ES-9663 Rev.0
R8-WTU
Remote I/O R8 Series
MULTI POWER INPUT MODULE
(clamp-on current sensor type CLSE use)
Functions & Features
• 5 to 600 A clamp CT use for current sensor
• Single-phase/2-wire, single-phase/3-wire, 3-phase/3-wire and 3-phase/4-wire are available
• Single phase can measure up to four circuits, single-phase/3-wire and three-phase/3-wire can measure up to two circuits
MODEL: R8-WTU22[1]
ORDERING INFORMATION
• Code number: R8-WTU22[1]
Specify a code from below for [1].
(e.g. R8-WTU22/Q)
• Specify the specification for option code /Q
(e.g. /C01)
CONFIGURATION
2
: Single phase / 2-wire and 3-wire,
3-phase / 3-wire and 4-wire
INPUT
2
: 480 V AC / CLSE
Clamp-on current sensor is selectable from below.
CLSE (5A, 50A, 100A, 200A, 400A, 600A)
5A is available as CT's secondary.
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
RELATED PRODUCTS
• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R8CFG)
Downloadable at our web site.
• Clamp-on current sensor (model: CLSE)
Note: When using with Power/Network module (model: R8-NECT1), firmware version Ver2.01 or later is supported.
GENERAL SPECIFICATIONS
Connection
•
Input
: Tension clamp
Applicable wire size
: 0.2 - 1.5 mm
2
Stripped length
: 10 mm
•
Excitation supply, internal bus
:
Connected to internal bus connector
•
Internal power
: Via internal bus connector
Isolation
: Voltage input or current input to internal bus or internal power
Measured variables
Voltage
: 1-N, 2-N, 3-N, 1-2, 2-3, 3-1
Current
: 1, 2, 3, N
Active power
Reactive power
Apparent power
Power factor
Frequency
Active energy
: Incoming / outgoing
Reactive energy
: Incoming / outgoing / lag (inductive)
/lead (capacitive)
Harmonic distortion:
Overall distortion ratio, content rate (2nd to 31st)
Max. and min. values
CO
2
emissions (energy conversion value)
Simplified measurement mode:
Calculates power from current values with fixed voltage values and power factor.
Measured variables data
Each measured variable can be set with 1 or 2 words using the configurator. (16 words can be used in total.)
Module address
: With DIP switch
Terminating resistor
: Built-in (DIP Switch, default: disable)
Status indicator
: Bi-color (red/green) LED; Refer to the instruction manual.
Input status indicator
: Red LED; Refer to the instruction manual.
INPUT SPECIFICATIONS
Frequency
: 50 / 60 Hz (45 – 66 Hz)
•
Voltage Input
Rated voltage for each wiring
:
• Single-phase/2-wire rated voltage 240 V AC
• Single-phase/3-wire phase voltage 240 V AC / line voltage 480 V AC
• Three-phase/3-wire line voltage 240 V AC
(480 V AC when voltage to ground for each line is ≤ 277 V)
• Three-phase/4-wire phase voltage 277 V / line voltage 480 V AC
Input range
: 1-N, 2-N, 3-N 50 to 277 V AC
1-2, 2-3, 3-1 50 to 480 V AC
Consumption VA:
Voltage circuit ≤ ULN
2
/ 250 kΩ / ph
Selectable primary voltage range
: 50 – 400 000 V
•
Current Input
Current sensor (default: CLSE-R5)
CLSE-R5
: 0 – 5 A AC
CLSE-05
: 0 – 50 A AC
CLSE-10
: 0 – 100 A AC
CLSE-20
: 0 – 200 A AC
CLSE-40
: 0 – 400 A AC
CLSE-60
: 0 – 600 A AC
Input range:
0 - 120 % of the rating
Low-end cutout (current):
0 - 99.9 % (default setting: 1 %)
Selectable primary current range
: 1 – 20 000 A (only with CLSE-R5, refer to the configurator settings)
INSTALLATION
Max. current consumption
: 100 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail
Weight
: 110 g (0.24 lb)
PERFORMANCE
Input Accuracy
*1
Voltage
: ±0.5 %
*2
Current
: ±0.5 %
*2
Power
: ±0.5 %
*2
Power factor
: ±1.5 %
Frequency
: ±0.1 Hz
Energy
: ±2 % (power factor ≥ 0.5, input ≥ 10%)
*1. Sensor error margin not included. Add sensor error margin when using with the combination of the sensor.
*2. An accuracy for rated input. The described accuracy levels are ensured at the input 1% or more for neutral current in a single-phase/3-wire circuit, phase-2 current in a 3-phase/3-wire circuit and phase-N current in a 3-phase/4-wire circuit.
Data allocation
: 2
Module addresses in use
: 8
Temp. coefficient:
±0.0075 %/°C (0.004 %/°F)
Sampling time
: ≤ 500 msec.
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
:
1500 V AC @ 1 minute (voltage input or current input to internal bus or internal power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1, EN 61010-2-201
Measurement Category II (input)
Pollution Degree 2
Voltage input to current input or internal bus or internal power:
Reinforced insulation (300 V)
RoHS Directive
EXTERNAL VIEW
TERMINAL CONNECTIONS
OPERATING MODE SETTING
(
*
) Factory setting
Note: Be sure to set unused SW1-7 to OFF.
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM