ES-4561-H1 Rev.0

38N-B

DCS Input/Output Relay Card Series

STANDARD RACK

Functions & Features
• The Standard Rack (Nest) model 38N can accept at the maximum of 16 channels of inputs and outputs
 

MODEL: 38N-B[1][2]

ORDERING INFORMATION

• Code number: 38N-B[1][2]
Specify a code from below for each of [1] and [2].
  (e.g. 38N-BH1/W)

[1] CONNECTOR

H1: Hitachi DCS connector
Y1: Yokogawa KS2 cable use connector
We guarantee the connecting section.

[2] OPTIONS

Mounting Bracket
blank: Rack mounting, standard
/W: Surface mounting

GENERAL SPECIFICATIONS

Construction: Metal plates assembly
Coating: Black Zn-Cr
Capacity: 16 positions
Connection
  Power input
: M3.5 screw terminals (torque 0.8 N·m; one for all 16 channels)
  Alarm output: M3.5 screw terminals (torque 0.8 N·m; one for all 16 channels)
  DCS I/O: Connector
Screw terminal: Nickel-plated brass
Isolation: I/O connector to alarm output to power for voltage output to power supply to metal frame

INSTALLATION

Power input
DC: 24 V DC ±10 % (ripple 10 %p-p max.)
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: JIS or EIA standard rack or surface
Weight: Approx. 2.5 kg (5.51 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1000V AC @1 minute (I/O connector to alarm output to power for voltage output to power supply to metal frame)

MOUNTING REQUIREMENTS unit: mm [inch]

CONNECTION DIAGRAM

EXTERNAL DIMENSIONS unit: mm [inch]

I/O CONNECTOR PIN ASSIGNMENT