ES-9321 Rev.6

48SV

Bargraph Indicators 48 Series

BARGRAPH INDICATOR

Functions & Features
• Displaying a process variable in graphic bargraph of 51 LED segments
• Small size
• High-density mounting

MODEL: 48SV–1R[1][2]-[3]

ORDERING INFORMATION

• Code number: 48SV-1R[1][2]-[3]
Specify a code from below for each of [1] through [3].
  (e.g. 48SV-1RVA-T)

BARGRAPHS

1: Single

BAR LED COLOR

R: Red

[1] MOUNTING DIRECTION

V: Vertical
H: Horizontal

[2] INPUT

Current
A: 4 – 20 mA DC (Input resistance 5.1Ω)
G: 0 – 1 mA DC (Input resistance 100 Ω)
Voltage
3: 0 – 1 V DC (Input resistance 200 kΩ)
5: 0 – 5 V DC (Input resistance 160 kΩ)
6: 1 – 5 V DC (Input resistance 160 kΩ)

[3] POWER INPUT

DC Power
T: 5 V DC
(Operational voltage range 5 V ±10 %, ripple 10 %p-p max.)
R: 24 V DC
(Operational voltage range 24 V ±15 %, ripple 10 %p-p max.)

GENERAL SPECIFICATIONS

Construction: Panel flush mounting
Connection: Connector (leadwires soldered)
Housing material: ABS resin
Isolation: Input to power
Scale plate: Aluminium (white scale & characters on black base)
Indicator: LED
No. of LED segments: 52 including over-range indicator “1”
Scale length: 50 mm (1.97”)
Scale: 0 - 100 %

INSTALLATION

Power consumption
DC: ≤ 1.5 W
Operating temperature: 0 to 50°C (32 to 122°F)
Operating humidity: 40 to 80 %RH (non-condensing)
Mounting: Panel flush mounting
Weight: 90 g (0.2 lb)

PERFORMANCE in percentage of span

Accuracy: ±2 %
Response time: 0.5 sec.
Insulation resistance: ≥ 50 MΩ with 500 V DC
(input or power to ground)
Dielectric strength: 2000 V AC @1 minute (input or power to ground)
500 V AC @ 1 minute (input to power)

CONNECTION DIAGRAM

EXTERNAL DIMENSIONS unit: mm [inch]

PANEL CUTOUT unit: mm [inch]