ES-7772-J Rev.0
R7G4HML3-6-SVAF4
Remote I/O R7G4H Series
MECHATROLINK I/O MODULE
(high resolution, high-speed DC voltage/current input, 4 points, isolated, screw terminal block, MECHATROLINK- III use)
Functions & Features
• 4 points high-speed DC voltage/current input for MECHATROLINK- III
• Easy parameter setting of individual channels with the configurator software
MODEL: R7G4HML3-6-SVAF4–R[1]
ORDERING INFORMATION
• Code number: R7G4HML3-6-SVAF4-R[1]
Specify a code from below for [1].
(e.g. R7G4HML3-6-SVAF4-R/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
TERMINAL BLOCK
6
: Screw terminal block for power supply
Connector for MECHATROLINK- III
Screw terminal block for I/O
I/O TYPE
SVAF4
: high resolution, high-speed DC voltage/current input,
4 points (10 V/20 mA)
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[1] OPTIONS
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-7772-J)
RELATED PRODUCTS
• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R7CFG)
Downloadable at our web site.
GENERAL SPECIFICATIONS
Connection
MECHATROLINK-III
: MECHATROLINK-III connector
Power input, input
: M3 separable screw terminal (torque 0.5 N·m)
Solderless terminal
: Refer to the drawing at the end of the section.
Recommended manufacturer
: Japan Solderless Terminal MFG.Co.Ltd, Nichifu Co.,ltd
Applicable wire size
: 0.25 to 1.65 mm
2
(AWG 22 to 16)
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (gray)
Isolation
: Input 0 to input 1 to input 2 to input 3 to MECHATROLINK or FE to power
Zero adjustments
: Configurable via R7CFG
Span adjustments
: Configurable via R7CFG
Input range
: Configurable via R7CFG
Number of times of averaging
: Configurable via R7CFG
Status indicator LEDs
: PWR, ERR, CON, LNK1, LNK2
(Refer to the instruction manual for details)
■Recommended solderless terminal
MECHATROLINK-III COMMUNICATION
Baud rate
: 100 Mbps
Transmission distance
: 6300 m max.
Distance between stations
: 100 m max.
Transmission media
: MECHATROLINK cable (Model JEPMC-W6013-x-E, Yaskawa Controls Co., Ltd.)
Connector
: TYCO AMP Industrial mini I/O connector
Max. number of slaves
: 62
(The maximum number of slaves might change depending on the master unit. Refer to the manual of the master unit)
Transmission cycle
: 125 µsec., 250 µsec., 500 µsec., 1 – 64 msec. (with 1 msec. increments)
Communication cycle
: 125 µsec. through 64 msec.
Applicable profile
: Standard I/O profile (cyclic communication)
Event-driven communication acquiring ID profile (event-driven communication)
Transmission
bytes
: 16 bytes
Station address
: 03H through EFH (set with rotary switches)
Cyclic communication
: Available
Event-driven communication
: Available
Slave monitoring
: None
INPUT SPECIFICATIONS
■ Current range
• Input resistance:
50Ω
• Operational range:
-23- +23mA
• Input range:
-20 – +20 mA DC, 0 – 20 mA DC,
4 – 20 mA DC
■ Narrow span voltage
• Input resistance:
≧ 100 kΩ
• Operational range:
-1.15- +1.15V
• Input range:
-1 – +1 V DC, 0 – 1 V DC,
-0.5 – +0.5 V DC
■ Wide span voltage
• Input resistance:
≧ 1 MkΩ
• Operational range:
-11.5 - +11.5V
• Input range:
-10 – +10 V DC, -5 – +5 V DC,
0 – 10 V DC, 0 – 5 V DC, 1 – 5 V DC
INSTALLATION
Current consumption
•
DC
: Approx. 100 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Surface or DIN rail (35 mm rail)
Weight
: 220 g (0.49 lb)
PERFORMANCE
Conversion accuracy
: ±0.1 %
Conversion rate
: 1 msec. / 4 CH
Conversion data:
-32768 - +32767 or 0 - 65535
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Input delay time
: ≤ 1 msec. (0 - 90 %)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength:
1500 V AC @ 1 minute
(input 0 to input 1 to input 2 to input 3 MECHATROLINK or FE to power)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
PC CONFIGURATOR
The following parameters can be set with using PC Configurator Software (model: R7CFG)
Refer to the users manual for the R7CFG for detailed operation of the software program.
EXTERNAL VIEW
TERMINAL ASSIGNMENTS
■ INPUT TERMINAL ASSIGNMENT
■ POWER SUPPLY TERMINAL ASSIGNMENT
MECHATROLINK RELATED COMMANDS
DATA CONVERSION
RESPONSE TIME
Response time of analog input module is time from when 0 to 100% stepwise signal change is applied to the analog module till when the communication ASIC of the module (slave) transmits 90% of input signal.
T
COM
: MECHATROLINK-III transmission cycle set at master
(depends on system and configuration)
T
INP
: Input module response time ≤ Input Delay time (Ta) + Conversion rate
*1
(Tb) + input internal processing delay time (Tc) (two transmission cycle)
*1. Conversion rate × Averaging
E.g.: Averaging (1), transmission cycle of 0.5 msec.
Input module response time (T
INP
): Input Delay time (1 msec.) + Conversion rate (1 msec.) × Averaging (1)
+ internal processing delay time (0.5 msec. x 2) = 3.0 [msec.]
I/O DATA DESCRIPTIONS
Scaling of analog input module is configurable with the configurator software (model: R7CFG). Refer to the software manual for details.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
MOUNTING REQUIREMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FE terminal to ground.
Caution: FE terminal is NOT a protective conductor terminal.