted
: -0.10 to -4.00; 0.01 increments
Bias adjustment
: -100 to +100 %; 1 % increments
Ratio/bias selector
: Double-throw SW (front)
UP/DOWN control
: Double-throw, momentary SW (front)
Equation
:
X
o
=
K
(
X
i
+
B)
(proportional)
X
o
=
K
(
X
i
+
B
) + 100 % (inverted)
where
X
o
: Output (%)
K
: Ratio
Linear characteristics
0.1 to 4.00 (proportional)
-0.1 to -4.00 (inverted)
X
i
: Input (approx. -10 to +120 %)
B
: Bias (-100 to +100 %)
■
INDICATORS
Ratio/bias digital display
: Red LED; 6.4 mm (.25”) 7 segment, 3 digits
Polarity indicator
: Dual color (red/green) LED; Red with a positive set value; Green with a negative set value.
Power saving mode
: Indicators turn off if the switches are untouched for 1 minute.
INPUT SPECIFICATIONS
■
DC Current
:
Shunt resistor attached to the input terminals (0.5 W)
Specify input resistance value for code Z.
■
DC Voltage
: -30 – +30 V DC
Minimum span
: 100 mV
Offset
: Max. 1.5 times span
•
Input resistance
Span 0.1 – 1 V : ≥ 100 kΩ
Span ≥ 1 V : ≥ 1 MΩ
OUTPUT SPECIFICATIONS
■ DC Current
: 0 – 20 mA DC
Minimum span
: 1 mA
Offset
: Max. 1.5 times span
Load resistance
: Output drive 15 V max.
■
DC Voltage
: -10 – +12 V DC
Minimum span
: 5 mV
Offset
: Max. 1.5 times span
Load resistance
: Output drive 1 mA max.; at ≥ 0.5 V
INSTALLATION
Power Consumption
•
AC
:
Approx. 3 VA at 100 V
Approx. 4 VA at 200 V
Approx. 5 VA at 264 V
•
DC
: Approx. 3 W
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface or DIN rail
Weight
: 150 g (0.33 lb)
PERFORMANCE in percentage of span
Accuracy
: ±0.2 %
Ratio = 1, Bias = 0 % (proportional)
Ratio = -1, Bias = 0 % (inverted)
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: ≤ 0.5 sec. (0 – 90 %)
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @1 minute (input to output to power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Installation Category II
Pollution Degree 2
Input or output to power: Reinforced insulation (300 V)
Input to output: Basic insulation (300 V)
RoHS Directive
Approval
:
UL/C-UL nonincendive Class I, Division 2,
Groups A, B, C, and D
(UL 121201, CAN/CSA-C22.2 No.213-17)
UL/C-UL general safety requirements
(UL 61010-1, CAN/CSA-C22.2 No.61010-1-12)
EXTERNAL VIEW
•
How to Set the Ratio
Turn the Ratio/Bias Selector (C) to the top.
The Ratio/Bias Display (B) shows the current ratio (0.10 – 4.00). Press UP/DOWN Control (D) until the display shows a desired set value.
The Polarity Indicator LED (A) is red when the set value is in positive range, green when in negative range.
•
How to Set the Bias
Turn the Ratio/Bias Selector (C) to the bottom.
The Ratio/Bias Display (B) shows the current bias (0 – 100%). Press UP/DOWN Control (D) until the display shows a desired set value.
The Polarity Indicator LED (A) is red when the set value is in positive range, green when in negative range.
•
Fine Calibration
Equation:
Xo
=
K
(
Xi
+
B
) (proportional)
Xo
=
K
(
Xi
+
B)
+ 100 % (inverted)
1) Calculate the input signal
Xi
which results in 0 % output.
Apply the calculated input and adjust with Zero Adj. (E) the output
Xo
to 0 %.
2) Calculate the input signal
Xi
which results in 100 % output. Apply the calculated input and adjust with Span Adj. (E) the output
Xo
to 100 %.
3) Apply the calculated zero point input again and check the output
Xo
.
4) If the output has been shifted, go through (1) through (3) again.
The unit is factory set and calibrated to the following ratio and bias values.
Proportional characteristics
: ratio (
K
) = 1, Bias (
B
) = 0 %
Inverted characteristics
: ratio (
K
) = -1, Bias (
B
) = 0 %
EXTERNAL DIMENSIONS unit: mm [inch]
TERMINAL ASSIGNMENTS unit: mm [inch]